KINCAID, IL —
OSHA Inspection: DYNEGY ILLINOIS, INC.
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of DYNEGY ILLINOIS, INC. in 199 ILLINOIS 104, KINCAID, IL 62540 (NAICS 221112). OSHA activity number 343053682.
Where did this inspection happen?
- Establishment
- DYNEGY ILLINOIS, INC.
- Site address
- 199 ILLINOIS 104
- City
- KINCAID
- State
- IL
- ZIP
- 62540
- Mailing
- PO BOX 260, KINCAID, IL 62540
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221112
- Employees
- 140
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.146 C02
- Issued
- Abate by
- Penalty
- Initial $7391.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.146(c)(2): The employer did not inform exposed employees, by posting danger signs or by any other equally effective means, of the existence and location of and the danger posed by permit spaces. On or about March 27, 2018, employees were exposed to potentially hazardous atmospheres present by the permit spaces accessible through the 14-cyclone hatchways and the employer did not post danger signs (or have other equally effective means) to inform employees on the danger posed by the permit spaces.
Recent events (3)
- — F (S) $0
- — C (S) $7391
- — Z (S) $7391
1910.219 C02 I
- Issued
- Abate by
- Penalty
- Initial $7391.00 · Current $7436.00
General-duty citation text
29 CFR 1910.219(c)(2)(i): All exposed part(s) of horizontal shafting seven (7) feet or less from floor or working platform were not protected by stationary casing(s) enclosing shafting completely or by trough(s) enclosing sides and top or sides and bottom of shafting: On or about March 27, 2018, employees were exposed to contact with an unprotected rotating shaft and the shaft was not protected by an enclosure at the following equipment: a) Conveyor 5B (ramp side); and b) Crusher 1B (West).
Recent events (3)
- — F (S) $7436
- — C (S) $7391
- — Z (S) $7391
1910.219 C04 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.219(c)(4)(i): Shaft ends projecting more than one-half the diameter of the shaft were not guarded by nonrotating caps or safety sleeves. On or about March 27, 2018, employees were exposed to contact with unprotected rotating shafts and the shafts were not protected by caps or safety sleeves at the following equipment: a) Conveyor Line 5B (ramp side); b) Conveyor Line 5B (stair side); and c) Feeder 5B2.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.307 B
- Issued
- Abate by
- Penalty
- Initial $7391.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.307(b): Documentation for areas designated as hazardous (classified) locations under the Class and Zone system and areas designated under the Class and Division system established after August 13, 2007 was not available to those authorized to design, install, inspect, maintain, or operate electric equipment at the location: On or about March 27, 2018, employees installed, inspected, and maintained electric equipment in hazardous locations and the employer did not document the boundaries of each division or zone in the form of drawings that visually depict the boundaries or in text that precisely describes the extent of each hazardous location.
Recent events (3)
- — F (S) $0
- — C (S) $7391
- — Z (S) $7391
1910.307 C
- Issued
- Penalty
- Initial $0.00 · Current $7436.00
General-duty citation text
29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location: On or about March 27, 2018, employees were exposed to smoke inhalation and burn hazards (combustible PRB coal dust) and the employer provided electrical equipment that was not safe for the hazardous (classified) location including: a) condulet plug missing near Feeder 6A; and b) unsecured condulet cover at the stairway landing of Conveyor 5B.
Recent events (3)
- — F (S) $7436
- — C (S) $0
- — Z (S) $0
More inspections in this industry (NAICS 221112)
JOLIET, IL—2026-07-08
COMMONWEALTH EDISON COMPANY
HARRODSBURG, KY—2026-06-11
69213 - LOUISVILLE GAS - ELECTRIC COMPANY
AGUIRRE, PR—2026-05-26
GENERA PR
WHEATFIELD, IN—2026-05-18
NORTHERN INDIANA PUBLIC SERVICE COMPANY
FAIRBANKS, AK—2026-05-13
AURORA ENERGY, LLC
More inspections in IL
BLOOMINGTON, IL—2026-07-13
UNKNOWN CONTRACTOR
GRANITE CITY, IL—2026-07-13
UNITED STATES STEEL CORPORATION
DECATUR, IL—2026-07-10
TILLAMOOK ILLINOIS, LLC
NEW LENOX, IL—2026-07-10
A.D GENERAL CONSTRUCTION LLC
LOCKPORT, IL—2026-07-09
ROBERTO GOMEZ DBA ROBERTO GOMEZ
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343053682.