Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: FQE ELECTRIC LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of FQE ELECTRIC LLC in 3415 FARRAGUT ROAD, BROOKLYN, NY 11210 (NAICS 238210). OSHA activity number 345481881.

Watch FQE Electric LLC — free Get an email when a new federal OSHA severe-injury report for FQE Electric LLC is published. One employer, no account, unsubscribe in one click.
Establishment
FQE ELECTRIC LLC
Site address
3415 FARRAGUT ROAD
City
BROOKLYN
State
NY
ZIP
11210
Mailing
75 HUNTINGTON STREET, BROOKLYN, NY 11231
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Last modified
Data loaded
NAICS code
238210
Employees
5
Ownership type
A

4 citations on file for this inspection.

1926.20 B02

Serious Gravity 5 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $10256.00 · Current $6483.00 Reduced
29 CFR  1926.20(b)(2): The employer did not initiate and maintain a safety program which provides for frequent and regular inspections of jobsites, materials, and equipment to be made by a competent person(s)   Location: 3415 Farragut Rd, Brooklyn, NY.  On or about 7/28/2021,  a) The employer did not ensure that frequent and regular inspections of the jobsite, materials, and equipment were preformed by a competent person capable of identifying existing hazards.  Employees exposed to electrical hazards located at the stairway landings of each floor.
Recent events (3)
  • — F (S) $6483
  • — C (S) $10256
  • — Z (S) $10256

1926.405 A02 II C

Serious Gravity 5 1 instance 2 exposed
Issued
Penalty
Initial $10256.00 · Current $6483.00 Reduced
29 CFR  1926.405(a)(2)(ii)(C):Receptacles were connected to the same ungrounded conductor of multi-wire circuits supplying temporary lighting.  Location: 3415 Farragut Road, Brooklyn, NY; 6th & 7th floor stairway landings.  On or about 7/28/2021  a) Receptacles for uses other than temporary lighting were connected to the same ungrounded conductors of multi-wire circuits which supply temporary lighting.  Receptacles not connected to ground.
Recent events (3)
  • — F (S) $6483
  • — C (S) $10256
  • — Z (S) $10256

1926.405 A02 II F

Serious Gravity 5 1 instance 12 exposed
Issued
Abate by
Penalty
Initial $8204.00 · Current $5600.00 Reduced
29 CFR  1926.405(a)(2)(ii)(F):Temporary lights were suspended by their electric cords and were not designed for this means of suspension.  Location: 3415 Farragut Rd, Brooklyn, NY.  On or about 7/28/2021  a) The temporary lights at the stairway landings were suspended by their electric cords/wires and neither lights or cords/wires were designed for such suspension.
Recent events (3)
  • — F (S) $5600
  • — C (S) $8204
  • — Z (S) $8204

1926.403 I02 I

Serious Gravity 10 2 instances 12 exposed
Issued
Penalty
Initial $14357.00 · Current $11500.00 Reduced
29 CFR  1926.403(i)(2)(i):Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures, nor by any of the means listed in subparagraphs (A) through (D) of this paragraph.  Location: 3415 Farragut Road, Brooklyn, NY.  On or about 7/28/2021 live electrical contacts were not protected from accidental contact by any acceptable means:  a)  The splice connections of the temporary lights at the stairway landings of the 2nd, 3rd, 4th, 5th, 6th, and 7th floors were exposed to accidental contact.  b) The electrical connections for the terminals of the duplex outlets at the stairway landings of the 6th and 7th floors were exposed to accidental contact.  The employer (First Quality Electrical Corp) was previously cited for a violation of this occupational safety and health standard or its equivalent standard 1926.403(i)(2)(i), which was contained in OSHA inspection number 1288666, citation number 1, item number 1a, and was affirmed as a final order on 3/13/2018, with respect to a workplace located at 195 Sullivan Place, Brooklyn, NY.
Recent events (3)
  • — F (S) $11500
  • — C (R) $14357
  • — Z (R) $14357

View FQE ELECTRIC LLC's full OSHA safety record →