SOUTHINGTON, CT —
OSHA Inspection: NORTHEASTERN SHAPED WIRE, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of NORTHEASTERN SHAPED WIRE, INC. in 411 NORTH MAIN STREET, SOUTHINGTON, CT 06489 (NAICS 332618). OSHA activity number 345194955.
Where did this inspection happen?
- Establishment
- NORTHEASTERN SHAPED WIRE, INC.
- Site address
- 411 NORTH MAIN STREET
- City
- SOUTHINGTON
- State
- CT
- ZIP
- 06489
- Mailing
- 411 NORTH MAIN STREET, SOUTHINGTON, CT 06489
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332618
- Employees
- 24
- Ownership type
- A
Citations
23 citations on file for this inspection.
1910.22 A01
- Issued
- Abate by
- Penalty
- Initial $3121.00 · Current $1561.00 Reduced
General-duty citation text
29 CFR 1910.22(a)(1): The employer did not ensure that all places of employment, passageways, storerooms, service rooms, and walking-working surfaces are kept in a clean, orderly, and sanitary condition: Draw Area: On, or about, April 23, 2021, Condat Vicadil SPS 9G, a powered soap that was used as a lubricant to draw wire, had accumulated on overhead surfaces such as a storage loft, a bridge crane, wall ledges, trusses and the roof of an interior room. The dust was classified as combustible on the Safety Data Sheet provided by the manufacturer and was determined to be explosive when subject to Kst (explosibility) testing.
Recent events (3)
- — P (S) $1560.5
- — I (S) $1560.5
- — Z (S) $3121
1910.25 B01
- Issued
- Penalty
- Initial $2653.00 · Current $1327.00 Reduced
General-duty citation text
29 CFR 1910.25(b)(1): The employer did not ensure that handrails, stair rail systems, and guardrail systems are provided in accordance with 29 CFR 1910.28: Draw Area, Storage Loft: On, or about, April 23, 2021, railings provided on the access stairs and loft platform were not adequate in that: 1. A mid rail was not provided on either side of the access stairs. 2. The railings provided around the stairway opening in the loft floor were too low and the vertical space between the supporting members for the railings was too large.
Recent events (2)
- — I (S) $1326.5
- — Z (S) $2653
1910.132 D01
- Issued
- Abate by
- Penalty
- Initial $3121.00 · Current $1561.00 Reduced
General-duty citation text
29 CFR 1910.132(d)(1): The employer did not assess the workplace to determine if hazards are present, or are likely to be present, which necessitate the use of personal protective equipment (PPE): Tank Area: On, or about, March 14, 2021, the company had not conducted a hazard assessment to determine what personal protective equipment was required to be worn when working in the tank area. Tasks that exposed employees to potential chemical and/or thermal burns included adding chemicals to the tanks and lifting/lowering coils of wires in to or out of the tanks.
Recent events (3)
- — P (S) $1560.5
- — I (S) $1560.5
- — Z (S) $3121
1910.133 A01
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.133(a)(1): Protective eye and face equipment was not required where there was a reasonable probability of injury that could be prevented by such equipment: Tank Area: On, or about, March 14, 2021, employees who worked in the tank area did not wear adequate eye and face protection where hot, corrosive liquids presented a splash hazard.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.138 A
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.138(a):The employer did not select and require employee(s) to use appropriate hand protection when employees' hands were exposed to hazards such as those from skin absorption of harmful substances; severe cuts or lacerations; severe abrasion; punctures; chemical burns; thermal burns; and harmful temperature extremes: Tank Area: On, or about, March 14, 2021, adequate hand protection was not provided where coils of wire were processed in tanks that contained hot, corrosive liquids.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.147 C04 I
- Issued
- Abate by
- Penalty
- Initial $2340.00 · Current $1170.00 Reduced
General-duty citation text
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented, and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section: Company: On, or about, June 11, 2021, the company had not developed specific lockout procedures for multiple energy source machines such as, but not limited to, the Four Stand mill and heat treat furnaces.
