PLEASANT PRAIRIE, WI —
OSHA Inspection: OCENCO, INCORPORATED
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of OCENCO, INCORPORATED in 10225 82ND AVE, PLEASANT PRAIRIE, WI 53158 (NAICS 339113). OSHA activity number 345516223.
Where did this inspection happen?
- Establishment
- OCENCO, INCORPORATED
- Site address
- 10225 82ND AVE
- City
- PLEASANT PRAIRIE
- State
- WI
- ZIP
- 53158
- Mailing
- 10225 82ND AVE, PLEASANT PRAIRIE, WI 53158
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 339113
- Employees
- 70
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.147 C01
- Issued
- Abate by
- Penalty
- Initial $6164.00 · Current $6164.00
General-duty citation text
29 CFR 1910.147(c)(1): The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative: (a) On or about September 07, 2021, the employer had not developed and provided to employees who operate, work around, and /or conduct service of the Oxygen tank fill station a written hazardous energy control program and machine specific isolation procedures to insure the proper isolation of stored energy, and /or to prevent the unexpected energizing and startup of the equipment. Further, the employer did not supply the training needed to recognize the hazards associated with the equipment, and its isolation from the appropriate energy sources, or the responsibilities of authorized or affected employees to insure the proper isolation of stored energy and the recognition of the related energy hazards.
Recent events (2)
- — I (S) $6164
- — Z (S) $6164
1910.307 B
- Issued
- Abate by
- Penalty
- Initial $6164.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.307(b): Areas designated as hazardous (classified) locations under the Class and Zone system and areas designated under the Class and Division system established after August 13, 2007, were not properly documented: This documentation was not available to those authorized to design, install, inspect, maintain, or operate electric equipment at the location. (a) On or about September 7, 2021, in the Valve Room to include calibration stations and the Oxygen filling control panel, were not documented to identify the area as a hazardous (classified (Class 1 Division 2 location )) location according to the flammable material (compressed oxygen) being used to fill EBA 6.5 compressed oxygen cylinders from a 30,000 pound bulk supply oxygen tank.
Recent events (2)
- — I (S) $0
- — Z (S) $6164
1910.307 C02 I
- Issued
- Abate by
- Penalty
- Initial $10151.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.307(c)(2)(i): Equipment in hazardous (classified) location(s) was not approved for class of location or for the ignitable or combustible properties of the specific gas, vapor, dust, or fiber that was or could be present: (a) On or about September 07, 2021, at the Oxygen tank filling station in the Valve Room, a Class 1 Division 2 Location, the employer did not insure that electrical equipment was intrinsically safe and approved for use near a category 1 flammable gas supply. Specifically, but not limited to the electrical switch controlling the gas filling station, was not rated for use in a hazardous location.
Recent events (2)
- — I (S) $0
- — Z (S) $10151
More inspections in this industry (NAICS 339113)
MT JULIET, TN—2026-05-21
HOLLISTER INCORPORATED
CHICO, CA—2026-05-14
RESCUE 42, INC
NEWPORT, VT—2026-04-21
GALVION BALLISTICS LTD.
JACKSONVILLE, FL—2026-03-26
INVOTEC INTERNATIONAL INC
TAMPA, FL—2026-03-26
STEMRAD
More inspections in WI
MUSCODA, WI—2026-07-10
SCOT INDUSTRIES, INC
FRANKLIN, WI—2026-07-10
EDGE BROADBAND SOLUTIONS LLC
APPLETON, WI—2026-07-10
LAWRENCE UNIVERSITY OF WISCONSIN
KIMBERLY, WI—2026-07-10
ENRIQUE RESENDIC
SLINGER, WI—2026-07-10
DYLAN MATTHEW SHELLEY LLC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345516223.