SPRINGDALE, AR —
OSHA Inspection: JAMES + JAMES
Unprogrammed Other inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Other safety inspection of JAMES + JAMES in 1609 N OLD MISSOURI RD, SPRINGDALE, AR 72764 (NAICS 238350). OSHA activity number 346384100.
Where did this inspection happen?
- Establishment
- JAMES + JAMES
- Site address
- 1609 N OLD MISSOURI RD
- City
- SPRINGDALE
- State
- AR
- ZIP
- 72764
- Mailing
- 1609 N OLD MISSOURI RD, SPRINGDALE, AR 72764
What kind of inspection was it?
- Inspection type
- Unprogrammed Other (I)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238350
- Employees
- 104
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.22 A01
- Issued
- Abate by
- Penalty
- Initial $6026.00 · Current $3013.00 Reduced
General-duty citation text
29 CFR 1910.22(a)(1): The employer did not ensure that all places of employment, passageways, storerooms, service rooms, and walking-working surfaces are kept in a clean, orderly, and sanitary condition: On or about December 9, 2022 , in the Builder Shop area, where employees were performing activities related to carpentry: (a) extension cords were coiled on the floor exposing employees to trip and fall hazards; (b) wood dust was allowed to accumulate on the floors exposing employees to slip and fall hazards. (c) wood dust was allowed to accumulate on the floors, walls, electrical equipment, and other surfaces exposing employees to fire and explosion hazards.
Recent events (2)
- — I (S) $3013
- — Z (S) $6026
1910.176 B
- Issued
- Abate by
- Penalty
- Initial $6026.00 · Current $3013.00 Reduced
General-duty citation text
29 CFR 1910.176(b): Storage of material created a hazard: On or about December 9, 2022, in the Builder Shop area, employees were performing activities related to carpentry were exposed to struck-by hazards when items such as, but not limited to, fan, plastic boxes, trays full of chargers, rags were stored on top of a flammable cabinet.
Recent events (2)
- — I (S) $3013
- — Z (S) $6026
1910.307 C02 I
- Issued
- Abate by
- Penalty
- Initial $14063.00 · Current $7032.00 Reduced
General-duty citation text
29 CFR 1910.307(c)(2)(i): Equipment in hazardous (classified) location(s) was not approved for the ignitable or combustible properties of the specific gas, vapor, dust, or fiber that was or could be present: On or about December 9, 2022, in the Builder Shop, employees using electrical equipment not designed for installation in a Class II, Division 1 area plugged into receptacles such as, but not limited to: (a) Box G-12 with two receptacles on a fixed installation on top of a portable fire extinguisher, was providing power to a phone charger. (b) flexible cord providing power to metal outlet box G-3 with two receptacles, mounted to the wall adjacent to "Do Not Forklift" sign , was providing power to extension cords. (c) flexible cord providing power to metal outlet box above box G-11, next to column, with two receptacles, was providing power to extension cords and sanders. (d) extension cords were providing power to chargers plugs at outlet box G-11, next to with two receptacles. (e) flexible cord providing power to metal outlet box B1-5, with two receptacles , next to column . (f) GFI receptacle mounted to column adjacent to boxes G-11, B1-5, and the one on top of G-11. (g) flexible cord providing power to metal outlet box G-1 with two receptacles, mounted to the wall adjacent to "Do Not Forklift" sign , was providing power to extension cords.
Recent events (2)
- — I (S) $7031.5
- — Z (S) $14063
1910.303 B02
- Issued
- Abate by
- Penalty
- Initial $14063.00 · Current $7032.00 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: On or about December 9, 2022 , in the Builder Shop, employees were plugging and unplugging various tools and equipment into metal junction boxes with prepunched knockouts installed as pendants. Instances include, but are not limited to the following: a) outlet box B1-5 providing power to equipment such as, but not limited to battery chargers b)outlet box G-11 providing power to equipment such as, but not limited to cell phone charges and sanders c) outlet box B1-1 providing power to equipment such as, but not limited to a fan d) outlet box B1-11, fan and sanders plug to these boxes e) outlet box providing power to dust collector located near Grizzly Industrial G0941 table saw f) outlet box G-3 providing power to equipment such as, but not limited to a Bosh Sander by "Do not Forklift" sign g) two metal outlet boxes with prepunched knockouts adjacent to Tank Room Pump disconnect used as pendants to provide power to sanders and extension cords
Recent events (2)
- — I (S) $7031.5
- — Z (S) $14063
1910.305 G01 IV A
- Issued
- Abate by
- Penalty
- Initial $14063.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: On or about December 9, 2022 , in the Builder Shop, employees were using flexible cords to supply power to equipment including, but not limited to the following: a) an extension cord was providing power to the Table saw Grizzly Industrial G0941, Ser. 2021252. b) an extension cord was providing power to a Bosh Sander plugged into to G-3 box by "Do not Forklift" sign. c) extension cords was providing power to a fan and Bosh sanders by B-1, B-11 boxes, near paint cabinet and fire extinguisher. d) extension cords were providing power to chargers plugs at G-11 and the box on top of box G-11. e) flexible cord receiving power from a junction box mounted to the ceiling joists provided power to a DeWalt miter saw f) extension cord providing power to battery chargers on lower shelf of cart g) flexible cord providing power to metal outlet box G-1 mounted to the wall adjacent to "Do Not Forklift" sign h) flexible cord providing power to metal outlet box G-3 mounted to the wall adjacent to "Do Not Forklift" sign i) flexible cord was providing power to pendant box where a dust collector was plugged by table saw Grizzly Industrial G0941. j) flexible cord providing power to metal outlet box B1-5 , next to column .
Recent events (2)
- — I (S) $0
- — Z (S) $14063
More inspections in this industry (NAICS 238350)
JAMESTOWN, RI—2026-07-10
A K I CARPENTRY INC
BROOKLYN, NY—2026-07-08
PALACE RESIDENTIAL CORP.
BROOKLYN, NY—2026-07-07
PRO PROPERTY RENO INC.
KENTON, OH—2026-07-01
SUNLIGHT WINDOWS AND EXTERIORS, LLC
ROBBINSVILLE, NJ—2026-06-30
FAST WRAP WINDOWS & DOORS, INC.
More inspections in AR
LITTLE ROCK, AR—2026-07-09
NABHOLZ CONSTRUCTION CORPORATION
FORT SMITH, AR—2026-07-08
HIREQUEST INC.
VAN BUREN, AR—2026-07-08
BEKAERT CORPORATION
SEARCY, AR—2026-07-06
CAL-MAINE FOODS, INC
ARKADELPHIA, AR—2026-07-06
JUSTIN KIRKSEY LOGGING, INC.
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346384100.