Safety Incidents OSHA Severe Injury Reports · 2015–2025
3,913,242Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: ALLSTATE ELECTRICAL CONTRACTING INC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of ALLSTATE ELECTRICAL CONTRACTING INC in 485 LEXINGTON AVENUE, NEW YORK, NY 10017 (NAICS 238210). OSHA activity number 343546560.

Watch Allstate Electrical Contracting INC — free Get an email when a new federal OSHA severe-injury report for Allstate Electrical Contracting INC is published. One employer, no account, unsubscribe in one click.
Site address
485 LEXINGTON AVENUE
City
NEW YORK
State
NY
ZIP
10017
Mailing
44 NORTH CENTRAL AVENUE, ELMSFORD, NY 10523
Inspection type
Complaint (B)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
43
Ownership type
A

3 citations on file for this inspection.

1926.21 B02

Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $9282.00 · Current $5000.00 Reduced
29 CFR 1926.21(b)(2): The employer did not instruct each employee in the recognition and avoidance of unsafe condition(s) and the regulation(s) applicable to his work environment to control or eliminate any hazard(s) or other exposure to illness or injury.    Location:     485 Lexington Avenue, New York, NY 9th Floor.     An employee was working in an energized panel and was not trained on the appropriate use of Personnel Protective Equipment or Deenergization  of the panel. On or about 10/15/2018.
Recent events (3)
  • — F (S) $5000
  • — C (S) $9282
  • — Z (S) $9282

1926.97 C02 VIII

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $6630.00 · Current $3000.00 Reduced
29 CFR 1926.97(c)(2)(viii): Electrical protective equipment was not subjected to periodic electrical tests. Test voltages and the maximum intervals between tests shall be in accordance with Table E-4 and Table E-5.    Location:     485 Lexington Avenue, New York, NY 9th Floor.     Rubber Insulating gloves were not subjected to periodic electrical testing.  Rubber electrical gloves with a tested fate of October 2006 were not recently tested as per the Tables.  On or about 10/15/2018.
Recent events (3)
  • — F (S) $3000
  • — C (S) $6630
  • — Z (S) $6630

1926.416 A01

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $9282.00 · Current $0.00 Reduced
29 CFR 1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means.  Location:         485 Lexington Avenue, New York, NY 9th Floor.   Employee was working in an energized panel and did not deenergize the panel nor use or wear personal protective equipment.  An arc flash occurred when a tool made contact with the energized bus duct. On or about 10/15/2018.
Recent events (3)
  • — F (S) $0
  • — C (S) $9282
  • — Z (S) $9282

View ALLSTATE ELECTRICAL CONTRACTING INC's full OSHA safety record →