OSHA Inspection: JSP ELECTRICAL CONTRACTING CORPORATION

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of JSP ELECTRICAL CONTRACTING CORPORATION in 17 JOHN STREET, NEW YORK, NY 10038 (NAICS 238210). OSHA activity number 342593332.

Watch JSP Electrical Contracting Corporation — free Get an email when a new federal OSHA severe-injury report for JSP Electrical Contracting Corporation is published. One employer, no account, unsubscribe in one click.
Site address
17 JOHN STREET
City
NEW YORK
State
NY
ZIP
10038
Mailing
178 INDUSTRIAL LOOP, STATEN ISLAND, NY 10309
Inspection type
Unprogrammed Other (I)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
17
Ownership type
A

4 citations on file for this inspection.

1926.403 B02

Serious Gravity 1 1 instance 10 exposed
Issued
Penalty
Initial $2217.00 · Current $1125.00 Reduced
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:    a) On or about 8/11/17 at a construction project for a new commercial property located at 17 John Street, New York, New York; on the 6th floor, a 4"x4" receptacle box with pre-punched knockouts was connected to non-metallic sheathed cable to provide temporary power for the project. The receptacles were being used to provide power to portable tools and were not mounted as required in the listing an labeling requirements for the boxes.    NO ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $1125
  • — Z (S) $2217

1926.405 B02

Serious Gravity 1 1 instance 10 exposed
Issued
Penalty
Initial $2217.00 · Current $1125.00 Reduced
29 CFR 1926.405(b)(2): In energized installations, each outlet box did not have a cover, faceplate, or fixture canopy:    a) On or about 8/11/17 at a construction project for a new commercial property located at 17 John Street, New York, New York; throughout the work areas, receptacles, switches and fixture boxes that were energized did not have covers or faceplates.    NO ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $1125
  • — Z (S) $2217

1926.405 G02 III

Serious Gravity 1 1 instance 17 exposed
Issued
Penalty
Initial $2217.00 · Current $1125.00 Reduced
29 CFR 1926.405(g)(2)(iii): Flexible cords were not used in continuous lengths without splice or tap:      a) On or about 8/11/17 at a construction project for a new commercial property located at 17 John Street, New York, New York; in the contractor's break area, a receptacle was spliced with non-metallic sheathed cable to provide power to a microwave oven.    NO ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $1125
  • — Z (S) $2217

1926.405 J01 I

Serious Gravity 1 1 instance 1 exposed
Issued
Penalty
Initial $2217.00 · Current $1125.00 Reduced
29 CFR 1926.405(j)(1)(i): Fixtures, lampholders, lamps, rosettes, or receptacles had live parts normally exposed to employee contact:    a) On or about 8/11/17 at a construction project for a new commercial property located at 17 John Street, New York, New York; on the 6th floor there were lamps missing from the energized sockets of the temporary lighting.    NO ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $1125
  • — Z (S) $2217

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342593332.