RICHARDSON, TX —
OSHA Inspection: WIN-SAM INC
Unprogrammed Related inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Related safety inspection of WIN-SAM INC in 2601 N FLOYD ROAD, RICHARDSON, TX 75080 (NAICS 221122). OSHA activity number 345115331.
Where did this inspection happen?
- Establishment
- WIN-SAM INC
- Site address
- 2601 N FLOYD ROAD
- City
- RICHARDSON
- State
- TX
- ZIP
- 75080
- Mailing
- 2822 WEST 5TH STREET # 2159, FORT WORTH, TX 76107
What kind of inspection was it?
- Inspection type
- Unprogrammed Related (G)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221122
- Employees
- 13
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.269 A03 III
- Issued
- Abate by
- Penalty
- Initial $9557.00 · Current $9557.00
General-duty citation text
29 CFR 1910.269(a)(3)(iii): The contract employer and the host employer did not coordinate their work rules and procedures so that each employee of the contract employer and the host employer was protected as required by this section: (a) On or about December 19, 2020, employees working on electrical equipment within the yard of the central energy plant were exposed to an electrical hazard when the employer did not coordinate their work rules and procedures.
Recent events (2)
- — C (S) $9557
- — Z (S) $9557
1910.269 C01 I
- Issued
- Abate by
- Penalty
- Initial $9557.00 · Current $9557.00
General-duty citation text
29 CFR 1910.269(c)(1)(i): In assigning an employee to perform a job, the employer did not provide the employee in charge of the job with all available information that relates to the determination of existing characteristics and conditions required by paragraph (a)(4) of this section: (a) On or about December 19, 2020 the employee in charge of overseeing maintenance of electrical equipment was not provided with all available information exposing employees to an electrical hazard.
Recent events (2)
- — C (S) $9557
- — Z (S) $9557
1910.269 C01 II
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.269(c)(1)(ii):The employer did not ensure that the employee in charge conducted a job briefing that met paragraphs (c)(2) though (c)(4) of this section with the employees involved before they start each job: On or about December 19, 2020, the employee in charge did not conduct with the crew a job briefing meeting the requirements exposing employees to an electrical hazard.
Recent events (2)
- — C (S) $0
- — Z (S) $0
1910.269 L01 III
- Issued
- Abate by
- Penalty
- Initial $9557.00 · Current $9557.00
General-duty citation text
29 CFR 1910.269(l)(1)(iii): Electric lines and equipment were not considered and treated as energized unless they had been deenergized in accordance with paragraph (d) or (m) of this section: (a) On or about December 19, 2020, employees working on electrical equipment were exposed to an electrical hazard when the equipment was not treated as energized.
Recent events (2)
- — C (S) $9557
- — Z (S) $9557
1910.269 M02 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.269(m)(2)(i): If a system operator is in charge of the lines or equipment and their means of disconnection, the employer shall designate one employee in the crew to be in charge of the clearance and shall comply with all of the requirements of paragraph (m)(3) of this section in the order specified. (a) On or about December 19, 2020, employees working on electrical equipment were exposed to an electrical hazard when the requirements of paragraph (m)(3) of this section were not met.
Recent events (2)
- — C (S) $0
- — Z (S) $0
1910.269 M03 II
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.269(m)(3)(ii):The employer did not ensure that all switches, disconnectors, jumpers, taps, and other means through which known sources of electric energy might be supplied to the particular lines and equipment were de-energized / inoperable (i.e. open) and then did not ensure that such means were tagged to indicate that employees were at work: (a) On or about December 19, 2020, employees working on electrical equipment were exposed to an electrical hazard when the known sources of electric energy that might be supplied to the equipment were not de-energized/open and tagged to indicate employees were at work.
Recent events (2)
- — C (S) $0
- — Z (S) $0
1910.269 L08 V
- Issued
- Abate by
- Penalty
- Initial $9557.00 · Current $9557.00
General-duty citation text
29 CFR 1910.269(l)(8)(v): The employer did not ensure that each employee exposed to hazards from electric arcs wore protective clothing and other protective equipment that had an arc rating greater than or equal to the heat energy estimated under paragraph (l)(8)(ii) of this section whenever that estimate exceeded 2.0 Cal/cm2: (a) On or about December 19, 2020, employees working without wearing adequate protective clothing and other protective equipment on an electrical box were exposed to an electrical arc hazard.
Recent events (2)
- — C (S) $9557
- — Z (S) $9557
More inspections in this industry (NAICS 221122)
MONROE, GA—2026-07-14
WALTON EMC
DETROIT, MI—2026-07-14
EES COKE BATTERY, LLC
LITTLETON, MA—2026-07-01
LITTLETON ELECTRIC LIGHT & WATER DEPARTMENT
PISCATAWAY, NJ—2026-06-30
PSE&G
BAYTOWN, TX—2026-06-30
CENTERPOINT ENERGY
More inspections in TX
WICHITA FALLS, TX—2026-07-16
UNITED RENTALS, INC.
SAN MARCOS, TX—2026-07-16
CASA MECHANICAL SERVICES, LTD.
CLARKSVILLE, TX—2026-07-15
SEQUOIAS TREE EXPERT LLC
EL PASO, TX—2026-07-15
SURE STEEL
CORPUS CHRISTI, TX—2026-07-15
NORTH STAR ENERGY SOLUTIONS LLC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345115331.