OSHA Inspection: MERCURY FUEL SERVICE INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of MERCURY FUEL SERVICE INC. in 68 WATERBURY ROAD, PROSPECT, CT 06712 (NAICS 447110). OSHA activity number 344887849.

Watch Mercury Fuel Service INC. — free Get an email when a new federal OSHA severe-injury report for Mercury Fuel Service INC. is published. One employer, no account, unsubscribe in one click.
Site address
68 WATERBURY ROAD
City
PROSPECT
State
CT
ZIP
06712
Mailing
68 WATERBURY ROAD, PROSPECT, CT 06712
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
447110
Employees
4
Ownership type
A

3 citations on file for this inspection.

1910.36 G02

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Penalty
Initial $7022.00 · Current $0.00 Reduced
1910.36(g)(2): The employer did not ensure an exit access was at least 28 inches (71.1 cm) wide at all points.  WORKSITE: The employer did not ensure an exit access was at least 28 inches wide at all points by maintaining an exit route measuring 24.5 inches wide at the narrowest point for workers performing tasks such as (but not limited to) turning fuel pump breakers on and off twice daily.
Recent events (2)
  • — I (S) $0
  • — Z (S) $7022

1910.303 B01

Serious Gravity 5 1 instance 1 exposed
Issued
Penalty
Initial $7022.00 · Current $4915.00 Reduced
29 CFR  1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees.   WORKSITE: Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to the employee using a wall-mounted breaker box with an unsecured nonmetallic-sheathed cable causing the cable to rub against the metal corner of the box creating a fire hazard. National Electric Code (2017) 334.39 Securing and Supporting requires nonmetallic-sheathed cables entering enclosures to be secured within 12 inches of entry which would prevent the hazard.
Recent events (2)
  • — I (S) $4915.4
  • — Z (S) $7022

1910.303 G01 I A

Serious Gravity 5 1 instance 1 exposed
Issued
Penalty
Initial $7022.00 · Current $4915.00 Reduced
29 CFR  1910.303(g)(1)(i)(A): The depth of the working space in the direction of access to live parts may not be less than indicated in Table S-1. Distances shall be measured from the live parts if they are exposed or from the enclosure front or opening if they are enclosed.  WORKSITE: The employer did not maintain a minimum working clearance of three (3) feet in front of the wall mounted breaker box. The front of the box was obstructed by a microwave, mini-refrigerator, and plastic cups.  The area in the direction of access to the live parts enclosure contained a five-gallon bucket with mop and broom heads, a plastic crate, a mini-fridge, and a small microwave. These materials were stored directly in the direction of access to the breaker box and there was no clear working space. Materials adjacent to the breaker box may also become energized during access to the breaker box, including a metal pole which protrudes from the 5-gallon bucket to within approximately one foot of the breaker box.
Recent events (2)
  • — I (S) $4915.4
  • — Z (S) $7022

AK, INC