KANSAS CITY, MO —
OSHA Inspection: FOCUS PARTNERS LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of FOCUS PARTNERS LLC in 6050 MANCHESTER TRAFFICWAY TERRACE, KANSAS CITY, MO 64130 (NAICS 111419). OSHA activity number 346331705.
Where did this inspection happen?
- Establishment
- FOCUS PARTNERS LLC
- Site address
- 6050 MANCHESTER TRAFFICWAY TERRACE
- City
- KANSAS CITY
- State
- MO
- ZIP
- 64130
- Mailing
- 6050 MANCHESTER TRAFFICWAY TERRACE, KANSAS CITY, MO 64150
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 111419
- Employees
- 60
- Ownership type
- A
Citations
9 citations on file for this inspection.
1910.178 A06
- Issued
- Abate by
- Penalty
- Initial $6250.00 · Current $3750.00 Reduced
General-duty citation text
29 CFR 1910.178(a)(6): The employer did not ensure that all nameplates and markings were maintained in a legible condition: At the worksite located at 6050 Manchester Trafficway, Kansas City, Missouri: Employees were exposed to struck by hazards when powered industrial trucks were in operation as the levers and knobs on the powered industrial trucks were not identifiable for the operator.
Recent events (2)
- — I (S) $3750
- — Z (S) $6250
1910.178 L02 II
- Issued
- Abate by
- Penalty
- Initial $6250.00 · Current $3750.00 Reduced
General-duty citation text
29 CFR 1910.178(l)(2)(ii): The employer did not ensure that each operator had successfully completed the training consisting of a combination of formal instruction (e.g., lecture, discussion, interactive computer learning, video tape, written material), practical training (demonstrations performed by the trainer and practical exercises performed by the trainee), and evaluation of the operator's performance in the workplace: At the worksite located at 6050 Manchester Trafficway, Kansas City, Missouri: Employees were exposed to struck by hazards. The employer did not ensure powered industrial truck operators had successfully completed training on operating powered industrial trucks.
Recent events (2)
- — I (S) $3750
- — Z (S) $6250
1910.178 L06
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.178(l)(6): The employer did not certify that each operator has been trained and evaluated as required by this paragraph (l): At the worksite located at 6050 Manchester Trafficway, Kansas City, Missouri: Employees were exposed to struck by hazards. Employees were not certified by the employer to operate powered industrial trucks prior to operating.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 B07 I
- Issued
- Abate by
- Penalty
- Initial $10938.00 · Current $6563.00 Reduced
General-duty citation text
29 CFR 1910.303(b)(7)(i): Unused opening in electrical cabinets were not effectively closed provide substantially equivalent protection to the equipment: At the worksite located at 6050 Manchester Trafficway, Kansas City, Missouri: Employees were exposed to serious shock, burn and or electrocution injuries in that the electrical equipment operating at 50 volts or more was not guarded or enclosed to protect from accidental contact in cultivation room 2.
Recent events (2)
- — I (S) $6562.8
- — Z (S) $10938
1910.303 G02 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets or other forms of approved enclosures, or other means listed under this provision: At the worksite located at 6050 Manchester Trafficway, Kansas City, Missouri: Employees were exposed to serious shock, burn and or electrocution injuries in that the electrical equipment operating at 50 volts or more was not enclosed to protect from accidental contact in cultivation room 2 due to the door to the cabinet being left open.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 G01 I B
- Issued
- Abate by
- Penalty
- Initial $10938.00 · Current $6563.00 Reduced
General-duty citation text
29 CFR 1910.303(g)(1)(i)(B): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the working space did not permit at least a 90-degree opening of equipment doors or hinged panels: At the worksite located at 6050 Manchester Trafficway, Kansas City, Missouri: Employees were exposed to serious shock, burn and or electrocution injuries when accessing electrical breaker panels. 1. The electrical breaker panels were blocked by tables which did not allow the doors to open at least 90 degrees in room 3. 2. The electrical breaker panels were blocked by equipment and chemicals in the chemical storage area.
Recent events (2)
- — I (S) $6562.8
- — Z (S) $10938
1910.305 G01 IV A
- Issued
- Abate by
- Penalty
- Initial $10938.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: At the worksite located at 6050 Manchester Trafficway, Kansas City, Missouri: Employees were exposed to electrical shock hazards. 1. Extension cords were used in lieu of fixed wiring for the sump pumps in grow room 2. 2. Extension cords were used in lieu of fixed wiring for a scale in grow room 4. 3. Extension cords were used in lieu of fixed wiring for employee time clocks outside of packaging.
Recent events (2)
- — I (S) $0
- — Z (S) $10938
1910.305 G01 IV D
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords were attached to building surfaces: Employees were exposed to electrical shock hazards. Extension cords used to power a sump pump were affixed to structures within the building. 1. Extension cords used to power the sump pump in grow room 2 were affixed to structures in the building. 2. Relocatable power taps used to power a scale in grow room 4 were affixed to structures in the building. 3. Relocatable power taps used to power employee time clocks outside the packaging room were affixed to structures in the building.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G02 III
- Issued
- Abate by
- Penalty
- Initial $9376.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief is provided that will prevent pull from being directly transmitted to joints and/or terminal screws. At the worksite located at 6050 Manchester Trafficway, Kansas City, Missouri: Employees were exposed to electrical shock hazards when charging the floor cleaner. The cord that connects the floor cleaner to the charger has been pulled out of the coupling providing no strain relief.
Recent events (2)
- — I (S) $0
- — Z (S) $9376
More inspections at FOCUS PARTNERS LLC
KANSAS CITY, MO—2022-11-07 00:00:00
FOCUS PARTNERS LLC
View FOCUS PARTNERS LLC's full OSHA safety record →
More inspections in this industry (NAICS 111419)
VASSAR, MI—2026-07-09
ACE CANNABIS, LLC
VASSAR, MI—2026-07-09
ACE CANNABIS, LLC
AUBURN, WA—2026-07-07
WA317991892 - GOLD MOUNTAIN CANNABIS INC
SPRINGDALE, AR—2026-07-06
80 ACRES FARMS
SMYRNA, TN—2026-07-06
TAYLOR FARMS TENNESSEE INC.
More inspections in MO
KANSAS CITY, MO—2026-07-09
NIAGARA BOTTLING
MONETT, MO—2026-07-09
MONETT METALS INC.
PARKVILLE, MO—2026-07-08
SKY-TECH ROOFING, LLC.
SPRINGFIELD, MO—2026-07-07
D & C CONSTRUCTION, LLC.
JOPLIN, MO—2026-07-07
SERVICE RECYCLING - NORTH PLANT
Source