On , OSHA opened a planned safety inspection of TOP SHELF CABINETS, INC. in 7473 HWY 2 EAST, COLUMBIA FALLS, MT 59912 (NAICS 337110). OSHA activity number 342810058.

Watch TOP Shelf Cabinets, INC. — free Get an email when a new federal OSHA severe-injury report for TOP Shelf Cabinets, INC. is published. One employer, no account, unsubscribe in one click.
Site address
7473 HWY 2 EAST
City
COLUMBIA FALLS
State
MT
ZIP
59912
Mailing
7473 HWY 2 EAST, COLUMBIA FALLS, MT 59912
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
337110
Employees
1
Ownership type
A

4 citations on file for this inspection.

1910.107 C04

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $2772.00 · Current $1386.00 Reduced
29 CFR 1910.107(c)(4): Electrical wiring and equipment did not conform to the provisions of this paragraph and were not otherwise in accordance with subpart S of this part (Reference:  29 CFR 1910.307, Hazardous Locations):    a)  Top Shelf Cabinets, Paint Booth: On or about December 5, 2017 and at times prior, employees were exposed flash fires and related secondary fires while applying flammable and combustible liquids such as, but not limited to, n-Butyl acetate, Ethyl alcohol, Acetone, Isopropyl Alcohol, Isobutyl alcohol, 2-Hydroxy-4-n-octoxybenzophenone, Toluene, Ethylbenzene, Formaldehyde(Valspar, NUF-4801, Valtec Ultra Conversion Lacquer - Matte) to finished cabinets in spraying areas while using unapproved electrical wiring such as, but not limited to, switches, lights and outlets. The spraying application occurred where combustible vapor and residue was present.
Recent events (2)
  • — I (S) $1386
  • — Z (S) $2772

1910.107 C05

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.107(c)(5): Electrical equipment not approved for locations containing both deposits of readily ignitable residues and explosive vapors was present in spraying area(s):   a)  Top Shelf Cabinets, Paint Booth: On or about December 5, 2017 and at times prior, employees were exposed flash fires and related secondary fires from accumulating deposits of combustibles present such as, but not limited to, n-Butyl acetate, Ethyl alcohol, Acetone, Isopropyl Alcohol, Isobutyl alcohol, 2-Hydroxy-4-n-octoxybenzophenone, Toluene, Ethylbenzene, Formaldehyde(Valspar, NUF-4801, Valtec Ultra Conversion Lacquer - Matte) while using unapproved electrical equipment such as, the unapproved radio, flexible cords and cables, and temporary lighting.  The spraying application occurred where combustible vapor and residue was present.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B01 I

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasions:  a)  Top Shelf Cabinets, Paint Booth:  On or about December 5, 2017 and at times prior, employees were exposed to flash fires and related secondary fires from accumulating deposits of combustibles present such as, but not limited to, n-Butyl acetate, Ethyl alcohol, Acetone, Isopropyl Alcohol, Isobutyl alcohol, 2-Hydroxy-4-n-octoxybenzophenone, Toluene, Ethylbenzene, Formaldehyde(Valspar, NUF-4801, Valtec Ultra Conversion Lacquer - Matte) while using unapproved flexible cords and cables to energize electrical equipment such as switches and permanent lighting.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.307 C

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location:  a)  Top Shelf Cabinets, Paint Booth:  On or about December 5, 2017 and at times prior, employees were exposed to flash fires and related secondary fires while applying flammable and combustible liquids such as, but not limited to, n-Butyl acetate, Ethyl alcohol, Acetone, Isopropyl Alcohol, Isobutyl alcohol, 2-Hydroxy-4-n-octoxybenzophenone, Toluene, Ethylbenzene, Formaldehyde(Valspar, NUF-4801, Valtec Ultra Conversion Lacquer - Matte) to finished cabinets in spraying areas while using; unapproved electrical equipment such as, but not limited to, switches, lights and outlets, an unapproved radio, temporary lighting, and unapproved flexible cords and cables to energize electrical equipment such as switches and permanent lighting.