CONYERS, GA —
OSHA Inspection: PRECISION PAINT AND COLLISION, LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of PRECISION PAINT AND COLLISION, LLC in 1774 IRIS DRIVE, CONYERS, GA 30012 (NAICS 811121). OSHA activity number 343948394.
Where did this inspection happen?
- Establishment
- PRECISION PAINT AND COLLISION, LLC
- Site address
- 1774 IRIS DRIVE
- City
- CONYERS
- State
- GA
- ZIP
- 30012
- Mailing
- 1774 IRIS DRIVE, CONYERS, GA 30012
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 811121
- Employees
- 7
- Ownership type
- A
Citations
3 citations on file for this inspection.
5(a)(1)
- Issued
- Abate by
- Penalty
- Initial $2415.00 · Current $1449.00 Reduced
General-duty citation text
OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to flying particles into bodies of employees due to the hazard of compressed air at pressure of 175 psi being transported by PVC pipes in the facility: 1774 Iris Drive SW, Conyers, GA (Throughout Shop Area) - Employees were exposed to being struck by shrapnel. PVC pipes were being used to transport compressed air at pressures of 150 psi. Compressed air was being used for shop tools and machines for body repairs on automotive vehicles , on or about 04/22/19. AMONG OTHER METHODS, ONE FEASIBLE AND ACCEPTABLE ABATEMENT METHOD TO CORRECT THESE HAZARD IS: Replace the PVC pipes with an impact resistant Acrylonitrile-Butadiene-Styrene (ABS) pipe. This pipe is recommended by the plastic pipe institute for t his purpose.
Recent events (2)
- — I (S) $1449
- — Z (S) $2415
1910.37 A03
- Issued
- Penalty
- Initial $1232.00 · Current $739.00 Reduced
General-duty citation text
29 CFR 1910.37(a) (3): Exit route(s) were not kept free and unobstructed: a. 1774 Iris Drive SW, Conyers, GA (Spray Painting Area) - Employees were exposed to fire hazard. The designated, marked, and identified emergency exit door in the shop area was blocked with a large heavy wooden bar placed horizontally over the emergency exit door, making it difficult to access in the event of an emergency, on or about 04/22/19.
Recent events (2)
- — I (S) $739.2
- — Z (S) $1232
1910.106 D04 III
- Issued
- Abate by
- Penalty
- Initial $2898.00 · Current $1739.00 Reduced
General-duty citation text
29 CFR 1910.106(d)(4)(iii): Electrical wiring and equipment located in inside storage rooms used for Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), was not approved under subpart S of this part for Class I, Division 2 Hazardous Locations; for Category 3 flammable liquids with a flashpoint at or above 100 °F (37.8 °C) and Category 4 flammable liquids, was not approved for general use: a. 1774 Iris Drive SW, Conyers, GA (Paint Store-Mixing Room) - Employees were exposed to fire hazard. The designated room which is used to store and mix the flammable paints was equipped with electrical outlets, lights and circuit breaker boxes. The electrical equipment/wiring inside the stored and mixing paint room was not approved for the location and/or intrinsically safe. on or about 04/22/19.
Recent events (2)
- — I (S) $1738.8
- — Z (S) $2898
More inspections in this industry (NAICS 811121)
SUMMIT, IL—2026-07-08
BUDS BODY SHOP SUPPLY & PAINT
PUYALLUP, WA—2026-07-08
WA317991990 - GLASS WORKS PRO INC
SALEM, VA—2026-07-08
CERTIFIED COLLISION REPAIR
TUMWATER, WA—2026-07-07
WA317991940 - EMERGENCY VEHICLE SOLUTIONS LLC
ASHLAND, OR—2026-06-26
317744632 - HINKS ENTERPRISES INC
More inspections in GA
ROME, GA—2026-07-13
CAMP INDUSTRIES
SOUTH FULTON, GA—2026-07-10
REEDWICK, LLC
CONYERS, GA—2026-07-10
GOLDEN STATE FOODS
DALTON, GA—2026-07-10
ENGINEERED FLOORS, LLC
METTER, GA—2026-07-10
M.A.P.C CONSTRUCTION, LLC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343948394.