LINDSAY, OK —
OSHA Inspection: K & M HIGHLINE SERVICES
Federal Agency inspection · Safety discipline
At a glance
On , OSHA opened a federal Agency safety inspection of K & M HIGHLINE SERVICES in CR 1550 AND CR 2990, LINDSAY, OK 73052 (NAICS 237130). OSHA activity number 344167887.
Where did this inspection happen?
- Establishment
- K & M HIGHLINE SERVICES
- Site address
- CR 1550 AND CR 2990
- City
- LINDSAY
- State
- OK
- ZIP
- 73052
- Mailing
- 700 NE 63RD STREET, OKLAHOMA CITY, OK 73105
What kind of inspection was it?
- Inspection type
- Federal Agency (M)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 237130
- Employees
- 32
- Ownership type
- A
Citations
5 citations on file for this inspection.
1926.950 B02 IV
- Issued
- Abate by
- Penalty
- Initial $9282.00 · Current $5570.00 Reduced
General-duty citation text
29 CFR 1926.950(b)(2)(iv): The employer did not ensure that employee was not trained in the proper use of the special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools for working on or near exposed energized parts of electric equipment. On or about July 11, 2019, employees were exposed to electrical shock and electrocution hazards where employees were not trained in special precautionary techniques or equipment for working on or near exposed energized parts.
Recent events (2)
- — I (S) $5570
- — Z (S) $9282
1926.950 B02 V
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1926.950(b)(2)(v): 29 CFR 1926.950(b)(2)(v): The employer did not ensure that each employee had the required training to recognize electrical hazards to which the employee may be exposed and the skills and techniques necessary to control or avoid these hazards: On or about July 11, 2019, employees were exposed to electrical shock and electrocution hazards where the qualified person was not trained in the recognition of electrical hazards that might be unique to a specific installation of electrical power line transmission poles.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1926.960 C01 III B
- Issued
- Abate by
- Penalty
- Initial $9282.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1926.960(c)(1)(iii)(B): The employer did not ensure that no employee approaches or takes any conductive object closer to exposed energized parts than the employer's established minimum approach distance unless the energized part is insulated from the employee and from any other conductive object at a different potential. On or about July 11, 2019, employees were exposed to electrical shock and electrocution hazards where the employer failed to ensure that conductive material attached to the pole was insulated from energized parts.
Recent events (2)
- — I (S) $0
- — Z (S) $9282
1926.952 A02
- Issued
- Abate by
- Penalty
- Initial $9282.00 · Current $5570.00 Reduced
General-duty citation text
29 CFR 1926.952(a)(2): The employer did not ensure the employee in charge conducted a job briefing that met paragraphs (b), (c), and (d) of this section with the employees involved before they started each job. On or about July 11, 2019, employees were exposed to electric shock and electrocution hazards where the employer failed to ensure that the employee in charge conducted an adequate job briefing to identify any specific hazards associated with the work to be conducted.
Recent events (2)
- — I (S) $5570
- — Z (S) $9282
1926.960 D01
- Issued
- Abate by
- Penalty
- Initial $9282.00 · Current $5570.00 Reduced
General-duty citation text
29 CFR 1926.960(d)(1): Working from below. The employer did not ensure that each employee, to the extent that other safety-related conditions at the worksite permit, works in a position from which a slip or shock will not bring the employee's body into contact with exposed, uninsulated parts energized at a potential different from the employee's. On or about July 11, 2019, employees were exposed to electric shock and electrocution hazards where the employer failed to ensure that work was performed from below exposed, uninsulated, energized parts.
Recent events (2)
- — I (S) $5570
- — Z (S) $9282
More inspections in this industry (NAICS 237130)
LEXINGTON, KY—2026-07-09
69310 - DAVIS H ELLIOT COMPANY INC
POUGHQUAG, NY—2026-07-09
MK SHARP LLC.
KENMORE, WA—2026-07-08
WA317991980 - CASCADE TOWER & RIGGING INC
HUBBARD, TX—2026-07-07
3B DOZER SERVICE LLC
ALBANY, OR—2026-07-06
317744661 - TEXSTAR ENTERPRISES LLC
More inspections in OK
MADILL, OK—2026-07-08
MID AMERICAN STEEL & WIRE CO., LLC
SEILING, OK—2026-06-26
GORE ENERGY
ADA, OK—2026-06-25
PAN AMERICA ELECTRIC , INC.
ADA, OK—2026-06-25
CITATION OIL & GAS CORPORATION
EDMOND, OK—2026-06-23
BRICK EXPERTS INC.
Source