1,224,460Inspections Most recent open 2026-07-13 Last loaded 2026-07-16
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: JW POWERLINE, LLC

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of JW POWERLINE, LLC in NAIL RANCH A-6 SWD, MIDLAND, TX 79707 (NAICS 237130). OSHA activity number 343134946.

Watch JW Powerline, LLC — free Get an email when a new federal OSHA severe-injury report for JW Powerline, LLC is published. One employer, no account, unsubscribe in one click.
Establishment
JW POWERLINE, LLC
Site address
NAIL RANCH A-6 SWD
City
MIDLAND
State
TX
ZIP
79707
Mailing
2401 E. I-20, MIDLAND, TX 79701
Inspection type
Federal Agency (M)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
237130
Employees
3
Ownership type
A

4 citations on file for this inspection.

1910.269 A04

Serious Gravity 10 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $12806.00 · Current $12806.00
29 CFR 1910.269(a)(4): Existing characteristics and conditions of electric lines and equipment that were related to the safety of the work to be performed was not determined before work on or near the lines or equipment was started:  On or about May 2, 2018, the employer did not ensure that the existing characteristics and conditions of electrical lines, related to the safety of work, was determined before work was started.  This exposed the employees to electrical hazards.
Recent events (3)
  • — R (S) $12806
  • — C (S) $12806
  • — Z (S) $12806

1910.269 C01 I

Serious Gravity 10 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.269(c)(1)(i): A more extensive job briefing was not conducted where an employee could not be expected to recognize and avoid the hazards involved in the job:  On or about May 2, 2018, the employer did not conduct an extensive job briefing to employees performing repair work on an overhead power line.  This exposed the employees to electrical hazards.
Recent events (3)
  • — R (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.269 M03 II

Serious Gravity 10 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $12805.00 · Current $12805.00
29 CFR 1910.269(m)(3)(ii): The employer did not ensure that all switches, disconnectors, jumpers, taps, and other means through which known sources of electric energy may be supplied to the particular lines and equipment to be denenergized were open.  The employer did not render such means inoperable, unless its design does not so permit, and then sure that such means are tagged to indicate that employees are at work:  On or about May 2, 2018, employees performing repair work on an overhead power line were exposed to electrical hazards  when the employer did not ensure that all switches were open.
Recent events (3)
  • — R (S) $12805
  • — C (S) $12805
  • — Z (S) $12805

1910.269 N02

Serious Gravity 10 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.269(n)(2): For any employee to work transmission and distribution lines or equipment as deenergized, the employer did not ensure that the lines or equipment were deenergized under the provisions of paragraph (m) of this section and did not ensure proper grounding of the lines or equipment as specified in paragraphs (n)(3) through (n)(8) of this section:  On or about May 2, 2018, employees performing repair work on an overhead power line were exposed to electrical hazards when the employer did not ensure proper grounding of the lines.
Recent events (3)
  • — R (S) $0
  • — C (S) $0
  • — Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343134946.