Safety Incidents OSHA Severe Injury Reports · 2015–2025
3,783,325Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: ENVIRONMENTAL PROTECTION AGENCY - NATIONAL CENTER FOR RADIATION FIELD OPERATIONS

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of ENVIRONMENTAL PROTECTION AGENCY - NATIONAL CENTER FOR RADIATION FIELD OPERATIONS in 4220 S MARYLAND PARKWAY BUILDING C, LAS VEGAS, NV 89119 (NAICS 624230). OSHA activity number 343048328.

Watch Environmental Protection Agency - National Center FOR Radiation Field Operations — free Get an email when a new federal OSHA severe-injury report for Environmental Protection Agency - National Center FOR Radiation Field Operations is published. One employer, no account, unsubscribe in one click.
Site address
4220 S MARYLAND PARKWAY BUILDING C
City
LAS VEGAS
State
NV
ZIP
89119
Mailing
4220 S MARYLAND PARKWAY BUILDING C, LAS VEGAS, NV 89119
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
624230
Employees
21
Ownership type
D

3 citations on file for this inspection.

1910.304 B02

Serious Gravity 5 1 instance 10 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.304(b)(2): Outlet devices had an ampere rating less than the load being served:  Employees working in or near Building C room 624c were exposed to fire and smoke inhalation hazards in that a re-locatable power tap was being used to power a KEURIG coffee maker for which the equipment was not rated.
Recent events (1)
  • — Z (S) $0

1910.305 D02

Serious Gravity 5 1 instance 3 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(d)(2): Panelboard enclosures. Panelboards shall be mounted in cabinets, cutout boxes, or enclosures designed for the purpose and shall be dead front. However, panelboards other than the dead front externally-operable type are permitted where accessible only to qualified persons.  Employees working in or near the electronics shop panel 1LE1 were exposed to electrical shock, fire, and smoke inhalation hazards in that the electrical panel dead front allowed access to live parts.
Recent events (1)
  • — Z (S) $0

1910.1200 F06

Serious Gravity 5 1 instance 10 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.1200(f)(6): 29 CFR 1910.1200(f)(6): The employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with the information specified under paragraphs (f)(6)(i) through (ii) of this section:   Employees working in or near Building E flammable liquids cabinet were exposed to fire and smoke inhalation hazards in that a water bottle containing a blue liquid thought to be hydraulic fluid was not labeled.
Recent events (1)
  • — Z (S) $0

View ENVIRONMENTAL PROTECTION AGENCY - NATIONAL CENTER FOR RADIATION FIELD OPERATIONS's full OSHA safety record →