CINNAMINSON, NJ —
OSHA Inspection: FOREMAN MILLS, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of FOREMAN MILLS, INC. in 3000 CINDEL DRIVE, CINNAMINSON, NJ 08077 (NAICS 493110). OSHA activity number 343657128.
Where did this inspection happen?
- Establishment
- FOREMAN MILLS, INC.
- Site address
- 3000 CINDEL DRIVE
- City
- CINNAMINSON
- State
- NJ
- ZIP
- 08077
- Mailing
- 3000 CINDEL DRIVE, CINNAMINSON, NJ 08077
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 493110
- Employees
- 500
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.304 F01 VIII
- Issued
- Penalty
- Initial $5115.00 · Current $3836.00 Reduced
General-duty citation text
29 CFR 1910.304(f)(1)(viii): Circuit breakers used as switches in 120-volt and 277-volt, fluorescent lighting circuits were not listed and marked "SWD": a- Interior Lighting Panel #3 - 3000 Cindel Drive, Cinnaminson NJ: Circuit breakers were frequently used as switches, controlling the power to the warehouse lighting. As such these circuit breakers were not being used as per their manufacturer's requirements and were not listed or marked "SWD". Condition observed on or about 12/11/18.
Recent events (2)
- — I (S) $3836.25
- — Z (S) $5115
1910.334 B01
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.334(b)(1): Cable connectors not of the load break type, fuses, terminal lugs, or cable splice connections were used as disconnecting means of electric power and lighting circuits: a- Interior Lighting Panel #3 - 3000 Cindel Drive, Cinnaminson NJ: Circuit breakers were frequently used as switches, controlling the power to the warehouse lighting. As such these circuit breakers were not being used as per their manufacturer's requirements. Condition observed on or about 12/11/18.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B01 II
- Issued
- Penalty
- Initial $5115.00 · Current $3836.00 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a- Interior Lighting Panel #2A - 3000 Cindel Drive, Cinnaminson NJ: The exterior of the circuit breaker box contained several unprotected openings and within the box unused openings, between circuit breakers, were not effectively closed. Condition observed on or about 12/11/18.
Recent events (2)
- — I (S) $3836.25
- — Z (S) $5115
More inspections in this industry (NAICS 493110)
DUNDALK, MD—2026-07-09
WILLIAMS SCOTSMAN, INC.
ROCK HILL, SC—2026-07-08
77566 - WEST MARINE INC
BLACK MOUNTAIN, NC—2026-07-07
161500 - INGLES MARKETS, INCORPORATED - DISTRIBUTION CENTER
FRANKLIN, KY—2026-07-07
69287 - TRACTOR SUPPLY COMPANY
PARKERSBURG, WV—2026-07-07
PEOPLES CARTAGE INC
More inspections in NJ
FREEHOLD, NJ—2026-07-10
MARIO & SONS CONSTRUCTION GROUP, LLC
FREEHOLD, NJ—2026-07-10
VACCA ROOFING
FREEHOLD, NJ—2026-07-10
SPECTRA PAINTING, INC
FREEHOLD, NJ—2026-07-10
CRAIG'S MASONRY & HARDSCAPE LLC
FREEHOLD, NJ—2026-07-10
GTN CONSTRUCTION INC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343657128.