MANCHESTER, CT —
OSHA Inspection: CHAMPLIN-PACKRITE, INC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of CHAMPLIN-PACKRITE, INC in 151 BATSON DRIVE, MANCHESTER, CT 06042 (NAICS 321920). OSHA activity number 345135842.
Where did this inspection happen?
- Establishment
- CHAMPLIN-PACKRITE, INC
- Site address
- 151 BATSON DRIVE
- City
- MANCHESTER
- State
- CT
- ZIP
- 06042
- Mailing
- 151 BATSON DRIVE, MANCHESTER, CT 06042
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 321920
- Employees
- 24
- Ownership type
- A
Citations
15 citations on file for this inspection.
1910.36 B01
- Issued
- Abate by
- Penalty
- Initial $1989.00 · Current $995.00 Reduced
General-duty citation text
29 CFR 1910.36(b)(1): At least two exits routes were not available to permit prompt evacuation of employees during an emergency: Box Division, 236 Hamilton Street, Hartford, Connecticut, Warehouse: On, or about, February 5, 2021, the warehouse was only provided with a single entrance/exit. National Fire Protection Association (NFPA) Standard 101, Life Safety Code required at least two exits for the size and configuration of the space.
Recent events (2)
- — I (S) $994.5
- — Z (S) $1989
1910.37 A04
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times: A. Box Division, 236 Hamilton Street, Hartford, Connecticut, Inside Loading Dock: On, or about, February 5, 2021, the following exterior exits had not been maintained: 1. South Wall: The door was blocked by snow the exit sign was not lit. 2. North Wall: The exit sign was not lit. B. Box Division, 236 Hamilton Street, Hartford, Connecticut, Corrugated Department: On, or about, February 5, 2021, the sign provided over the exit door on the north wall was not lit.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.106 E06 I
- Issued
- Penalty
- Initial $2255.00 · Current $1128.00 Reduced
General-duty citation text
29 CFR 1910.106(e)(6)(i): Adequate precautions were not taken to prevent the ignition of flammable vapors: Box Division, 236 Hamilton Street, Hartford, Connecticut, Wood Shop: On, or about, February 5, 2021, 3M Holdfast Adhesive, a Category 1 flammable liquid with a flashpoint of -42 degrees, F, was applied to box components using an airless spray gun. Neither the spray gun nor the tank of adhesive was grounded to prevent the build-up of static electricity.
Recent events (2)
- — I (S) $1127.5
- — Z (S) $2255
1910.178 L01 I
- Issued
- Penalty
- Initial $1691.00 · Current $846.00 Reduced
General-duty citation text
29 CFR 1910.178(l)(1)(i): The employer did not ensure that each powered industrial truck operator is competent to operate a powered industrial truck safely, as demonstrated by the successful completion of the training and evaluation specified in this paragraph (l): I-Hub Packaging & Logistics Division, Warehouse: On, or about, February 2, 2021, an employee who operated a forktruck daily had not been provided with training regarding the safe operation of powered industrial trucks.
Recent events (2)
- — I (S) $845.5
- — Z (S) $1691
1910.212 A01
- Issued
- Abate by
- Penalty
- Initial $3316.00 · Current $1658.00 Reduced
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: A. Box Division, 236 Hamilton Street, Hartford, Connecticut, Wood Shop: On, or about, February 5, 2021, the barrier guard provided on the Universal Box Slitter did not prevent access to the slitting knives from the top and left a three inch wide gap at the feed into the cutting area. B. Box Division, 236 Hamilton Street, Hartford, Connecticut, Wood Shop: On, or about, February 5, 2021, the Economy Baler was not provided with an interlocked access doors for the loading chamber and the bale chamber. C. Box Division, 236 Hamilton Street, Hartford, Connecticut, Wood Shop: On, or about, February 5, 2021, safeguarding was not provided on the Heina NC controlled router to protect the operator from the point of operation and other moving machine parts, such as the traversing table. D. Box Division, 236 Hamilton Street, Hartford, Connecticut, Wood Shop: On, or about, February 5, 2021, the guards provided on the two automatic radial saws were not properly adjusted.
Recent events (2)
- — I (S) $1658
- — Z (S) $3316
1910.303 B02
- Issued
- Penalty
- Initial $1989.00 · Current $995.00 Reduced
General-duty citation text
29 CFR 1910.303(b)(2):Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: I-Hub Packaging & Logistics Division, Bullpen 1: On, or about, February 4, 2021, a relocatable power tap used to energize a computer workstation was energized through an orange and black extension cord. The UL Whitebook contains limitations regarding the use of relocatable power taps, including emerging them through extension cords.
