Safety Incidents OSHA Severe Injury Reports · 2015–2025
3,913,242Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: FOREMAN MILLS, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of FOREMAN MILLS, INC. in 3000 CINDEL DRIVE, CINNAMINSON, NJ 08077 (NAICS 493110). OSHA activity number 343657128.

Watch Foreman Mills, INC. — free Get an email when a new federal OSHA severe-injury report for Foreman Mills, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
FOREMAN MILLS, INC.
Site address
3000 CINDEL DRIVE
City
CINNAMINSON
State
NJ
ZIP
08077
Mailing
3000 CINDEL DRIVE, CINNAMINSON, NJ 08077
Inspection type
Complaint (B)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493110
Employees
500
Ownership type
A

3 citations on file for this inspection.

1910.304 F01 VIII

Serious Gravity 1 1 instance 2 exposed
Issued
Penalty
Initial $5115.00 · Current $3836.00 Reduced
29 CFR 1910.304(f)(1)(viii): Circuit breakers used as switches in 120-volt and 277-volt, fluorescent lighting circuits were not listed and marked "SWD":  a- Interior Lighting Panel #3 - 3000 Cindel Drive, Cinnaminson NJ: Circuit breakers were frequently used as switches, controlling the power to the warehouse lighting.  As such these circuit breakers were not being used as per their manufacturer's requirements and were not listed or marked "SWD". Condition observed on or about 12/11/18.
Recent events (2)
  • — I (S) $3836.25
  • — Z (S) $5115

1910.334 B01

Serious Gravity 5 1 instance 2 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.334(b)(1): Cable connectors not of the load break type, fuses, terminal lugs, or cable splice connections were used as disconnecting means of electric power and lighting circuits:  a- Interior Lighting Panel #3 - 3000 Cindel Drive, Cinnaminson NJ: Circuit breakers were frequently used as switches, controlling the power to the warehouse lighting.  As such these circuit breakers were not being used as per their manufacturer's requirements. Condition observed on or about 12/11/18.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B01 II

Serious Gravity 1 1 instance 2 exposed
Issued
Penalty
Initial $5115.00 · Current $3836.00 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:  a- Interior Lighting Panel #2A - 3000 Cindel Drive, Cinnaminson NJ: The exterior of the circuit breaker box contained several unprotected openings and within the box unused openings, between circuit breakers, were not effectively closed.  Condition observed on or about 12/11/18.
Recent events (2)
  • — I (S) $3836.25
  • — Z (S) $5115

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343657128.