Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: JR MENENDEZ, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of JR MENENDEZ, INC. in 4623 GULF BLVD, SAINT PETE BEACH, FL 33706 (NAICS 722513). OSHA activity number 343450052.

Watch JR Menendez, INC. — free Get an email when a new federal OSHA severe-injury report for JR Menendez, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
JR MENENDEZ, INC.
Site address
4623 GULF BLVD
City
SAINT PETE BEACH
State
FL
ZIP
33706
Mailing
4623 GULF BLVD, SAINT PETE BEACH, FL 33706
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
722513
Employees
45
Ownership type
A

5 citations on file for this inspection.

1910.303 F02

Serious Gravity 1 1 instance 45 exposed
Issued
Penalty
Initial $3978.00 · Current $1989.00 Reduced
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:    (a) cage area - breakers inside the electrical panels were not adequately labeled, in that, the labels were either missing or not legible; observed on or about 9/7/2018.
Recent events (2)
  • — I (S) $1989
  • — Z (S) $3978

1910.303 G01

Serious Gravity 1 1 instance 45 exposed
Issued
Penalty
Initial $3978.00 · Current $1989.00 Reduced
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:    (a) cage area - bread racks, a trash cart, and a trash container obstructed access to the electrical panels, observed on or about 9/7/2018.
Recent events (2)
  • — I (S) $1989
  • — Z (S) $3978

1910.305 B01 II

Serious Gravity 5 2 instances 45 exposed
Issued
Penalty
Initial $6630.00 · Current $3315.00 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:    (a) cage area, Square D 240V electrical panel C - the live busbar behind the panelboard front was exposed through the open spaces of missing breakers and/or fillers; observed on or about 9/7/2018.    (b) cage area, Square D 240V electrical panel E - the live busbar behind the panelboard front was exposed through the open spaces of missing breakers and/or fillers; observed on or about 9/7/2018.
Recent events (2)
  • — I (S) $3315
  • — Z (S) $6630

1910.305 D02

Serious Gravity 5 1 instance 45 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(d)(2): Panelboards mounted in cabinets, cutout boxes, or enclosures designed for the purpose were not dead front:  (a) cage area, Square D 240V electrical panel B - live wires were exposed at the front of the panelboard; observed on or about 9/7/2018.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.157 C01

Other-than-serious 1 instance 45 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries:  (a) at the workplace - the locations of fire extinguishers were not identified; observed on or about 9/7/2018.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343450052.