Recent events (2)
- — I (S) $994.5
- — Z (S) $1989
1910.305 G01 IV A
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: A. I-Hub Packaging & Logistics Division, Dock Area: On, or about, February 4, 2021, an orange extension cord was used to energize the motor on an overhead door. B. I-Hub Packaging & Logistics Division, Bullpen 1: On, or about, February 4, 2021, an orange and black extension cord was used to energize a computer and peripherals located at the second work station. C. Box Division, 236 Hamilton Street, Hartford, Connecticut, Middle Room: On, or about, February 5, 2021, a Delta drill press head that was mounted to the wall was energized through a black extension cord. D. Box Division, 236 Hamilton Street, Hartford, Connecticut, Corrugated Department: On, or about, February 5, 2021, a yellow extension cord was used to energize a computer at the job center station. Abatement Note: Per 29 CFR 1910.305(g)(1)(iv)(D), flexible cords and cables cannot be attached to building surfaces.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 B07 IV
- Issued
- Penalty
- Initial $1691.00 · Current $846.00 Reduced
General-duty citation text
29 CFR 1910.303(b)(7)(iv): There were damaged parts that adversely affected safe operation or mechanical strength of the equipment, such as parts that were broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating: I-Hub Packaging & Logistics Division, Dock Area: On, or about, February 4, 2021, a wall mounted quad receptacle was damaged, exposing the internal metal parts.
Recent events (2)
- — I (S) $845.5
- — Z (S) $1691
1910.305 B02 I
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: I-Hub Packaging & Logistics Division: On, or about, February 4, 2021, in the following locations, receptacles were not provided with a cover: A. Dock Area: Quad receptacle mounted on the wall near the propane storage cage. B. Bullpen 1: Duplex receptacle mounted on the wall to energize a server and relocatable power tap.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 G01 I A
- Issued
- Abate by
- Penalty
- Initial $1989.00 · Current $995.00 Reduced
General-duty citation text
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening whwere they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910: I-Hub Packaging & Logistics Division, Far Warehouse: On, or about, February 4, 2021, a floor mounted bollard and metal fencing was located within the working space of a 480/277 volt Crouse-Hinds distribution panel.
Recent events (2)
- — I (S) $994.5
- — Z (S) $1989
1910.303 G01 II
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(g)(1)(ii):The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: I-Hub Packaging & Logistics Division, Far Warehouse: On, or about, February 4, 2021, a pallet of material was stored in front of Panel 13, a Square D Load Center.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.110 F04 I
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.110(f)(4)(i): The quantity of LP-Gas stored within a building exceeded 300 pounds: I-Hub Packaging & Logistics Division, Dock Area: On, or about, February 4, 2021, sixteen LPG cylinders were stored inside of the building.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.184 D
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.184(d):Damaged or defective sling(s) were not immediately removed from service: I-Hub Packaging & Logistics Division, Crane Room: On, or about, February 4, 2021, a 10 foot long Lift-All nylon sling was damaged in that it was cut in two places and the identification tag was no longer intact and was only partially legible.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.242 B
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.242(b):Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.: Box Division, 236 Hamilton Street, Hartford, Connecticut, Wood Shop: On, or about, February 5, 2021, a compressed air nozzle used for cleaning was measured to be 60 p.s.i., dead-ended.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.1200 H03 IV
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.1200(h)(3)(iv): The details of the hazard communication program developed by the employer, did not include an explanation of the labels received on shipped containers and the workplace labeling system used by their employer; the safety data sheet, including the order of information and how employee could obtain and use the appropriate hazard information: Company: On, or about, April 5, 2021, the employer had not provided training to employees regarding updated container labeling (pictograms) and the update format of Safety Data Sheets for hazardous materials used such as, but not limited to, adhesives, adhesive cleaner, propane and miscellaneous chemicals used for maintenance activities.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at CHAMPLIN-PACKRITE, INC
HARTFORD, CT—2008-02-07 00:00:00
CHAMPLIN-PACKRITE, INC.
HARTFORD, CT—2007-07-24 00:00:00
CHAMPLIN-PACKRITE, INC.
View CHAMPLIN-PACKRITE, INC's full OSHA safety record →
More inspections in this industry (NAICS 321920)
LAKELAND, FL—2026-07-16
ELIJAH WHOLESALE, LLC.
DECATUR, GA—2026-07-15
PALLETS ACQUISITION LLC
CLANTON, AL—2026-07-14
SPECWOOD PRODUCTS, INC.
FITCHBURG, MA—2026-07-10
KELLEY WOOD PRODUCTS, INC.
WASHINGTON COURT HOUSE, OH—2026-07-09
HALLIDAY LUMBER, LLC
More inspections in CT
ENFIELD, CT—2026-07-16
MOMS ENFIELD
DAYVILLE, CT—2026-07-16
HARBOR FREIGHT
NEW BRITAIN, CT—2026-07-14
JANANII, LLC
NEWINGTON, CT—2026-07-14
TRUSS MANUFACTURING INC
NORTH BRANFORD, CT—2026-07-14
NYK STATEWIDE MOLINA CONSTRUCTION LLC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345135842.