Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: PRITCHARDS BAKERY, INC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of PRITCHARDS BAKERY, INC in MAIN ROAD, LEONE VILLAGE, PAGO PAGO, AS 96799 (NAICS 311811). OSHA activity number 346637994.

Watch Pritchards Bakery, INC — free Get an email when a new federal OSHA severe-injury report for Pritchards Bakery, INC is published. One employer, no account, unsubscribe in one click.
Site address
MAIN ROAD, LEONE VILLAGE
City
PAGO PAGO
State
AS
ZIP
96799
Mailing
P.O. BOX 204, PAGO PAGO, AS 96799
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311811
Employees
32
Ownership type
A

6 citations on file for this inspection.

1910.303 B02

Serious Gravity 1 2 instances 5 exposed
Issued
Penalty
Initial $4687.00 · Current $3281.00 Reduced
29 CFR  1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  A) Front counter: A relocatable power tap was used to power a warming case and a refrigerator.  Employees were exposed to electrical and fire hazards.  B) Kitchen: An extension cord was used to power the white microwave under a steel counter where scales were kept. Employees were exposed to electrical and fire hazards.
Recent events (2)
  • — I (S) $3280.9
  • — Z (S) $4687

1910.305 B02 I

Serious Gravity 1 1 instance 5 exposed
Issued
Penalty
Initial $4687.00 · Current $3281.00 Reduced
29 CFR  1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:  Kitchen: Between the Baxter ovens, there was exposed live wire on the top exhaust fan.  Employees were exposed to electrical hazards.
Recent events (2)
  • — I (S) $3280.9
  • — Z (S) $4687

1910.303 G01

Other-than-serious 2 instances 5 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:  A) In Manager's Office: A breaker panel box was blocked by a file cabinet and paper storage.   Employees were exposed to electrical hazards.  B) In kitchen, by window: Subpanel emergency shut off was blocked by a steel rack and storage.  Employees were exposed to electrical hazards.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 B01 I

Other-than-serious 2 instances 5 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasion, and openings through which conductors enter were not effectively closed.   A) Manager's Office: An unprotected electrical conductor was coming out of the circuit breaker box.  Employees were exposed to electrical hazards.  B) Kitchen: Outlet box attached to conduit, powering the large stainless steel freezer: The conductor entering the outlet box was exposed and not covered with conduit.  Employees were exposed to electrical hazards.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 G01 IV A

Other-than-serious 2 instances 5 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  A) Front lobby: The television was plugged into an extension cord used  as permanent wiring.  Employees were exposed to electrical and fire hazards.  B) By mixer #2: An extension cord powering the electronic fly catcher was used as permanent wiring to connect to the existing outlet.  Employees were exposed to electrical and fire hazards.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 G02 III

Other-than-serious 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:  Front Counter: The right warmer's cord was pulled away from the joint and strain relief was not provided.  Employees were exposed to electrical hazards.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346637994.