Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: JEGS HIGH PERFORMANCE CENTERS

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of JEGS HIGH PERFORMANCE CENTERS in 751 EAST 11TH AVENUE, COLUMBUS, OH 43211 (NAICS 441310). OSHA activity number 345753859.

Watch Jegs High Performance Centers — free Get an email when a new federal OSHA severe-injury report for Jegs High Performance Centers is published. One employer, no account, unsubscribe in one click.
Site address
751 EAST 11TH AVENUE
City
COLUMBUS
State
OH
ZIP
43211
Mailing
751 EAST 11TH AVENUE, COLUMBUS, OH 43211
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
441310
Employees
250
Ownership type
A

7 citations on file for this inspection.

1910.37 A03

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $8718.00 · Current $3923.00 Reduced
29 CFR  1910.37(a)(3):Exit route(s) were not kept free and unobstructed:  a) Jegs High Performance Centers located at 751 East 11th Ave, Columbus, OH 43211:  On and preceding January 31, 2022, the employer did not ensure that the exit through the back storage room leading outside of the lower shop was unobstructed thereby exposing employees to fire hazards.
Recent events (2)
  • — I (S) $3923.1
  • — Z (S) $8718

1910.37 B02

Serious Gravity 1 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":   a) Jegs High Performance Centers located at 751 East 11th Ave, Columbus, OH 43211:  On and preceding January 31, 2022, the employer did not ensure that the exit through the back storage room leading outside of the lower shop had a sign reading "exit" thereby exposing employees to fire hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 B01

Serious Gravity 5 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $6974.00 · Current $3138.00 Reduced
29 CFR  1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees:   a) Jegs High Performance Centers located at 751 East 11th Ave, Columbus, OH 43211:  On and preceding January 31, 2022, an electrical circuit breaker box in the north west corner of the lower shop had broken circuit breakers with metal parts exposed and unused openings not covered thereby exposing employees to fire and electrical shock hazards.
Recent events (2)
  • — I (S) $3138.3
  • — Z (S) $6974

1910.303 F02

Serious Gravity 1 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:    a) Jegs High Performance Centers located at 751 East 11th Ave, Columbus, OH 43211:  On and preceding January 31, 2022, an in service electrical circuit breaker box in the north west corner of the lower shop was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G01 II

Serious Gravity 1 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:   a) Jegs High Performance Centers located at 751 East 11th Ave, Columbus, OH 43211:  On and preceding January 31, 2022, an electrical circuit breaker box in the north west corner of the lower shop did not have sufficient access and working space around it to permit ready and safe operation of the equipment. Several stacks of tires were blocking the electrical panel thereby exposing employees to electrical shock and fire hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV B

Serious Gravity 5 1 instance 3 exposed
Issued
Penalty
Initial $6974.00 · Current $3163.00 Reduced
29 CFR  1910.305(g)(1)(iv)(B): Flexible cords and/or cables were run through holes in walls, ceilings, or floors:   a) Jegs High Performance Centers located at 751 East 11th Ave, Columbus, OH 43211:  On and preceding January 31, 2022, a flexible cord powering a Hoffman 2200 wheel/tire balancing machine was run through the wall and plugged into an outlet on the opposite side of the wall thereby exposing employees to fire and electrical shock hazards.
Recent events (2)
  • — I (S) $3163.3
  • — Z (S) $6974

1910.334 A02 I

Serious Gravity 5 1 instance 3 exposed
Issued
Penalty
Initial $6974.00 · Current $3163.00 Reduced
29 CFR  1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket):  a) Jegs High Performance Centers located at 751 East 11th Ave, Columbus, OH 43211:  On and preceding January 31, 2022, a flexible extension cord and power cord for a large fan was not visually inspected for defects prior to use.  the extension cord and fan cord had several areas with damaged insulation and other damage thereby exposing employees to electrical shock hazards.  b) Jegs High Performance Centers located at 751 East 11th Ave, Columbus, OH 43211:  On and preceding January 31, 2022, a power cord for a  Skil 6265 drill was not visually inspected for defects prior to use.  The outer jacket was pulled out from the bottom of the drill handle thereby exposing employees to electrical shock hazards.
Recent events (2)
  • — I (S) $3163.3
  • — Z (S) $6974

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345753859.