GOSHEN, NY —
OSHA Inspection: UNITED PUMP & TANK, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of UNITED PUMP & TANK, INC. in 399 GREENWICH AVE, GOSHEN, NY 10924 (NAICS 238990). OSHA activity number 344418850.
Where did this inspection happen?
- Establishment
- UNITED PUMP & TANK, INC.
- Site address
- 399 GREENWICH AVE
- City
- GOSHEN
- State
- NY
- ZIP
- 10924
- Mailing
- PO BOX 214, PLATTEKILL, NY 12568
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238990
- Employees
- 3
- Ownership type
- A
Citations
6 citations on file for this inspection.
1926.407 B
- Issued
- Penalty
- Initial $3856.00 · Current $2621.00 Reduced
General-duty citation text
29 CFR 1926.407(b): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not approved as intrinsically safe or approved for the hazardous (classified) location or safe for the hazardous (classified) location: (a) At the worksite, on or prior to 10/30/19: Employees were using a Milwaukee Fuel 18v 1/2" Cordless Hammer Drill and Milwaukee Fuel 18v cordless reciprocating saw (Sawzall) to cut holes in FRP tanks containing residual gasoline tank sludge and vapors; tools are not approved for use in a Class I Division II environment, exposing employees to fire and explosion hazards.
Recent events (2)
- — I (S) $2620.5
- — Z (S) $3856
1926.651 G01 IV
- Issued
- Penalty
- Initial $3856.00 · Current $2621.00 Reduced
General-duty citation text
29 CFR 1926.651(g)(1)(iv): When controls were used that were intended to reduce the level of atmospheric contaminants to acceptable levels, testing was not conducted as often as necessary to ensure that the atmosphere remained safe: (a) At the worksite, on or prior to 10/30/19: While preparing a gasoline UST for removal, including excavation of the tank and opening the tank for ventilation, the employer did not conduct testing to ensure that concentration of flammable vapors in the excavation did not exceed a safe level, exposing employees to fire and explosion hazards.
Recent events (2)
- — I (S) $2620.5
- — Z (S) $3856
1926.651 I03
- Issued
- Penalty
- Initial $5398.00 · Current $2621.00 Reduced
General-duty citation text
29 CFR 1926.651(i)(3): Sidewalks, pavements and appurtenant structure shall not be undermined unless a support system or another method of protection is provided to protect employees from the possible collapse of such structures. (a) At the worksite, on or prior to 10/30/19: Pavement on the North and East side(s) of the excavation was undermined and not supported, exposing employees to struck-by and collapse hazards.
Recent events (2)
- — I (S) $2620.5
- — Z (S) $5398
1926.651 J02
- Issued
- Penalty
- Initial $5398.00 · Current $2621.00 Reduced
General-duty citation text
29 CFR 1926.651(j)(2): Protection was not provided by placing and keeping excavated or other materials or equipment at least 2 feet (.61m) from the edge of excavations, or by the use of retaining devices that were sufficient to prevent materials or equipment from falling or rolling into excavations, or by a combination of both if necessary. (a) At the worksite, on or prior to 10/30/19: Excavated pea gravel and concrete debris was not placed at least 2 feet from the edge of the excavation, exposing employees to engulfment or struck-by hazards.
Recent events (2)
- — I (S) $2620.5
- — Z (S) $5398
1926.651 K01
- Issued
- Penalty
- Initial $3856.00 · Current $2621.00 Reduced
General-duty citation text
29 CFR 1926.651(k)(1): Daily inspections of excavations, the adjacent areas, and protective systems were not made by a competent person for evidence of a situation that could have resulted in possible cave-ins, indications of failure of protective systems. (a) At the worksite, on or prior to 10/30/19: UST excavation and adjacent area was not inspected by a competent person.
Recent events (2)
- — I (S) $2620.5
- — Z (S) $3856
1926.652 A01
- Issued
- Penalty
- Initial $3856.00 · Current $2621.00 Reduced
General-duty citation text
29 CFR 1926.652(a)(1): Each employee in an excavation was not protected from cave-ins by an adequate protective system designed in accordance with 29 CFR 1926.652 (b) or (c). (a) At the worksite, on or prior to 10/30/19: UST excavation was not properly sloped/shored/or otherwise protected from collapse.
Recent events (2)
- — I (S) $2620.5
- — Z (S) $3856
More inspections at UNITED PUMP & TANK, INC.
GOSHEN, NY—2019-10-31 00:00:00
UNITED PUMP & TANK, INC.
View UNITED PUMP & TANK, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238990)
NEW YORK, NY—2026-07-09
PALM INDUSTRIES LLC
NEW YORK, NY—2026-07-09
PALM INDUSTRIES LLC
EL PASO, TX—2026-07-09
RM CRANE & RIGGING LLC.
LAKEWOOD, WA—2026-07-08
WA317992018 - HARMON INC DBA HARMON SERVICE GLAZING INC
VICTOR, NY—2026-07-08
DIMARCO CONSTRUCTORS
More inspections in NY
POUGHKEEPSIE, NY—2026-07-13
MARCO BOARD HOUSE, INC.
CORTLANDT MANOR, NY—2026-07-13
LG BUILDERS INC.
CORTLANDT MANOR, NY—2026-07-13
RJW RENOVATIONS, LLC
HEMPSTEAD, NY—2026-07-13
NYSDOCCS NASSAU AREA OFFICE
NIAGARA FALLS, NY—2026-07-10
NTVI FEDERAL INC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344418850.