Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: ST EDWARD HOME

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of ST EDWARD HOME in 3125 SMITH ROAD, FAIRLAWN, OH 44333 (NAICS 623110). OSHA activity number 344917141.

Watch ST Edward Home — free Get an email when a new federal OSHA severe-injury report for ST Edward Home is published. One employer, no account, unsubscribe in one click.
Establishment
ST EDWARD HOME
Site address
3125 SMITH ROAD
City
FAIRLAWN
State
OH
ZIP
44333
Mailing
3125 SMITH ROAD, FAIRLAWN, OH 44333
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
623110
Employees
280
Ownership type
A

3 citations on file for this inspection.

1910.332 B01

Serious Gravity 10 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $13653.00 · Current $10240.00 Reduced
29 CFR 1910.332(b)(1) ): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:  On or about August 24, 2020, the employer did not ensure maintenance employees were provided with training on electrical safety related work practices to include but not limited to, live/dead/live testing of electrical test equipment, deenergizing equipment before performing work, lock out/tag out procedures involving electrical equipment, and personal protective equipment for electrical hazards.
Recent events (2)
  • — I (S) $10240
  • — Z (S) $13653

1910.333 A01

Serious Gravity 10 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.333(a)(1): Live parts to which an employee was exposed were not deenergized before the employee worked on or near them:  On or about August 24, 2020, the employer did not ensure maintenance employees performing work on the heat pump unit, to include but not limited to the blower motors capacitor, properly deenergized the piece of equipment.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.335 A01 I

Deleted Serious Gravity 10 4 instances 5 exposed
Issued
Abate by
Penalty
Initial $13653.00 · Current $0.00 Reduced
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed:  a) On or about August 24, 2020, the employer did not ensure maintenance employees were provided with arc rated upper torso clothing to protect against potential arc flash hazards when verifying zero energy on the exposed to 277 volt heat pump system circuit.  b) On or about August 24, 2020, the employer did not ensure maintenance employees were provided with arc rated clothing for the legs to protect against potential arc flash hazards when verifying zero energy on the exposed to 277 volt heat pump system circuit.  c) On or about August 24, 2020, the employer did not ensure maintenance employees were provided with leather gloves to protect against potential arc flash hazards when verifying zero energy on the exposed to 277 volt heat pump system circuit.  d) On or about August 24, 2020, the employer did not ensure maintenance employees were provided with arc rated face shields and hard hats to protect against potential arc flash hazards when verifying zero energy on the exposed 277 volt heat pump system circuit.
Recent events (2)
  • — I (S) $0
  • — Z (S) $13653

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344917141.