Recent events (3)
- — P (S) $1170
- — I (S) $1170
- — Z (S) $2340
1910.333 B02 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.333(b)(2)(i): The employer did not maintain a written copy of the procedures outlined in paragraph (b)(2) of 29 CFR 1910.333 and did not make it available for inspection by the Assistant Secretary of Labor and his or her authorized representatives: Company: On, or about, June 11, 2021, the employer did not have either a copy of the procedures listed in the standard or a requirement in the lockout/tagout program that test equipment be used to verify absence of voltage before work was done on electrical circuits and equipment.
Recent events (3)
- — P (S) $0
- — I (S) $0
- — Z (S) $0
1910.212 A01
- Issued
- Abate by
- Penalty
- Initial $3901.00 · Current $1951.00 Reduced
General-duty citation text
29 CFR 1910.212(a)(1): Machine guarding was not provided to protect operator(s) and other employees from hazard(s) created by rotating parts, in-running nip points and the unused portion of a blade: A. Mill Area: On, or about, March 12, 2021, safeguarding was needed on the following machines: 1. Turks Head 1: Capstan. 2. Turks Head with double capstan: Double capstan and Turks head. 3. Four T Mill: Chain and sprocket drives at the tandem mill heads. 4. Four S Mill: Chain and sprocket drive at the mill head. B. Maintenance: On, or about, April 23, 2021, adjustable guards were not provided over the unused portions of the blade on the Johnson horizontal band saw.
Recent events (3)
- — P (S) $1950.5
- — I (S) $1950.5
- — Z (S) $3901
1910.219 I02
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.219(i)(2): Bolt(s), nuts, or setscrews used in shaft coupling(s) extended beyond the flange of the coupling and were not covered with safety sleeve(s): Mill Area: On, or about March 12, 2021, a guard was not provided over the rotating coupler for the pinion stand and transmission on the 6F mill.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 B02
- Issued
- Penalty
- Initial $1989.00 · Current $995.00 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: A. Mill Area: On, or about, March 12, 2021, a knockout box designed for permanent mounting was used in an extension cord assembly. B. Draw Area: On, or about, April 23, 2021, nonmetallic sheathed cable (romex) that was installed for power in and in the vicinity of the Die Room was not installed in accordance with the National Electric Code in that it was left exposed and not concealed behind drywall or other approved building material.
Recent events (2)
- — I (S) $994.5
- — Z (S) $1989
1910.334 A02 II
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.334(a)(2)(ii): There was a defect or evidence of damage that could have exposed an employee to injury and the defective or damaged item was not removed from service: Mill Area: On, or about, March 12, 2021, an extension cord used to energize butt welders was damaged and was wrapped with electrical tape.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 G01
- Issued
- Penalty
- Initial $3121.00 · Current $1561.00 Reduced
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: Tank Area: On, or about, March 12, 2021, a 250 gallon storage tank that contained mill oil was reduced access to electrical boxes and equipment located behind the evaporator tank.
Recent events (2)
- — I (S) $1560.5
- — Z (S) $3121
1910.303 G01 I A
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910: Draw Area: On, or about, April 23, 2021, a Hevi-Duty transformer and the waste oil tank were located in the working space for the Motor Block Panel DP4-1.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 G01 I C
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(g)(1)(i)(C): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of work space was not clear and did not extend from the grade, floor, or platform to the height required by paragraph (g)(1)(vi) of 29 CFR 1910.303. Other equipment associated with the electrical installation located above or below the electric equipment extended more than 153 mm (6 inches) beyond the front of the electric equipment: Draw Area: On, or about, April 23, 2021, a Hevi-Duty transformer was installed in the working space for Panel 6, an Eaton panelboard. The transformer projected 13 inches from the face of Panel 6.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 G01 II
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(g)(1)(ii):The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: AVD A. Draw Area: On, or about, April 23, 2021, a barrel was stored in front of two disconnect boxes located near the Morgan wire tip sizing machine. B. Maintenance Area: On, or about, April 23, 2021, a shop vac and metal panels were stored in front of a GE 277 volt lighting panel.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.332 B01
- Issued
- Abate by
- Penalty
- Initial $3121.00 · Current $1561.00 Reduced
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: Company: On, or about, April 23, 2021, maintenance personnel had not been trained regarding what work practices and protective equipment was required to protect them against electric shock, arc flash and arc blast hazards while performing live electrical work, live trouble-shooting and verifying whether or not electrical equipment was properly de-energized.
