HAMPTON, NH —
OSHA Inspection: FOSS PERFORMANCE MATERIALS, LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of FOSS PERFORMANCE MATERIALS, LLC in 380 LAFAYETTE ROAD, HAMPTON, NH 03843 (NAICS 313230). OSHA activity number 343681771.
Where did this inspection happen?
- Establishment
- FOSS PERFORMANCE MATERIALS, LLC
- Site address
- 380 LAFAYETTE ROAD
- City
- HAMPTON
- State
- NH
- ZIP
- 03843
- Mailing
- 11 MERRILL INDUSTRIAL DRIVE, HAMPTON, NH 03843
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 313230
- Employees
- 430
- Ownership type
- A
Citations
9 citations on file for this inspection.
1910.28 B01 I
- Issued
- Abate by
- Penalty
- Initial $9472.00 · Current $7104.00 Reduced
General-duty citation text
29 CFR 1910.28(b)(1)(i): The employer did not ensure that each employee on a walking-working surface with an unprotected side or edge that was 4 feet (1.2 m) or more above a lower level was protected from falling by one or more of the following: Guardrail systems, safety net systems, or personal fall arrest systems: Location: mezzanine above the extruder Employees were not protected from falling when the guard rails were removed to load and unload material from a mezzanine that was more than 4 feet above a lower level.
Recent events (2)
- — I (S) $7104
- — Z (S) $9472
1910.151 C
- Issued
- Abate by
- Penalty
- Initial $9472.00 · Current $7104.00 Reduced
General-duty citation text
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use: On or about 12/19/18, eye stations where employees were working with corrosive chemicals such as Starsurf 680 and Metal Medic 7055 were not inspected and/or maintained in working condition: Location 1: Coating Location 2: Dip tanks
Recent events (2)
- — I (S) $7104
- — Z (S) $9472
1910.212 A01
- Issued
- Abate by
- Penalty
- Initial $9472.00 · Current $7104.00 Reduced
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: On or about 12/19/18, employees were not protected from ingoing nip points and rotating parts while interlocked doors were by-passed while the machine was in operation: Location 1: Line J, cross lapper guarding was not adequately secured, Location 2: Line J, feeder window guarding was not in place and the interlock was not functional.
Recent events (2)
- — I (S) $7104
- — Z (S) $9472
1910.219 F03
- Issued
- Abate by
- Penalty
- Initial $9472.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.219(f)(3): Sprocket wheels and chains which were seven -7 feet or less above floors or platforms were not enclosed: On or about 12/19/18, Line operators were not adequately protected from moving chain and sprockets while feeding material during the startup process: Location 1: Line E Location 2: Line F Location 3: Line H
Recent events (2)
- — I (S) $0
- — Z (S) $9472
1910.303 B07 I
- Issued
- Abate by
- Penalty
- Initial $9472.00 · Current $3978.00 Reduced
General-duty citation text
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment. On or about 12/19/18, Openings in sides of energized 480 volt electrical cabinets were not closed: Location 1: Line B Brush/loom head motor control cabinet. Location 2: Line J cabinet for cross lapper switch gear.
Recent events (2)
- — I (S) $3978
- — Z (S) $9472
1910.303 E01 II
- Issued
- Abate by
- Penalty
- Initial $9472.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.303(e)(1)(ii): Electric equipment was used without markings giving voltage, current, wattage, or other ratings as necessary: Location: throughout facility On or about 12/19/18, electrical cabinets throughout the facility were not labeled to indicate voltage and wattage.
Recent events (2)
- — I (S) $0
- — Z (S) $9472
1910.303 F01
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(f)(1): Each disconnecting means required by Subpart S of Part 1910 for motors and appliances was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: Location: throughout facility On or about 12/19/18 numerous electrical disconnects found throughout the facility were not labeled to indicate their purpose.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 A02 IX
- Issued
- Abate by
- Penalty
- Initial $5683.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.305(a)(2)(ix): Lamps for general illumination were not protected from accidental contact or breakage by a suitable fixture or lamp holder with a guard: Location: Line E On or about 12/19/18, florescent lights located above the walkway over the machine were not protected by guards or suitable lamp holder.
Recent events (2)
- — I (S) $0
- — Z (S) $5683
1910.305 A02 V C
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(a)(2)(v)(C): Branch-circuit conductors were laid on the floor. Location: line B On or about 12/19/18 the flexible power cord for the line B Edge Winder was laid on the floor.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 313230)
MCHENRY, IL—2026-07-08
SUPERIOR FELT & FILTRATION, L.L.C.
CONOVER, NC—2026-06-03
161327 - DALCO GFT NONWOVENS, LLC
UTICA, NY—2026-04-07
ENVIRONMENTAL COMPOSITES, INC.
LENOIR, NC—2026-03-19
160748 - NUTEX CONCEPTS OF NORTH CAROLINA CORPORATION
GROVER, NC—2026-03-09
160714 - UNIQUETEX, LLC
More inspections in NH
CONCORD, NH—2026-07-10
C.C. TOMATOES
FRANCESTOWN, NH—2026-07-10
JM BUILDERS LLC
FRANCESTOWN, NH—2026-07-10
D&D INSULATION, LLC
NORTHFIELD, NH—2026-07-03
JP PEST SERVICES
CONCORD, NH—2026-07-01
REYES CARPENTRY, LLC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343681771.