NEW YORK, NY —
OSHA Inspection: EXCEL INTERIOR CONSTRUCTION CORP.
Unprogrammed Related inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Related safety inspection of EXCEL INTERIOR CONSTRUCTION CORP. in 2 PARK AVE, NEW YORK, NY 10016 (NAICS 236220). OSHA activity number 342558616.
Where did this inspection happen?
- Establishment
- EXCEL INTERIOR CONSTRUCTION CORP.
- Site address
- 2 PARK AVE
- City
- NEW YORK
- State
- NY
- ZIP
- 10016
- Mailing
- 307 W 38TH ST #1501, NEW YORK, NY 10018
What kind of inspection was it?
- Inspection type
- Unprogrammed Related (G)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 236220
- Employees
- 27
- Ownership type
- A
Citations
3 citations on file for this inspection.
1926.403 B01
- Issued
- Abate by
- Penalty
- Initial $12934.00 · Current $10000.00 Reduced
General-duty citation text
29 CFR 1926.403(b)(1): Employer did not ensure that electrical equipment is free from recognized hazards that are likely to cause death or serious physical harm to employees: a) Roof near new bulkhead: On or about July 18, 2017 The exhaust fan conduit feed was damaged and partially dismantled exposing inner wires.
Recent events (3)
- — F (S) $10000
- — C (S) $12934
- — Z (S) $12934
1926.404 F07 I
- Issued
- Abate by
- Penalty
- Initial $12934.00 · Current $10000.00 Reduced
General-duty citation text
29 CFR 1926.404(f)(7)(i): Metal cable trays, metal raceways, or metal enclosures for conductors were not grounded and such assemblies did not meet the exceptions described in subparagraphs [A] and [B]: a) Roof near new bulkhead: On or about July 18, 2017 The roofer was shocked after coming into contact with ungrounded electrical conductors while installing roofing termination bars.
Recent events (3)
- — F (S) $10000
- — C (S) $12934
- — Z (S) $12934
1926.405 A01 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1926.405(a)(1)(i): Metal raceways, cable armor, and other metal enclosures for conductors were not metallically joined together into a continuous electric conductor and so connected to all boxes, fittings, and cabinets as to provide effective elect a) Roof near new bulkhead: On or about July 18, 2017 The conduit which connected the electrical feed to the fan was not continuous while the fan was operated.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
More inspections at EXCEL INTERIOR CONSTRUCTION CORP.
NEW YORK, NY—2022-03-04 00:00:00
EXCEL INTERIOR CONSTRUCTION CORP.
View EXCEL INTERIOR CONSTRUCTION CORP.'s full OSHA safety record →
More inspections in this industry (NAICS 236220)
IRVINE, CA—2026-07-13
SNEARY CONSTRUCTION, INC.
IRVINE, CA—2026-07-13
KUKBO DESIGN USA LLC
SIOUX FALLS, SD—2026-07-13
REM CONSTRUCTION SERVICES, LLC
INDIAN ROCKS BEACH, FL—2026-07-10
UNKNOWN CONTRACTOR
SIOUX FALLS, SD—2026-07-10
HENRY CARLSON COMPANY
More inspections in NY
POUGHKEEPSIE, NY—2026-07-13
MARCO BOARD HOUSE, INC.
CORTLANDT MANOR, NY—2026-07-13
LG BUILDERS INC.
CORTLANDT MANOR, NY—2026-07-13
RJW RENOVATIONS, LLC
HEMPSTEAD, NY—2026-07-13
NYSDOCCS NASSAU AREA OFFICE
NIAGARA FALLS, NY—2026-07-10
NTVI FEDERAL INC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342558616.