Recent events (3)
- — P (S) $1560.5
- — I (S) $1560.5
- — Z (S) $3121
1910.335 A01 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: Company: On, or about, April 23, 2021, personal protective equipment such as, but not limited to, voltage rated gloves, fire resistive clothing, face shields, balaclavas, hard hats and hearing protection were not provided to employees who performed live electrical work, including trouble-shooting, or who verified that electrical equipment was properly de-energized.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.37 B06
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color: Mill Area: On, or about, March 14, 2021, the exit sign provided for the exterior door near the tank area was worn and dirty.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.111 B07 IV
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.111(b)(7)(iv): Piping used on non-refrigerated systems did not meet the requirements of the American Society for Testing and Materials (ASTM) A-53-69 Grade B Electric Resistance Welded and Electric Flash Welded Pipe, which is incorporated by reference as specified in 29 CFR 1910.6, or equal. Such pipe was not at least schedule 80 when joints are threaded: Furnace Area: On, or about, March 12, 2021, a sections of the piping system that transferred anhydrous ammonia from the storage tank to the dissociator were not constructed with suitable materials of construction in that threaded Schedule 40 pipe was provided on two of the vertical risers.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.145 F05
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.145(f)(5): Danger tags were not used where an immediate hazard presented a threat of death or serious injury to employees: Tank Area: On, or about, March 12, 2021, a dip tank that contained a solution of Vicafil TS 649 at 160 degrees, F was not provided with warning signage or labeling to indicate the presence of a hot solution that could cause burns.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.215 B09
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.215(b)(9): Guard for abrasive wheel machine where the operator stands in front of the machine was not constructed so that the peripheral protecting member could be adjusted to the constantly decreasing diameter of the wheel: Maintenance Area: On, or about, April 23, 2021, a tongue guard was not provided on the left side of the Delta pedestal off-hand grinder.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.303 B07 IV
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(b)(7)(iv): Electric equipment had damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating: Draw Area, Morgan #2: On, or about, April 23, 2021, liquid tight conduit provided for the safety bar emergency stop circuit was pulled from its fitting, exposing the inner conductors.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.1200 F06 II
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.1200(f)(6)(ii): Except as provided in 29 CFR 1910.1200(f)(7) and 29 CFR 1910.1200(f)(8), the employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with the product identifier and words, pictures, symbols, or combination thereof, which provide at least general information regarding the hazards of the chemicals and which, in conjunction with the other information immediately available to employees under the hazard communication program, would provide employees with the specific information regarding the physical and health hazards of the hazardous chemical: In the following locations, containers were not properly labeled: A. Tank Area: On, or about, March 12, 2021, process tanks that contained solutions of Vicafil TS and Condaclean 168. B. Tank Area: On, or about, March 12, 2021, storage tank that contained Hydraulic H32 oil. C. Draw Area: On, or about, April 23, 2021, storage tank that contained waste mill oil.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at NORTHEASTERN SHAPED WIRE, INC.
Southington, CT—1982-03-02
NORTHEASTERN SHAPED WIRE INC
View NORTHEASTERN SHAPED WIRE, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 332618)
JACKSON, MI—2026-07-06
SALCO ENGINEERING & MANUFACTURING INC
MC KEES ROCKS, PA—2026-06-12
ACE WIRE SPRING & FORM CO., INC.
BUFFALO, NY—2026-06-03
PERMCLIP PRODUCTS CORP. 1130 MILITARY ROAD BUFFALO, NY 14217
AKRON, OH—2026-05-28
RICHARDS WHOLESALE FENCE CO., INC.
TULSA, OK—2026-05-20
MIKE ALEXANDER COMPANY
More inspections in CT
BRIDGEPORT, CT—2026-07-10
WRR, INC.
BERLIN, CT—2026-07-10
MMF CONSTRUCTION LLC
NAUGATUCK, CT—2026-07-08
WHITING-TURNER LCT2 JOINT VENTURE
SOMERS, CT—2026-07-08
F&G RECYCLING LLC
STAMFORD, CT—2026-07-07
FAIRFIELD AVENUE MAINTENANCE COMPANY, INC.
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345194955.