WILMINGTON, MA —
OSHA Inspection: CHEMGENES CORPORATION
Referral inspection · Health discipline
At a glance
On , OSHA opened a referral health inspection of CHEMGENES CORPORATION in 33 INDUSTRIAL WAY, WILMINGTON, MA 01887 (NAICS 541711). OSHA activity number 344550991.
Where did this inspection happen?
- Establishment
- CHEMGENES CORPORATION
- Site address
- 33 INDUSTRIAL WAY
- City
- WILMINGTON
- State
- MA
- ZIP
- 01887
- Mailing
- 33 INDUSTRIAL WAY, WILMINGTON, MA 01887
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 541711
- Employees
- 43
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.106 H04 III A
- Issued
- Abate by
- Penalty
- Initial $9446.00 · Current $4700.00 Reduced
General-duty citation text
29 CFR 1910.106(h)(4)(iii)(a): The transfer of large quantities of flammable liquids was not through piping, by means of pumps, or by water displacement. 33 Industrial Way, Wilmington, MA 01887 On or about 1/9/20, employees were exposed to fire hazards from a flammable liquid that was transferred using compressed air. A fire occurred during a transfer process.
Recent events (2)
- — I (S) $4700
- — Z (S) $9446
1910.305 G01 IV A
- Issued
- Abate by
- Penalty
- Initial $9446.00 · Current $4700.00 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: Production floor, 33 Industrial Way, Wilmington, MA. a) On or about 1/9/20, a flexible cord was used to move power from a receptacle fed by a fixed conduit to a relocatable power tap in a location away from the receptacle. During transfer of a silica slurry that contained a flammable material, the material caught on fire.
Recent events (2)
- — I (S) $4700
- — Z (S) $9446
1910.307 B
- Issued
- Abate by
- Penalty
- Initial $9446.00 · Current $4700.00 Reduced
General-duty citation text
29 CFR 1910.307(b): Areas designated as hazardous (classified) locations under the Class and Zone system and areas designated under the Class and Division system established after August 13, 2007 were not properly documented: 33 Industrial Way, Wilmington, MA 01887 On or about 1/9/20, employees were exposed to fire hazards while working with flammable liquids in an area that was not designated as a Class I, Division 2 hazardous location.
Recent events (2)
- — I (S) $4700
- — Z (S) $9446
1910.307 C01
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.307(c)(1): Equipment and associated wiring not approved as intrinsically safe was permitted in a hazardous location (Classified) location for which it was not approved 33 Industrial Way, Wilmington, MA 01887 On or about 1/9/20, employees were exposed to fire hazards while working with flammable liquids in an area that was not designated as a Class I, Division 2 hazardous location. A relocatable power tap, and electrical conduit in the area did not meet the requirements to be intrinsically safe.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.307 D
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.307(d): Conduits in hazardous (classified) locations were not threaded: 33 Industrial Way, Wilmington, MA 01887 On or about 1/9/20, employees were exposed to fire hazards while working with flammable liquids in an area where electrical conduit was not threaded.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.1200 H01
- Issued
- Penalty
- Initial $5735.00 · Current $1800.00 Reduced
General-duty citation text
29 CFR 1910.1200(h)(1): Employees were not provided effective information and training on hazardous chemicals in their work area at the time of their initial assignment and whenever a new hazard that the employees had not been previously trained about was introduced into their work area: 33 Industrial Way, Wilmington, MA 01887 On or about 1/9/20, employees were not adequately trained on the hazards of chemicals including, but not limited to ethyl acetate and hexanes.
Recent events (2)
- — I (O) $1800
- — Z (S) $5735
More inspections in this industry (NAICS 541711)
SEATTLE, WA—2025-05-28
WA317986271 - MONOD BIO INC
SEATTLE, WA—2024-06-04 00:00:00
WA317980508 - DISCOVERY LIFE SCIENCES LLC
WINCHESTER, KY—2024-04-04 00:00:00
66893 - DANIMER SCIENTIFIC KENTUCKY INC
BREVARD, NC—2023-12-13 00:00:00
155648 - RAYBOW USA, INC.
BREVARD, NC—2023-12-13 00:00:00
155645 - RAYBOW USA, INC.
More inspections in MA
WORCESTER, MA—2026-07-10
QUINSIGAMOND COMMUNITY COLLEGE