On , OSHA opened a complaint safety inspection of ALLSTATE ELECTRICAL CONTRACTING INC in 485 LEXINGTON AVENUE, NEW YORK, NY 10017 (NAICS 238210). OSHA activity number 343546560.
Where did this inspection happen?
- Establishment
- ALLSTATE ELECTRICAL CONTRACTING INC
- Site address
- 485 LEXINGTON AVENUE
- City
- NEW YORK
- State
- NY
- ZIP
- 10017
- Mailing
- 44 NORTH CENTRAL AVENUE, ELMSFORD, NY 10523
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 43
- Ownership type
- A
Citations
3 citations on file for this inspection.
1926.21 B02
- Issued
- Abate by
- Penalty
- Initial $9282.00 · Current $5000.00 Reduced
General-duty citation text
29 CFR 1926.21(b)(2): The employer did not instruct each employee in the recognition and avoidance of unsafe condition(s) and the regulation(s) applicable to his work environment to control or eliminate any hazard(s) or other exposure to illness or injury. Location: 485 Lexington Avenue, New York, NY 9th Floor. An employee was working in an energized panel and was not trained on the appropriate use of Personnel Protective Equipment or Deenergization of the panel. On or about 10/15/2018.
Recent events (3)
- — F (S) $5000
- — C (S) $9282
- — Z (S) $9282
1926.97 C02 VIII
- Issued
- Abate by
- Penalty
- Initial $6630.00 · Current $3000.00 Reduced
General-duty citation text
29 CFR 1926.97(c)(2)(viii): Electrical protective equipment was not subjected to periodic electrical tests. Test voltages and the maximum intervals between tests shall be in accordance with Table E-4 and Table E-5. Location: 485 Lexington Avenue, New York, NY 9th Floor. Rubber Insulating gloves were not subjected to periodic electrical testing. Rubber electrical gloves with a tested fate of October 2006 were not recently tested as per the Tables. On or about 10/15/2018.
Recent events (3)
- — F (S) $3000
- — C (S) $6630
- — Z (S) $6630
1926.416 A01
- Issued
- Abate by
- Penalty
- Initial $9282.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means. Location: 485 Lexington Avenue, New York, NY 9th Floor. Employee was working in an energized panel and did not deenergize the panel nor use or wear personal protective equipment. An arc flash occurred when a tool made contact with the energized bus duct. On or about 10/15/2018.
Recent events (3)
- — F (S) $0
- — C (S) $9282
- — Z (S) $9282
More inspections at ALLSTATE ELECTRICAL CONTRACTING INC
YONKERS, NY—2025-03-10
ALLSTATE ELECTRICAL CONTRACTING INC
View ALLSTATE ELECTRICAL CONTRACTING INC's full OSHA safety record →
More inspections in this industry (NAICS 238210)
SOUTH FULTON, GA—2026-07-10
REEDWICK, LLC
NIAGARA FALLS, NY—2026-07-10
GAINES ELECTRICAL CONTRACTING, INC.
OGDENSBURG, NY—2026-07-10
S & L ELECTRIC, INC.
BOISE, ID—2026-07-09
POWERHOUSE ELECTRIC INC.
LYNCHBURG, VA—2026-07-09
WHITE ELECTRICAL SERVICES LLC
More inspections in NY
POUGHKEEPSIE, NY—2026-07-13
MARCO BOARD HOUSE, INC.
CORTLANDT MANOR, NY—2026-07-13
LG BUILDERS INC.
CORTLANDT MANOR, NY—2026-07-13
RJW RENOVATIONS, LLC
HEMPSTEAD, NY—2026-07-13
NYSDOCCS NASSAU AREA OFFICE
NIAGARA FALLS, NY—2026-07-10
NTVI FEDERAL INC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343546560.