On , OSHA opened a planned health inspection of HULME WAREHOUSING, LLC in 103 HOUSTON ST., QUEEN CITY, TX 75572 (NAICS 493110). OSHA activity number 343469078.

Watch Hulme Warehousing, LLC — free Get an email when a new federal OSHA severe-injury report for Hulme Warehousing, LLC is published. One employer, no account, unsubscribe in one click.
Site address
103 HOUSTON ST.
City
QUEEN CITY
State
TX
ZIP
75572
Mailing
PO BOX 336, QUEEN CITY, TX 75572
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493110
Employees
3
Ownership type
A

7 citations on file for this inspection.

1910.22 A02

Serious Gravity 1 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $1663.00 · Current $998.00 Reduced
29 CFR 1910.22(a)(2): The floor of a workroom was not maintained in a clean condition.  (a) Warehouse Loading Dock area, trash and other debris exposed employees to trip hazards.
Recent events (2)
  • — I (S) $997.8
  • — Z (S) $1663

1910.178 L01 II

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $2217.00 · Current $1330.00 Reduced
29 CFR 1910.178(l)(1)(ii): Prior to permitting an employee to operate a powered industrial truck (except for training purposes), the employer did not ensure that each operator had successfully completed the training required by 29 CFR 1910.178(l):  a) In the Warehouse area, employees operated various forklift trucks without having first completed training of consisting formal instruction, practical training, and an evaluation of the operator's performance in the workplace.
Recent events (2)
  • — I (S) $1330.2
  • — Z (S) $2217

1910.178 L06

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.178(l)(6): The employer did not certify that each operator has been trained and evaluated as required by this paragraph (l):  a) In the Warehouse Area, employees operated various forklift trucks without having first been trained and evaluated.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 F02

Serious Gravity 5 2 instances 2 exposed
Issued
Abate by
Penalty
Initial $2217.00 · Current $1330.00 Reduced
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:   (a) Wood Shop Area/ Gin Barn the electrical panel box was not labeled indicating the purpose and location. Employees are exposed to electrical hazards.
Recent events (2)
  • — I (S) $1330.2
  • — Z (S) $2217

1910.305 B01 II

Serious Gravity 5 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:  (a) Wood Shop Area/ Gin Barn, the electrical panel box was not effectively closed. Employees were exposed to electrical hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G02 I

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $2217.00 · Current $1330.00 Reduced
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):  (a) Wood Shop Area/ Gin Barn , the Craftsman air compressor electrical components had missing primary and secondary insulation exposing employees to energized conductors.
Recent events (2)
  • — I (S) $1330.2
  • — Z (S) $2217

1910.305 J04 VI

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(j)(4)(vi): An individual disconnecting means was not provided for each motor:   (a) Wood Shop Area/ Gin Barn , the Craftsman air compressor motor was not provided with a disconnecting means for the motor. Employees were exposed to electrical hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

SPEEDX