Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: DIONISIO ROLL-OFF SERVICE, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of DIONISIO ROLL-OFF SERVICE, INC. in 30679 E US HWY 50, LA JUNTA, CO 81050 (NAICS 423930). OSHA activity number 344629076.

Watch Dionisio Roll-Off Service, INC. — free Get an email when a new federal OSHA severe-injury report for Dionisio Roll-Off Service, INC. is published. One employer, no account, unsubscribe in one click.
Site address
30679 E US HWY 50
City
LA JUNTA
State
CO
ZIP
81050
Mailing
PO BOX 11253, PUEBLO, CO 81001
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
423930
Employees
4
Ownership type
A

6 citations on file for this inspection.

1910.215 A01

Serious Gravity 1 1 instance 2 exposed
Issued
Penalty
Initial $1475.00 · Current $737.00 Reduced
29 CFR 1910.215(a)(1): Abrasive wheel(s) used on grinding machinery were not used with safety guard(s):    a) On or about February 12, 2020, and at times prior, the employer did not ensure that abrasive wheels on grinding machines were used with safety guards. Employees of Dionisio Metals Recycling were exposed to struck-by hazards, in that a 5" Central Machinery model 907 grinder was used without the side abrasive wheel guard.      Abatement Note: Abatement certification is not required for this item.
Recent events (2)
  • — I (S) $737
  • — Z (S) $1475

1910.215 A04

Serious Gravity 1 1 instance 2 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.215(a)(4): Work rest(s) on grinding machinery were not adjusted closely to the wheel with a maximum opening of one eighth inch:  a) On or about February 12, 2020, and at times prior, the employer did not ensure that work rests on grinding machinery were adjusted closely to the wheel with a maximum opening of one eighth inch. Employees of Dionisio Metals Recycling were exposed to struck-by hazards, in that the opening between the abrasive wheel of a  5" Central Machinery model 907 grinder and the work rest was 1 inch.  Abatement Note: Abatement certification is not required for this item.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B01 II

Serious Gravity 1 3 instances 2 exposed
Issued
Abate by
Penalty
Initial $1735.00 · Current $867.00 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:    a) On or about February 12, 2020, and at times prior, the employer did not ensure that unused openings in boxes, cabinets, or fittings were effectively closed. Employees of Dionisio Metals Recycling were exposed to contact with electrical hazards, in that receptacles with unused openings were not effectively closed exposing the live wiring as follows:      1- Receptacle on the North wall of the processing area had two unused openings.      2- Receptacle on the West wall of the processing area had one unused opening.      3- Receptacle on the South wall of the storage area had one unused opening.    Abatement Note: Abatement certification is required for this item (see enclosed "Certification of Corrective Action Worksheet").
Recent events (2)
  • — I (S) $867
  • — Z (S) $1735

1910.305 G01 II L

Serious Gravity 5 2 instances 2 exposed
Issued
Abate by
Penalty
Initial $2313.00 · Current $1156.00 Reduced
29 CFR 1910.305(g)(1)(ii): Flexible cords and cables were used for a purpose not approved by paragraphs A thorough L of this section:     a) On or about February 12, 2020, and at times prior, the employer used flexible cords for purposes not approved by paragraphs A through L of this section. Employees of Dionisio Metals Recycling were exposed to contact with electrical hazards in that the employer used flexible cords as a substitute for permanent wiring as follows:      1- A flexible cord was used to provide power to 120V scale and equipment in the customer intake area.      2- A flexible cord was used to provide power to 120V equipment for the aluminum can conveyor/hopper in the outdoor yard.                  Abatement Note: Abatement certification is required for this item (see enclosed "Certification of Corrective Action Worksheet").
Recent events (2)
  • — I (S) $1156
  • — Z (S) $2313

1910.37 A03

Other-than-serious 1 instance 3 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed:  a) On or about February 12, 2020, and at times prior, the employer did not ensure that exit routes were kept free and unobstructed. Employees of Dionisio Metals Recycling were exposed to fire and entrapment hazards in that the south side storage area exit was blocked by equipment and materials.     Abatement Note: Abatement certification is not required for this item.   .
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 G01

Other-than-serious 1 instance 3 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:  a) On or about February 12, 2020, and at times prior, the employer did not ensure that sufficient access and working space was provided and maintained about electric equipment operating at less than 600 volts. Employees of Dionisio Metals Recycling were exposed to electrical hazards in that access to electrical panels in the main electrical room was blocked by tools, equipment, and materials.    Abatement Note: Abatement certification is not required for this item.