MACON, MS —
OSHA Inspection: SOUTHERN SEED AND FEED, LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of SOUTHERN SEED AND FEED, LLC in 5069 MAGNOLIA DRIVE, MACON, MS 39341 (NAICS 311119). OSHA activity number 344457981.
Where did this inspection happen?
- Establishment
- SOUTHERN SEED AND FEED, LLC
- Site address
- 5069 MAGNOLIA DRIVE
- City
- MACON
- State
- MS
- ZIP
- 39341
- Mailing
- 5069 MAGNOLIA DRIVE, MACON, MS 39341
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311119
- Employees
- 37
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.272 J02 II
- Issued
- Penalty
- Initial $5735.00 · Current $3441.00 Reduced
General-duty citation text
29 CFR 1910.272(j)(2)(ii): The employer did not immediately remove any fugitive grain dust accumulations whenever the exceeded 1/ 8 inch (.32cm) at priority housekeeping areas, pursuant to the housekeeping program for grain elevators. a. Bagging Area - On or about November 20, 2019 grain dust was accumulated on elevated surfaces greater than 1/8 inch in depth, exposing employees to fire hazards.
Recent events (2)
- — I (S) $3441
- — Z (S) $5735
1910.305 B01 I
- Issued
- Abate by
- Penalty
- Initial $3441.00 · Current $2065.00 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(i): Openings through which conductors entered cutout boxes, cabinets, or fittings were not effectively closed. a. Small Hopper, Bagging Area - On or about November 20, 2019 the opening where electrical wiring entered bulk ingredient electric motor was not closed, exposing employees to fire hazards.
Recent events (2)
- — I (S) $2064.6
- — Z (S) $3441
1910.305 C04
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(c)(4): Snap switches mounted in boxes did not have faceplates installed so as to completely cover the opening and seat against the finished surface. a. Pallet Area - On or about November 20, 2019 the exhaust fan switch did not have a cover, exposing employees to electrical hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 311119)
CHILLICOTHE, MO—2026-06-30
MILBANK MILLS INC
SALT LAKE CITY, UT—2026-06-25
INVE AQUACULTURE INC
GREELEY, CO—2026-06-16
GREELEY SEED CO., LLC
HELM, CA—2026-06-15
B&R CUSTOM CHOPPING LLC
LEXINGTON, NE—2026-06-05
LIVESTOCK NUTRITION CENTER
More inspections in MS
LAUREL, MS—2026-07-01
THERMO-KOOL
HORN LAKE, MS—2026-07-01
NEWLY WEDS FOODS, INC.
GAUTIER, MS—2026-07-01
DOUBLE R GAUTIER, LLC
OLIVE BRANCH, MS—2026-06-30
HYVE SOLUTIONS
GAUTIER, MS—2026-06-30
STEVE WILSON ENTERPRISE
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344457981.