Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: WIN-SAM INC

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of WIN-SAM INC in 2601 N FLOYD ROAD, RICHARDSON, TX 75080 (NAICS 221122). OSHA activity number 345115331.

Watch Win-Sam INC — free Get an email when a new federal OSHA severe-injury report for Win-Sam INC is published. One employer, no account, unsubscribe in one click.
Establishment
WIN-SAM INC
Site address
2601 N FLOYD ROAD
City
RICHARDSON
State
TX
ZIP
75080
Mailing
2822 WEST 5TH STREET # 2159, FORT WORTH, TX 76107
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Last modified
Data loaded
NAICS code
221122
Employees
13
Ownership type
A

7 citations on file for this inspection.

1910.269 A03 III

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $9557.00 · Current $9557.00
29 CFR 1910.269(a)(3)(iii): The contract employer and the host employer did not coordinate their work rules and procedures so that each employee of the contract employer and the host employer was protected as required by this section:  (a) On or about December 19, 2020, employees working on electrical equipment within the yard of the central energy plant were exposed to an electrical hazard when the employer did not coordinate their work rules and procedures.
Recent events (2)
  • — C (S) $9557
  • — Z (S) $9557

1910.269 C01 I

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $9557.00 · Current $9557.00
29 CFR 1910.269(c)(1)(i): In assigning an employee to perform a job, the employer did not provide the employee in charge of the job with all available information that relates to the determination of existing characteristics and conditions required by paragraph (a)(4) of this section:  (a) On or about December 19, 2020 the employee in charge of overseeing maintenance of electrical equipment was not provided with all available information exposing employees to an electrical hazard.
Recent events (2)
  • — C (S) $9557
  • — Z (S) $9557

1910.269 C01 II

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.269(c)(1)(ii):The employer did not ensure that the employee in charge conducted a job briefing that met paragraphs (c)(2) though (c)(4) of this section with the employees involved before they start each job:  On or about December 19, 2020, the employee in charge did not conduct with the crew a job briefing meeting the requirements exposing employees to an electrical hazard.
Recent events (2)
  • — C (S) $0
  • — Z (S) $0

1910.269 L01 III

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $9557.00 · Current $9557.00
29 CFR 1910.269(l)(1)(iii): Electric lines and equipment were not considered and treated as energized unless they had been deenergized in accordance with paragraph (d) or (m) of this section:  (a) On or about December 19, 2020, employees working on electrical equipment were exposed to an electrical hazard when the equipment was not treated as energized.
Recent events (2)
  • — C (S) $9557
  • — Z (S) $9557

1910.269 M02 I

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.269(m)(2)(i): If a system operator is in charge of the lines or equipment and their means of disconnection, the employer shall designate one employee in the crew to be in charge of the clearance and shall comply with all of the requirements of paragraph (m)(3) of this section in the order specified.   (a) On or about December 19, 2020, employees working on electrical equipment were exposed to an electrical hazard when the requirements of paragraph (m)(3) of this section were not met.
Recent events (2)
  • — C (S) $0
  • — Z (S) $0

1910.269 M03 II

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.269(m)(3)(ii):The employer did not ensure that all switches, disconnectors, jumpers, taps, and other means through which known sources of electric energy might be supplied to the particular lines and equipment were de-energized / inoperable (i.e. open) and then did not ensure that such means were tagged to indicate that employees were at work:  (a) On or about December 19, 2020, employees working on electrical equipment were exposed to an electrical hazard when the known sources of electric energy that might be supplied to the equipment were not de-energized/open and tagged to indicate employees were at work.
Recent events (2)
  • — C (S) $0
  • — Z (S) $0

1910.269 L08 V

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $9557.00 · Current $9557.00
29 CFR 1910.269(l)(8)(v): The employer did not ensure that each employee exposed to hazards from electric arcs wore protective clothing and other protective equipment that had an arc rating greater than or equal to the heat energy estimated under paragraph (l)(8)(ii) of this section whenever that estimate exceeded 2.0 Cal/cm2:  (a) On or about December 19, 2020, employees working without wearing adequate protective clothing and other protective equipment on an electrical box were exposed to an electrical arc hazard.
Recent events (2)
  • — C (S) $9557
  • — Z (S) $9557

PSE&G

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345115331.