OSHA Inspection: MCCLELLAND, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of MCCLELLAND, INC. in 2655 MARYSVILLE PIKE, ZANESVILLE, OH 43701 (NAICS 722513). OSHA activity number 343761201.

Watch Mcclelland, INC. — free Get an email when a new federal OSHA severe-injury report for Mcclelland, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
MCCLELLAND, INC.
Site address
2655 MARYSVILLE PIKE
City
ZANESVILLE
State
OH
ZIP
43701
Mailing
98 EAST LASALLE STREET, ZANESVILLE, OH 43701
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
722513
Employees
70
Ownership type
A

5 citations on file for this inspection.

1910.303 B01 VI

Serious Gravity 5 1 instance 25 exposed
Issued
Penalty
Initial $6630.00 · Current $3978.00 Reduced
29 CFR 1910.303(b)(1): Examination. Electric equipment shall be free from recognized hazards that are likely to cause death or serious physical harm to employees. Safety of equipment shall be determined using the following considerations:  29 CFR 1910.303(b)(1)(vi): Arcing effects   a. Located in the first and second floor kitchen areas, employees were exposed to an electrical shock hazard while plugging in the hot boxes into two 120 volt electrical receptacles that were arcing.
Recent events (2)
  • — I (S) $3978
  • — Z (S) $6630

1910.304 G05

Serious Gravity 5 1 instance 25 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.304(g)(5): Grounding path. The path to ground from circuits, equipment, and enclosures shall be permanent, continuous, and effective.   a. Located in the first floor kitchen area, employees were exposed to an electrical shock hazard while plugging in two hot boxes that had a missing ground pin.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 5 2 instances 25 exposed
Issued
Penalty
Initial $6630.00 · Current $3978.00 Reduced
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear.   a. Located throughout the first and second floor kitchen areas, employees were exposed to an electrical shock hazard due to several 120 volt receptacles in use without a faceplate.      b. Located in the first floor kitchen area, the junction box under the garbage disposal sink had a cover that was not secured to the box, exposing employees to an electrical shock hazard.
Recent events (2)
  • — I (S) $3978
  • — Z (S) $6630

1910.305 C04

Serious Gravity 5 1 instance 25 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(c)(4): Faceplates for flush-mounted snap switches. Snap switches mounted in boxes shall have faceplates installed so as to completely cover the opening and seat against the finished surface.   a. Located in the first floor kitchen area, employees were exposed to an electrical shock hazard while operating the main hallway switches due to a missing faceplate.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G02 II

Other-than-serious 1 instance 25 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(2)(ii): Flexible cords may be used only in continuous lengths without splice or tap. Hard-service cord and junior hard-service cord No. 14 and larger may be repaired if spliced so that the splice retains the insulation, outer sheath properties, and usage characteristics of the cord being spliced.   a. Located in the basement kitchen area, two flexible cords were connected together and ran through storage shelves to supply 120 volts to the bacteria digestant pump.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343761201.