Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: EQUILON ENTERPRISES LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of EQUILON ENTERPRISES LLC in 15536 RIVER RD., NORCO, LA 70079 (NAICS 325199). OSHA activity number 346495880.

Watch Equilon Enterprises LLC — free Get an email when a new federal OSHA severe-injury report for Equilon Enterprises LLC is published. One employer, no account, unsubscribe in one click.
Site address
15536 RIVER RD.
City
NORCO
State
LA
ZIP
70079
Mailing
P.O. BOX 10, NORCO, LA 70079
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325199
Employees
819
Ownership type
A

3 citations on file for this inspection.

1910.119 D03 II

Serious Gravity 10 1 instance 5 exposed
Issued
Penalty
Initial $15625.00 · Current $15625.00
29 CFR  1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices.  On or about January 30, 2023, employees were exposed to fire, explosion and toxic gas release hazards when the employer did not document that equipment, including the pressure relief systems complied with the employer's chosen RAGAGEP such as but not limited to ASME Boiler and Pressure Vessel Code, Section VIII Division 1, Part UG-134(e) when there were block valves in the relief paths and they were not positively secured in the opened position; including but not limited to block valves on the vapor vent line of the Knock Out Drum  (PV-1522).
Recent events (1)
  • — Z (S) $15625

1910.119 E05

Serious Gravity 10 1 instance 5 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.119(e)(5): The employer did not establish a system to promptly address the team's findings and recommendations; assure that the recommendations are resolved in a timely manner and that the resolution is documented; document what actions are to be taken; complete actions as soon as possible; develop a written schedule of when these actions are to be completed; communicate the actions to operating, maintenance and other employees whose work assignments are in the process and who may be affected by the recommendations or actions.   On or about January 30, 2023, employees were exposed to fire, explosion and toxic gas release hazards when the employer did not resolve the NHT 2020 PHA recommendations in a timely manner, including but not limited to Recommendation 8.5.1.1. Make 4" Block valve on vent line between PV-1522 and PV-0603 Car Sealed Open (CSO) to prevent overpressure in PV-1522.
Recent events (1)
  • — Z (S) $0

1910.119 D03 I B

Other-than-serious 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.119(d)(3)(i)(B): Piping and instrument diagrams (P&ID's);   On or about January 30, 2023, employees were exposed to fire, explosion and toxic gas release hazards when the employer did not ensure the Piping and Instrument Diagrams (P&ID) were updated to reflect the equipment including but not limited to;  Instance a) In  NHT, car seals were not shown on P&ID E-06A-0633 for 10" valves on inlet piping of PV-0604 and PV-0605.     Instance b) In 1st Stage HCU process area, pressure gauge was installed instead of plug on ?" bleeder valve as shown in P&ID E-16A-0196.
Recent events (1)
  • — Z (O) $0

View EQUILON ENTERPRISES LLC's full OSHA safety record →