Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: CGC CONSULTING

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of CGC CONSULTING in RYAN AVE 40.041744, -75.044129, PHILADELPHIA, PA 19136 (NAICS 237110). OSHA activity number 344290853.

Watch CGC Consulting — free Get an email when a new federal OSHA severe-injury report for CGC Consulting is published. One employer, no account, unsubscribe in one click.
Establishment
CGC CONSULTING
Site address
RYAN AVE 40.041744, -75.044129
City
PHILADELPHIA
State
PA
ZIP
19136
Mailing
5400 LIMESTONE RD, WILMINGTON, DE 19808
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
237110
Employees
15
Ownership type
A

4 citations on file for this inspection.

1910.332 B01

Other-than-serious 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $12146.00 · Current $7895.00 Reduced
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments.    a) Jobsite: Ryan Ave (40.041744, -75.044129), Philadelphia, PA. - Employees conducting geotechnical drilling and sampling operations in proximity to an underground and energized 13.2 kv line were exposed to shock hazards as they were not provided with electrical safety related work practices respective to their job assignments.    Noted on or about 9/5/19.
Recent events (2)
  • — I (O) $7894.9
  • — Z (S) $12146

1910.333 A02

Other-than-serious 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $12145.00 · Current $7894.00 Reduced
29 CFR 1910.333(a)(2): Where exposed live parts were not deenergized (i.e., for reasons of increased or additional hazards or infeasibility), other safety-related work practices were not used to protect employees who could be exposed to the electrical hazards involved.    a) Jobsite: Ryan Ave (40.041744, -75.044129), Philadelphia, PA. - The employer did not use safety related practices to protect employees exposed to an underground and energized 13.2 kv line while conducting geotechnical drilling and sampling operations, such as, but not limited to, verifying the location of underground electrical utilities and maintaining the PA One Call utility mark-outs at the site after they were made.  An employee suffered an electrical shock when he drilled into the ground and contacted the underground line at a location that was previously marked, but was no longer visible.    Noted on or about 9/5/19.
Recent events (2)
  • — I (O) $7894.25
  • — Z (S) $12145

1910.335 B01

Other-than-serious 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.335(b)(1): Safety signs, safety symbols, or accident prevention tags were not used where necessary to warn employees about electrical hazards which may endanger them.    a) Jobsite: Ryan Ave (40.041744, -75.044129), Philadelphia, PA. - The employer did not ensure safety symbols were in place to warn employees conducting geotechnical drilling and sampling operations at the site of the energized underground 13.2 kv line, in that, PA One Call utility mark-outs were not maintained at the site to identify the location of the underground electrical lines.    Observed on or about 9/5/19.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.335 A01 I

Other-than-serious 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $12145.00 · Current $7894.00 Reduced
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed.    a) Jobsite: Ryan Ave (40.041744, -75.044129), Philadelphia, PA. - The employer did not provide employees conducting geotechnical drilling and sampling operations in proximity to an underground and energized 13.2 kv line with electrical protective equipment.    Noted on or about 9/5/19.
Recent events (2)
  • — I (O) $7894.25
  • — Z (S) $12145

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344290853.