Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: WORLD CLASS PRECISION PRODUCTS

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of WORLD CLASS PRECISION PRODUCTS in 36600 COUNTY ROAD J, BAYFIELD, WI 54814 (NAICS 332710). OSHA activity number 342345139.

Watch World Class Precision Products — free Get an email when a new federal OSHA severe-injury report for World Class Precision Products is published. One employer, no account, unsubscribe in one click.
Site address
36600 COUNTY ROAD J
City
BAYFIELD
State
WI
ZIP
54814
Mailing
36600 COUNTY ROAD J, BAYFIELD, WI 54814
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332710
Employees
15
Ownership type
A

5 citations on file for this inspection.

1910.147 C04 I

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $5070.00 · Current $3550.00 Reduced
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section:    (a) Throughout the facility; The employer did not develop specific procedures to isolate energy sources of machines during servicing and maintenance.
Recent events (2)
  • — I (S) $3550
  • — Z (S) $5070

1910.147 C07 I

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.147(c)(7)(i): The employer did not provide training to ensure that the purpose and function of the energy control program are understood by employees and that the knowledge and skills required for the safe application, usage, and removal of the energy controls are acquired by employees.  (a) Throughout the facility; The employer did not provide adequate training on the hazardous energy control program.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.147 D03

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $5070.00 · Current $3550.00 Reduced
29 CFR 1910.147(d)(3): All energy isolating devices that are needed to control the energy to the machine or equipment were not physically located and operated in such a manner as to isolate the machine or equipment from the energy sources:    (a)Throughout the facility; All energy isolating devices were not physically located and operated in such a manner as to isolate the machine or equipment from the energy sources during cleaning, servicing and maintenance activities.
Recent events (2)
  • — I (S) $3550
  • — Z (S) $5070

1910.147 D04 I

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.147(d)(4)(i): Lockout or tagout devices were not affixed to each energy isolating device by authorized employees:  (a) Throughout the facility; Authorized employees did not affix an energy control device while performing cleaning, servicing and maintenance activities to machines such as but not limited to the SKT 300 CNC turning center serial # G3158-0244.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G02 III

Other-than-serious 1 instance 15 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:  (a) North west end of production floor; The yellow extension cord powering the overhead hoist had damaged strain relief.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342345139.