Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: BURGARD PLUMBING & HEATING INC.

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of BURGARD PLUMBING & HEATING INC. in 1540A GAUTREAUX STREET, HOUMA, LA 70360 (NAICS 238220). OSHA activity number 346427214.

Watch Burgard Plumbing & Heating INC. — free Get an email when a new federal OSHA severe-injury report for Burgard Plumbing & Heating INC. is published. One employer, no account, unsubscribe in one click.
Site address
1540A GAUTREAUX STREET
City
HOUMA
State
LA
ZIP
70360
Mailing
1540 A GAUTREAUX STREET, HOUMA, LA 70360
Inspection type
Federal Agency (M)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Last modified
Data loaded
NAICS code
238220
Employees
5
Ownership type
A

11 citations on file for this inspection.

1910.106 D05 VI F

Serious Gravity 1 1 instance 9 exposed
Issued
Abate by
Penalty
Initial $2009.00 · Current $1509.00 Reduced
29 CFR  1910.106(d)(5)(vi)(f): The employer did not ensure that aisleways of at least three feet were maintained to provide access to doors, windows, and standpipes.  On or about January 05, 2023, in the shipping container used to store flammable materials, the aisle was not maintained at least three (3) feet wide.
Recent events (2)
  • — I (S) $1509
  • — Z (S) $2009

1910.106 D07 I

Serious Gravity 10 1 instance 9 exposed
Issued
Abate by
Penalty
Initial $4688.00 · Current $2688.00 Reduced
29 CFR 1910.106(d)(7)(i): Suitable fire control devices, such as small hose or portable fire extinguishers, were not available at locations where flammable or combustible liquids were stored.  On or about January 05, 2023, in or near the shipping container, there was no fire extinguishers for employees to utilize in an area containing flammable hazards.
Recent events (2)
  • — I (S) $2688
  • — Z (S) $4688

1910.106 D07 III

Serious Gravity 10 1 instance 9 exposed
Issued
Abate by
Penalty
Initial $4688.00 · Current $3000.00 Reduced
29 CFR  1910.106(d)(7)(iii): Open flames and smoking, including ignitable sources, were permitted in flammable liquid storage areas.  On or about January 05, 2023, in the shipping container, employees were utilizing a mechanical pump used for siphoning gasoline that had uninsulated wiring connected to a battery.
Recent events (2)
  • — I (S) $3000
  • — Z (S) $4688

1910.106 E06 I

Serious Gravity 10 1 instance 9 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.106(e)(6)(i): Adequate precautions were not taken to prevent the ignition of flammable vapors from sources such as open flames; lightning; smoking; cutting and welding; hot surfaces; frictional heat; static, electrical, and mechanical sparks; spontaneous ignition, including heat-producing chemical reactions; and radiant heat:  On or about January 05, 2023, in the shipping container, employees were utilizing a mechanical pump used for siphoning gasoline that had uninsulated wiring connected to a battery .
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.106 E06 II

Serious Gravity 10 1 instance 9 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.106(e)(6)(ii):Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), were dispensed into containers without the nozzle and container being electrically interconnected.  On or about January 05, 2023, in the shipping container, employees were utilizing a mechanical pump used for siphoning gasoline that was not interconnected to the container.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.106 E02 III

Serious Gravity 1 1 instance 9 exposed
Issued
Abate by
Penalty
Initial $2009.00 · Current $1000.00 Reduced
29 CFR  1910.106(e)(2)(iii): Drainage or other means to control spills was not provided in areas where flammable or combustible liquids were transferred from one tank or container to another container:  On or about January 05, 2023, in the shipping container, the employer did not adequately install drainage for the tote gasoline containers stored.
Recent events (2)
  • — I (S) $1000
  • — Z (S) $2009

1910.106 E03 V A

Serious Gravity 10 1 instance 9 exposed
Issued
Abate by
Penalty
Initial $4688.00 · Current $4688.00
29 CFR  1910.106(e)(3)(v)(a): An area as defined in paragraph (e)(3)(i) of this section using Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), was not ventilated be accomplished by natural or mechanical ventilation with discharge or exhaust to a safe location outside of the building:  On or about January 05, 2023, in the yard area; the employer installed an exhaust fan for ventilation inside a shipping container (used as a fuel storage room) that did not provide adequate air/ventilation.
Recent events (2)
  • — I (S) $4688
  • — Z (S) $4688

1910.1200 E01

Serious Gravity 10 1 instance 9 exposed
Issued
Abate by
Penalty
Initial $4688.00 · Current $4115.00 Reduced
29 CFR  1910.1200(e)(1): The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f), (g), and (h) will be met:  On or about January 05, 2023, The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program for chemicals such as, but not limited to gasoline and diesel fuels that were stored onsite.
Recent events (2)
  • — I (S) $4115
  • — Z (S) $4688

1910.1200 H01

Serious Gravity 10 1 instance 9 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.1200(h)(1): Employees were not provided effective information and training on hazardous chemicals in their work area at the time of their initial assignment and whenever a new hazard that the employees had not been previously trained about was introduced into their work area:  On or about January 05, 2023, the employer did not provide effective employee training for chemicals such as, but not limited to, gasoline and diesel fuels used in fueling operations onsite.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.1200 G08

Serious Gravity 10 1 instance 9 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.1200(g)(8):  The employer did not maintain in the workplace copies of the required safety data sheets for each hazardous chemical, and did not ensure that they were readily accessible during each work  shift to employees when they were in their work area(s).  On or about January 05, 2023, the employer did not maintain in the workplace copies of the required safety data sheets for the gasoline and diesel fuels stored in the tote containers.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.132 D02

Deleted Other-than-serious 1 instance 9 exposed
Issued
Abate by
Penalty
Initial $376.00 · Current $0.00 Reduced
29 CFR  1910.132(d)(2): The employer did not verify that the required workplace hazard assessment had been performed through a written certification that identified the workplace evaluated;  the person certifying that the evaluation has been performed;  the date(s) of the hazard assessment;  and which identifies the document as a certification of hazard assessment:  On or about January 05, 2023, the employer did not verify by written certification that a hazard assessment had been conducted for the personal protective equipment that was required for gasoline fueling operations onsite.
Recent events (2)
  • — I (O) $0
  • — Z (O) $376

OXYCHEM