1,224,460Inspections Most recent open 2026-07-13 Last loaded 2026-07-16
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: SELIGSOHN SOENS HESS COMPANY

Referral inspection · Health discipline

On , OSHA opened a referral health inspection of SELIGSOHN SOENS HESS COMPANY in THE SHERIDAN BUILDING, 125 SOUTH 9TH STREET, PHILADELPHIA, PA 19107 (NAICS 531312). OSHA activity number 343257036.

Watch Seligsohn Soens Hess Company — free Get an email when a new federal OSHA severe-injury report for Seligsohn Soens Hess Company is published. One employer, no account, unsubscribe in one click.
Site address
THE SHERIDAN BUILDING, 125 SOUTH 9TH STREET
City
PHILADELPHIA
State
PA
ZIP
19107
Mailing
123 SOUTH BOARD STREET, 8TH FLOOR, PHILADELPHIA, PA 19109
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
531312
Employees
10
Ownership type
A

2 citations on file for this inspection.

1910.332 B01

Deleted Serious Gravity 1 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $3298.00 · Current $0.00 Reduced
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:  a. The Sheridan Building located at 125 South 9th Street, Philadelphia, PA 19107  - The employer did not trained employees in safety-related work practices, including but not limited to, when and how to de-energize electrical equipment, the hazards of arc-flash, the purpose of electrical warning signs and labels, protective grounding, and general electrical hazards. Employees work duties included but not limited: basic electrical work, such as, the replacement of lights and lighting ballasts for fluorescent lights, and checking if junction boxes, control boxes, connections and other wiring have covers.  Observed On or About 06/22/18
Recent events (3)
  • — F (S) $0
  • — C (S) $3298
  • — Z (S) $3298

1910.303 H02 III B

Other-than-serious 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $617.00 · Current $493.00 Reduced
29 CFR 1910.303(h)(2)(iii)(B): The employer did not mark metal-enclosed switchgear, unit substations, transformers, pull boxes, connection boxes, and other similar associated equipment  with appropriate caution signs; and danger signs:    a.  Sub-basement, The Sheridan Building located at 125 South 9th Street, Philadelphia, PA 19107 - The employer did not affix Arc Flash hazard warning labels to a cubicle that contained a high voltage Air Interrupter Switchgear equipment to ensure that employees were warned about the hazards of arc flash. A Building Maintenance Technician sustained severe burns to the face, neck, and chest when an arc flash occurred as he worked near or in close proximity to energized electrical parts at 13,200 volts.  Observed On or About 06/22/18
Recent events (3)
  • — F (O) $493
  • — C (O) $617
  • — Z (O) $617

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343257036.