Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: FOND MEMORIES PET CEMETERY & CREMATORIUM - PET REST CEMETERY

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of FOND MEMORIES PET CEMETERY & CREMATORIUM - PET REST CEMETERY in 6800 SOUTH STATE HIGHWAY 78, SACHSE, TX 75048 (NAICS 812220). OSHA activity number 346427255.

Watch Fond Memories PET Cemetery & Crematorium - PET Rest Cemetery — free Get an email when a new federal OSHA severe-injury report for Fond Memories PET Cemetery & Crematorium - PET Rest Cemetery is published. One employer, no account, unsubscribe in one click.
Site address
6800 SOUTH STATE HIGHWAY 78
City
SACHSE
State
TX
ZIP
75048
Mailing
6800 SOUTH STATE HIGHWAY 78, SACHSE, TX 75048
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
812220
Employees
8
Ownership type
A

7 citations on file for this inspection.

1910.22 A01

Serious Gravity 10 5 instances 6 exposed
Issued
Abate by
Penalty
Initial $15625.00 · Current $11719.00 Reduced
29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms, service rooms, and walking-working surfaces were not kept in a clean, orderly, and sanitary condition:  a) On or about January 10, 2023, and at times prior thereto; in the Crematory area, where electrical extension cords on floor, running across passageways, exposing employees to trip and fall hazards:  a.	Between the Cyclopentane freezers #006 and #005. b.	At the scale "Rubbermaid Commercial Products" near to the garage door. c.	Between the Evaporative Cooler system and Cremation System 1 area. d.	At the clay pawprints/oven area. e.	At the passageway to the freezers on the sidewall area.
Recent events (2)
  • — I (S) $11718.75
  • — Z (S) $15625

1910.303 B02

Serious Gravity 10 2 instances 6 exposed
Issued
Abate by
Penalty
Initial $15625.00 · Current $11719.00 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  a) The employer did not ensure electrical equipment is used and installed in accordance with the listing or labeling instructions.  This violation occurred on or about January 10, 2023, and at times prior thereto; in the crematory area, relocatable power tap/power strips were being used to power Freezers, fans, and other equipment:  a.	White relocatable power taps/power strip to power freezers. b.	Black relocatable power tap/power strip to power floor fan and other extension cords.
Recent events (2)
  • — I (S) $11718.75
  • — Z (S) $15625

1910.303 E01 II

Serious Gravity 10 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $15625.00 · Current $0.00 Reduced
29 CFR 1910.303(e)(1)(ii): Electric equipment was used without markings giving voltage, current, wattage, or other ratings as necessary:  On or about January 10, 2023, and at times prior thereto; in the crematory area, where the electrical panels were used to power the cremation systems and other equipment were not markings giving voltage, current, or other ratings as necessary.
Recent events (2)
  • — I (S) $0
  • — Z (S) $15625

1910.303 G01

Serious Gravity 5 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $11162.00 · Current $0.00 Reduced
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment.  a) On or about January 10, 2023, In Crematory area, where electrical panels were blocked by boxes and materials.
Recent events (2)
  • — I (S) $0
  • — Z (S) $11162

1910.305 B03 III

Serious Gravity 10 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(b)(3)(iii): Covers for boxes were not permanently marked "HIGH VOLTAGE." The marking shall be on the outside of the box cover and shall be readily visible and legible.  On or about January 10, 2023, and at times prior thereto; in the Crematory area, where the electrical panels to power the cremation systems and other equipment were not marked "HIGH VOLTAGE" on the outside of the electrical panel box.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 10 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $15625.00 · Current $0.00 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  On or about January 10, 2023, and at times prior thereto; in the Crematory area, where electrical extension cords were used as a substitute for the fixed wiring of a structure.
Recent events (2)
  • — I (S) $0
  • — Z (S) $15625

1910.334 A02 II

Serious Gravity 10 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $15625.00 · Current $11719.00 Reduced
29 CFR 1910.334(a)(2)(ii): There was a defect or evidence of damage that could have exposes an employee to injury and the defective or damaged item was not removed from service:  a) On or about January 10, 2023, and at times prior thereto;  in the Crematory area, where extension cord used to power Cyclopentane Freezers #005 and #006 had damaged insulation.
Recent events (2)
  • — I (S) $11718.75
  • — Z (S) $15625

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346427255.