Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: MCCOY'S MILLWORK DOOR FACILITY #451

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of MCCOY'S MILLWORK DOOR FACILITY #451 in 3209 W. BUSINESS 83, MCALLEN, TX 78501 (NAICS 423310). OSHA activity number 343602686.

Watch Mccoy'S Millwork Door Facility #451 — free Get an email when a new federal OSHA severe-injury report for Mccoy'S Millwork Door Facility #451 is published. One employer, no account, unsubscribe in one click.
Site address
3209 W. BUSINESS 83
City
MCALLEN
State
TX
ZIP
78501
Mailing
1350 IH 35 NORTH, SAN MARCOS, TX 78666
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
423310
Employees
26
Ownership type
A

12 citations on file for this inspection.

1910.147 C07 IV

Deleted Serious Gravity 5 2 instances 4 exposed
Issued
Abate by
Penalty
Initial $9472.00 · Current $0.00 Reduced
29 CFR 1910.147(c)(7)(iv): The employer did not certify that employee training had been accomplished and kept up to date:       On November 14, 2018 and times prior thereto, at this work site facility,  the employer did not train or provide certification on Lockout/Tagout procedures, for employees who perform maintenance tasks on the machinery.
Recent events (2)
  • — I (S) $0
  • — Z (S) $9472

1910.212 A01

Other-than-serious 1 instance 4 exposed
Issued
Penalty
Initial $13260.00 · Current $8000.00 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and metal.    On November 14, 2018, and times prior thereto, at the Interior Line work area, employees used an unguarded stapling machine to conduct door assembly tasks.
Recent events (2)
  • — I (O) $8000
  • — Z (S) $13260

1910.212 A03 II

Other-than-serious 1 instance 4 exposed
Issued
Penalty
Initial $13260.00 · Current $3000.00 Reduced
29 CFR 1910.212(a)(3)(ii): Point(s) of operation of machinery were not guarded to prevent employee(s) from having any part of their body in the danger zone(s) during operating cycle(s):    On November 14, 2018 and times prior there to, at the Interior Line work area, employees conducted door assembly tasks, using an unguarded boring handler machine.
Recent events (2)
  • — I (O) $3000
  • — Z (S) $13260

1910.212 B

Deleted Serious Gravity 5 2 instances 2 exposed
Issued
Penalty
Initial $7577.00 · Current $0.00 Reduced
29 CFR 1910.212(b): Machine(s) designed for fixed location(s) were not securely anchored to prevent walking or moving:  On November 14, 2018, and times prior thereto, in the Interior Line work area, the employees used a Polychem machine which was not securely anchored to prevent walking or moving.
Recent events (2)
  • — I (S) $0
  • — Z (S) $7577

1910.303 B02

Other-than-serious 1 instance 4 exposed
Issued
Penalty
Initial $9472.00 · Current $9472.00
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:    On November 14, 2018, and times prior thereto, at the Interior Line, employees used a stapler machine to conduct door assembly tasks and the controls to the machine were not installed in accordance with manufactures instructions.
Recent events (2)
  • — I (O) $9472
  • — Z (S) $9472

1910.303 B07

Other-than-serious 1 instance 4 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(b)(7): Mechanical execution of work. Electric equipment shall be installed in a neat and workmanlike manner.          On November 14, 2018 and times prior thereto, at the Interior Line, electrical equipment was not installed in a neat and workmanlike manner.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.303 B08 I

Other-than-serious 1 instance 4 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(b)(8)(i): Electric equipment was not firmly secured to the surface on which it is mounted:    On November 14, 2019, and times prior thereto, at the Interior Line work area, the employer failed to ensure the receptacle for the 700 B machine was permanently secured to a fixed surface.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.305 A02 V C

Other-than-serious 1 instance 4 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(a)(2)(v)(C): No branch-circuit conductor may be laid on the floor:    On November 14, 2018, and times prior thereto, at the Interior Line, employees used an energized machine to conduct door assembly tasks and the branch circuit was laid on the floor in the employees walking/working path.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.305 G02 III

Other-than-serious 1 instance 4 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:    On November 14, 2018, and times prior thereto, at the interior line, employees used an energized, single phase, electrical plug fitting, without strain relief.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.305 J01 I

Other-than-serious 1 instance 4 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(j)(1)(i): Fixtures, lampholders, lamps, rosettes, and receptacles located had live parts normally exposed to employee contact:    On November14, 2019, and times prior thereto, at the Interior Line, employees operated the door assembly machine where the receptacles, located adjacent to the employee work area, had exposed live wiring.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.307 C01

Other-than-serious 1 instance 4 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.307(c)(1): Equipment and associated wiring was not approved as intrinsically safe:    On November 14, 2019, Interior Line, Door Assembly machine,  receptacles contained accumulated dust inside the receptacles and were not approved for use in Class II locations where combustible dust was present or is reasonably expected to be present.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.141 A04 II

Other-than-serious 1 instance 26 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.141(a)(4)(ii): Wastes were not removed as often as necessary to maintain the place of employment in a sanitary condition:  On November 14, 2018, in the employee restrooms, sanitary conditions had not been maintained, there was urine and fecal matter on the walking surface, and other trash which had not been removed.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343602686.