OSHA Inspection: ENERGY SCIENCES, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of ENERGY SCIENCES, INC. in 42 INDUSTRIAL WAY, WILMINGTON, MA 01887 (NAICS 334419). OSHA activity number 345868137.

Watch Energy Sciences, INC. — free Get an email when a new federal OSHA severe-injury report for Energy Sciences, INC. is published. One employer, no account, unsubscribe in one click.
Site address
42 INDUSTRIAL WAY
City
WILMINGTON
State
MA
ZIP
01887
Mailing
42 INDUSTRIAL WAY, WILMINGTON, MA 01887
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
334419
Employees
45
Ownership type
A

3 citations on file for this inspection.

1910.37 A03

Deleted Serious Gravity 5 1 instance 1 exposed
Issued
Penalty
Initial $5801.00 · Current $0.00 Reduced
29 CFR  1910.37(a)(3): Exit route(s) were not kept free and unobstructed:  (a) Location - Production Area / Bay 3 testing Area: On or about 03/31/2022, employee working at test bay 3 had an obstructed exit path.
Recent events (2)
  • — I (S) $0
  • — Z (S) $5801

1910.137 C02 VIII

Serious Gravity 5 1 instance 1 exposed
Issued
Penalty
Initial $7252.00 · Current $3000.00 Reduced
29 CFR  1910.137(c)(2)(viii): Electrical protective equipment was not subjected to periodic electrical tests. Test voltages and/or the maximum intervals between tests were not conducted in accordance with Table I-4 and Table I-5.   (a) Location - Production Area / Bay 3 testing Area: On or about 03/31/2022, the rubber insulating gloves were not subjected to periodic electrical tests in accordance with Table I-4 and I-5.
Recent events (2)
  • — I (S) $3000
  • — Z (S) $7252

1910.303 G02 I

Serious Gravity 10 1 instance 1 exposed
Issued
Penalty
Initial $10151.00 · Current $2000.00 Reduced
1910.303(g)(2)(i): Live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures:  (a) Location -Production Area / Bay 3 testing Area: On or about 03/31/2022,  live electrical was not guarded from accidental contact where the cover on an energized electrical panel was not effectively closed.
Recent events (2)
  • — I (S) $2000
  • — Z (S) $10151

View ENERGY SCIENCES, INC.'s full OSHA safety record →