Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: U.S. DEPARTMENT OF VETERANS AFFAIRS

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of U.S. DEPARTMENT OF VETERANS AFFAIRS in ATTN: JOHN LI (1-08 ENG) 3601 SOUTH 6TH AVENUE, TUCSON, AZ 85723 (NAICS 622110). OSHA activity number 344653795.

Watch U.S. Department OF Veterans Affairs — free Get an email when a new federal OSHA severe-injury report for U.S. Department OF Veterans Affairs is published. One employer, no account, unsubscribe in one click.
Site address
ATTN: JOHN LI (1-08 ENG) 3601 SOUTH 6TH AVENUE
City
TUCSON
State
AZ
ZIP
85723
Mailing
SOUTHERN ARIZONA VA HEALTH CARE SYSTEM 3601 SOUTH 6TH AVENUE, TUCSON, AZ 85723
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
622110
Employees
2845
Ownership type
D

5 citations on file for this inspection.

1910.212 A01

Serious Gravity 5 2 instances 17 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:  (a) BUILDING 43: The Porter Cable Drill Press SN-063243 was not guarded to protect employees from contact with the rotating bit, exposing them to caught-in hazards.  (b) BOILER ROOM: The Rockwell Drill Press SN-1784343 was not guarded to protect employees from contact with the rotating bit, exposing them to caught-in hazards.
Recent events (1)
  • — Z (S) $0

1910.303 G01 I B

Serious Gravity 5 1 instance 13 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(g)(1)(i)(B): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater :  (a) BUILDING 43: The electrical panel was blocked by an portable air exchanger and a tool box exposing employees to fire and electrocution hazards.
Recent events (1)
  • — Z (S) $0

1910.303 G01 III

Serious Gravity 5 1 instance 1 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(g)(1)(iii): The employer did not ensure that at least one entrance of sufficient area was provided to give access to the working space about electric equipment 600 Volts, nominal, or less. BUILDING 44: The main disconnect panel was blocked by cactus preventing access to the panel in the event of an emergency, exposing employees to electrocution, burn, and smoke inhalation hazards.
Recent events (1)
  • — Z (S) $0

1910.104 B08 VIII

Other-than-serious 1 instance 2 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.104(b)(8)(viii): "Placarding." The bulk oxygen storage location shall be permanently placarded to indicate: "OXYGEN - NO SMOKING - NO OPEN FLAMES", or an equivalent warning.  29 CFR 1910.104(b)(8)(viii): "Placarding." The bulk oxygen storage location shall be permanently placarded to indicate: "OXYGEN - NO SMOKING - NO OPEN FLAMES", or an equivalent warning.  29 CFR 1910.104(b)(8)(viii): "Placarding." The bulk oxygen storage location shall be permanently placarded to indicate: "OXYGEN - NO SMOKING - NO OPEN FLAMES", or an equivalent warning.     ROOM A148:  Signs had not been posted to make employees aware of the location and dangers associated oxygen storage, exposing them to hazards from fires.
Recent events (1)
  • — Z (O) $0

1910.178 Q07

Other-than-serious 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.178(q)(7): Industrial trucks were not examined before being placed in service: BUILDING 14 WAREHOUSE:  The Hyster H70FT forklift was not examined before being placed in use exposing employees to injury from defects.