TAUNTON, MA —
OSHA Inspection: WATERFRONT COLD STORE, LLC
Referral inspection · Health discipline
At a glance
On , OSHA opened a referral health inspection of WATERFRONT COLD STORE, LLC in 81 INGELL STREET, TAUNTON, MA 02780 (NAICS 493120). OSHA activity number 345797062.
Where did this inspection happen?
- Establishment
- WATERFRONT COLD STORE, LLC
- Site address
- 81 INGELL STREET
- City
- TAUNTON
- State
- MA
- ZIP
- 02780
- Mailing
- 81 INGELL STREET, TAUNTON, MA 02780
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 493120
- Employees
- 15
- Ownership type
- A
Citations
2 citations on file for this inspection.
5(a)(1)
- Issued
- Penalty
- Initial $10151.00 · Current $5076.00 Reduced
General-duty citation text
29 CFR OSH ACT of 1970 Section (5)(a)(1):Section 5(a)(1) of the Occupational Safety and Health Act: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to a potential catastrophic release of ammonia gas or liquid resulting in irritation, pulmonary edema, skin burns and frostbite from the deficient design and lack of maintenance of the ammonia refrigeration facility and equipment: (a) Main King Valve - The hand operated Main King valve located above the receiver was not accessible for operation from the floor exposing employees to the risk of exposure to ammonia gas or liquid.
Recent events (2)
- — I (S) $5075.5
- — Z (S) $10151
1910.38 D
- Issued
- Penalty
- Initial $10151.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.38(d):The employer did not have and maintain an employee alarm system with a distinctive signal for each purpose that complied with the requirements in � 1910.165. Facility: The alarm system for reporting the release of anhydrous ammonia was the same system for a fire. They were not separate and distinct from one another.
Recent events (2)
- — I (S) $0
- — Z (S) $10151
More inspections in this industry (NAICS 493120)
NEWPORT, MI—2026-07-15
MEIJER DISTRIBUTION CENTER FACILITY
BIGLERVILLE, PA—2026-07-10
BREAM BEAR ORCHARDS
BIGLERVILLE, PA—2026-07-10
BREAM BEAR ORCHARDS
PLANT CITY, FL—2026-07-01
AMERICOLD LOGISTICS, LLC.
KELLER, TX—2026-07-01
KROGER TEXAS L.P.
More inspections in MA
BELLINGHAM, MA—2026-07-16
BELLINGHAM DEPARTMENT OF PUBLIC WORKS
PLYMOUTH, MA—2026-07-15
TECH-ETCH, INC.
WESTFIELD, MA—2026-07-15
BOISE CASCADE BUILDING MATERIALS DISTRIBUTION, L.L.C.
QUINCY, MA—2026-07-15
UNITEDWOR VM CONTRACTOR CORP
FALL RIVER, MA—2026-07-15
CRESCO LABS, INC.
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345797062.