NAMPA, ID —
OSHA Inspection: CHRISTENSEN INCORPORATED
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of CHRISTENSEN INCORPORATED in 17661 CAN ADA ROAD, NAMPA, ID 83687 (NAICS 454310). OSHA activity number 346284102.
Where did this inspection happen?
- Establishment
- CHRISTENSEN INCORPORATED
- Site address
- 17661 CAN ADA ROAD
- City
- NAMPA
- State
- ID
- ZIP
- 83687
- Mailing
- P.O BOX 5159, TWIN FALLS, ID 83303
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 454310
- Employees
- 120
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.28 B01 I
- Issued
- Abate by
- Penalty
- Initial $8929.00 · Current $5000.00 Reduced
General-duty citation text
29 CFR 1910.28(b)(1)(i): The employer did not ensure that each employee on a walking-working surface with an unprotected side or edge that was 4 feet or more above a lower level was protected from falling by one or more of the systems described in 29 CFR 1910.28(b)(1)(i): a) On October 13, 2022 and at times prior employees were exposed to fall hazards up to 8.5 feet to the ground below while standing on the top of a fuel delivery "tank wagon" truck and a fuel storage trailer while transferring fuel from the storage trailer into the delivery truck. Note) Certification of corrective action is required for this item.
Recent events (2)
- — I (S) $5000
- — Z (S) $8929
1910.106 F03 IV A
- Issued
- Abate by
- Penalty
- Initial $15625.00 · Current $10000.00 Reduced
General-duty citation text
29 CFR 1910.106(f)(3)(iv)(a): Bonding facilities for protection against static sparks during the loading of tank vehicles through open domes were not provided: a) On October 13, 2022, employees transloaded diesel fuel between a storage trailer and two delivery trucks without grounding or bonding any of the vehicles together. A mixture of red and green diesel fuel was pumped out of the top of a 5000- gallon storage trailer using the pump of a delivery truck into the rear, open dome of another delivery truck. Note) Abatement certification and documentation are required for this item.
Recent events (2)
- — I (S) $10000
- — Z (S) $15625
1910.106 F03 IV C
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.106(f)(3)(iv)(c): Bonding connections were not made to the vehicle or tank before dome covers are raised: a) October 13, 2022, bonding connection hardware was not available for employees to use prior to opening the rear dome on a fuel delivery truck. Employees transloaded a mixture of red and green diesel into the top rear dome of a 3600- gallon capacity fuel truck that was not equipped with bonding connection hardware. Note) Certification and documentation of corrective actions are required for this item.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.106 F03 IV E
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.106(f)(3)(iv)(e): Filling through open domes into the tanks of tank vehicles or tank cars, that contain vapor-air mixtures within the flammable range or where the liquid being filled can form such a mixture, was not done by means of a downspout which extends near the bottom of the tank: a) On October 13, 2022 the delivery hose used by an employee to top load diesel fuel into the rear dome of a 3600 gallon capacity delivery truck tank did not extend to the bottom of the tank, creating a potential flammable vapor atmosphere. Note) Certification and documentation of corrective actions are required for this item.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.132 D01
- Issued
- Abate by
- Penalty
- Initial $8929.00 · Current $5000.00 Reduced
General-duty citation text
29 CFR 1910.132(d)(1): The employer did not assess the workplace to determine if hazards were present, or were likely to be present, which necessitated the use of personal protective equipment: a) On August 13, 2022 and times prior: an assessment of the potential hazards associated with the delivery truck drivers tasks was not done to determine if or when fire rated clothing (PPE) was necessary. Note) Certification of corrective action is required for this item.
Recent events (2)
- — I (S) $5000
- — Z (S) $8929
More inspections in this industry (NAICS 454310)
SALT LAKE CITY, UT—2026-07-16
FUEL UP LLC
PLANT CITY, FL—2026-05-14
PROPANE NINJA
RIPPLEMEAD, VA—2026-04-30
RED FLAME OIL & PROPANE, INC.
FULTON, NY—2026-04-23
JOHNSTON'S PROPANE SERVICE
QUINCY, CA—2026-03-19
HUNT & SONS, LLC
More inspections in ID
BOISE, ID—2026-07-16
RAYMOND MANAGEMENT COMPANY