Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: MJ ELECTRIC LLC

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of MJ ELECTRIC LLC in INTERSECTION OF EAGLE NEST LANDING AND PADDOCK ROAD, TOWNSEND, DE 19734 (NAICS 237130). OSHA activity number 342744992.

Watch MJ Electric LLC — free Get an email when a new federal OSHA severe-injury report for MJ Electric LLC is published. One employer, no account, unsubscribe in one click.
Establishment
MJ ELECTRIC LLC
Site address
INTERSECTION OF EAGLE NEST LANDING AND PADDOCK ROAD
City
TOWNSEND
State
DE
ZIP
19734
Mailing
P. O. BOX 686, IRON MOUNTAIN, MI 49801
Inspection type
Federal Agency (M)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
237130
Employees
30
Ownership type
A

6 citations on file for this inspection.

1926.960 E03

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $12934.00
29 CFR 1926.962(f)(2): Oreder of removal.  The employer did not ensure that an employee removed a grounding device from the line or equipment using a live-line tool before removing the ground end connection.      a) Eagle Nest Landing Road, Townsend, DE- On October 28, 2017, a grounding device was removed from a structure while the grounding device was still connected to a conductor subject to induced voltage.
Recent events (3)
  • — F (S) $12934
  • — C (S) $0
  • — Z (S) $0

1926.960 B02

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $12934.00 · Current $0.00 Reduced
29 CFR 1926.960(b)(2): Treat as energized. Electric lines and equipment were not considered and treated as energized and were not de-energized in accordance with � 1926.961.   a) Eagle Nest Landing Road, Townsend, DE- On or about October 28, 2017, the employer failed to treat electrical lines that were not de-energized in accordance with 1926.961, as energized.
Recent events (3)
  • — F (S) $0
  • — C (S) $12934
  • — Z (S) $12934

1926.960 D02

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.960(d)(2): Requirements for working without electrical protective equipment. When an employee performs work near exposed parts energized at more than 600 volts, but not more than 72.5 kilovolts, and is not wearing rubber insulating gloves, being protected by insulating equipment covering the energized parts, performing work using live-line tools, or performing live-line bare hand work under � 1926.964(c), the employee shall not work from a position where he or she can reach into the minimum approach distance, established by the employer under paragraph (c)(1) of this section.  a) Eagle Nest Landing Road, Townsend, DE- On or about October 28, 2017, the employer failed to ensure that employees working near energized parts, within the minimum approach distance, wore the proper rubber insulating gloves and sleeves, were protected by insulating equipment, and were using live-line tools.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1926.961 C06

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $12934.00 · Current $0.00 Reduced
29 CFR 1926.961(c)(6): The employer did not verify that lines and equipment were de-energized by testing the lines and equipment to be worked with a device designed to detect voltage:   a) Eagle Nest Landing Road, Townsend, DE- On or about October 28, 2017, the employer failed to verify that the lines and equipment were de-energized by testing the lines and equipment to be worked on with a device designed to detect voltage.
Recent events (3)
  • — F (S) $0
  • — C (S) $12934
  • — Z (S) $12934

1926.961 C07

Other-than-serious 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $12934.00 · Current $7760.00 Reduced
29 CFR 1926.952(b):  The pre-job briefing did not cover at least the following subjects:  Hazards associated with the job, work procedures involved, special precautions, energy-source controls, and personal protective equipment requirements.    a) Eagle Nest Landing Road, Townsend, DE- On October 28, 2017, the pre-job briefing did not cover the order of removal of a grounding device that was connected to a conductor subject to induced voltage and that needed to be removed to complete training of OPGW.
Recent events (3)
  • — F (O) $7760
  • — C (S) $12934
  • — Z (S) $12934

1926.962 C

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $12934.00 · Current $0.00 Reduced
29 CFR 1926.962(c): Equipotential zone. Temporary protective grounds were not placed at such locations and were not arranged in such a manner that the employer could demonstrate will prevent each employee from being exposed to hazardous differences in electric potential. Note to paragraph (c): Appendix C to this subpart contains guidelines for establishing the equipotential zone required by this paragraph. The Occupational Safety and Health Administration will deem grounding practices meeting these guidelines as complying with paragraph (c) of this section.   a) Eagle Nest Landing Road, Townsend, DE- On or about October 28, 2017, the employer failed to create an equipotential zone where the temporary grounds were placed in a manner that the employer could demonstrate it would have prevented each employee from being exposed to hazardous differences in electric potential.
Recent events (3)
  • — F (S) $0
  • — C (S) $12934
  • — Z (S) $12934

View MJ ELECTRIC LLC's full OSHA safety record →