TONAWANDA, NY —
OSHA Inspection: PEROXYCHEM TONAWANDA PLANT
Unprogrammed Related inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Related safety inspection of PEROXYCHEM TONAWANDA PLANT in 35 SAWYER AVENUE, TONAWANDA, NY 14150 (NAICS 325180). OSHA activity number 342413408.
Where did this inspection happen?
- Establishment
- PEROXYCHEM TONAWANDA PLANT
- Site address
- 35 SAWYER AVENUE
- City
- TONAWANDA
- State
- NY
- ZIP
- 14150
- Mailing
- 35 SAWYER AVENUE, TONAWANDA, NY 14150
What kind of inspection was it?
- Inspection type
- Unprogrammed Related (G)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 325180
- Employees
- 91
- Ownership type
- A
Citations
2 citations on file for this inspection.
5(a)(1)
- Issued
- Abate by
- Penalty
- Initial $12675.00 · Current $8500.00 Reduced
General-duty citation text
OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees
Recent events (3)
- — J (S) $8500
- — C (S) $12675
- — Z (S) $12675
1910.269 M03 II
- Issued
- Penalty
- Initial $12675.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.269(m)(3)(ii): The employer did not ensure that all switches, disconnectors, jumpers, taps, and other means through which known sources of electric energy may be supplied to the particular lines and equipment to be denenergized were open. The employer did not render such means inoperable, unless its design does not so permit, and then sure that such means are tagged to indicate that employees are at work: a) On or about 05/18/17 at the PeroxyChem substation located at 78 Sawyer Avenue, Tonawanda, New York; employees were performing preventative maintenance on the breakers in the substation. While preparing to work on breaker #6, an employee contacted live equipment and suffered burns and fractures. Switch #10 was left closed causing a backfeed from breaker #2 to breaker #6. NO ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — J (S) $0
- — C (S) $12675
- — Z (S) $12675
More inspections in this industry (NAICS 325180)
LA PORTE, TX—2026-07-07
OXY VINYLS, LP
JEFFERSONVILLE, IN—2026-07-06
DALLAS GROUP OF AMERICA
DONALDSONVILLE, LA—2026-06-24
CF INDUSTRIES NITROGEN
ODESSA, TX—2026-05-20
LIBERTYSTREAM INFRASTRUCTURE PARTNERS INC.
MULBERRY, FL—2026-05-01
ARRMAZ PRODUCTS INC.
More inspections in NY
POUGHKEEPSIE, NY—2026-07-13
MARCO BOARD HOUSE, INC.
CORTLANDT MANOR, NY—2026-07-13
LG BUILDERS INC.
CORTLANDT MANOR, NY—2026-07-13
RJW RENOVATIONS, LLC
HEMPSTEAD, NY—2026-07-13
NYSDOCCS NASSAU AREA OFFICE
NIAGARA FALLS, NY—2026-07-10
NTVI FEDERAL INC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342413408.