Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: WARBIRD TUBULAR PROCESSORS, LLC

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of WARBIRD TUBULAR PROCESSORS, LLC in 11011 SHELDON RD. INDUCTION LINE, HOUSTON, TX 77044 (NAICS 331210). OSHA activity number 346849425.

Watch Warbird Tubular Processors, LLC — free Get an email when a new federal OSHA severe-injury report for Warbird Tubular Processors, LLC is published. One employer, no account, unsubscribe in one click.
Site address
11011 SHELDON RD. INDUCTION LINE
City
HOUSTON
State
TX
ZIP
77044
Mailing
5810 WILSON RD SUITE 250, HUMBLE, TX 77396
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
331210
Employees
60
Ownership type
A

8 citations on file for this inspection.

1910.212 A05

Serious Gravity 5 1 instance 13 exposed
Issued
Penalty
Initial $7813.00 · Current $7813.00
29 CFR  1910.212(a)(5): Fan blade guards, where the periphery of the blades was less than seven feet above the floor or working level, had openings larger than one half inch:   On or about July 19, 2023, a fan used at the steel tubing induction line was missing the front guard exposing the fan blades.
Recent events (1)
  • — Z (S) $7813

1910.304 G05

Serious Gravity 5 1 instance 13 exposed
Issued
Penalty
Initial $7813.00 · Current $7813.00
29 CFR  1910.304(g)(5):The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:  On or about July 19, 2023, employees were exposed to electrical hazards while using a fan that had a plug with a missing ground prong.
Recent events (1)
  • — Z (S) $7813

1910.305 G01 IV C

Serious Gravity 5 1 instance 13 exposed
Issued
Penalty
Initial $7813.00 · Current $7813.00
29 CFR  1910.305(g)(1)(iv)(C):Flexible cords and cables were used where run through doorways, windows, or similar openings.  On or about July 19, 2023, employees were exposed to electrical hazards while using an extension cord that ran underneath a closed metal door.
Recent events (1)
  • — Z (S) $7813

1910.305 G02 III

Serious Gravity 5 1 instance 13 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(2)(iii):Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws:  On or about July 19, 2023, employees were exposed to electrical hazards while using an extension cord whose strain relief had been damaged.
Recent events (1)
  • — Z (S) $0

1910.333 C06

Serious Gravity 10 1 instance 12 exposed
Issued
Abate by
Penalty
Initial $10938.00 · Current $10938.00
29 CFR  1910.333(c)(6):Where an employee is required to handle long dimensional conductive objects in areas with exposed live parts, the employer did not institute work practices which will minimize the hazard (such as the insulation, guarding, and material handling techniques).  On or about July 19, 2023, at the steel tubing induction line, employees were exposed to an electrocution hazard while working with steel tubing without the employer instituting proper work practices.
Recent events (1)
  • — Z (S) $10938

1910.335 A01 I

Serious Gravity 10 1 instance 12 exposed
Issued
Abate by
Penalty
Initial $10938.00 · Current $10938.00
29 CFR  1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed:   On or about July 19, 2023, at the steel tubing induction machine, employees were exposed to an electrocution hazard while working with steel tubing and not wearing proper protective equipment.
Recent events (1)
  • — Z (S) $10938

1910.335 A02 II

Serious Gravity 10 1 instance 12 exposed
Issued
Abate by
Penalty
Initial $10938.00 · Current $10938.00
29 CFR 1910.335(a)(2)(ii): Protective shields, protective barriers, or insulating materials were not used to protect each employee from shock, burns, or other electrically related injuries while that employee was working near exposed energized parts which might accidently be contacted or where dangerous electric heating or arcing might occur:    On or about July 19, 2023, at the steel tubing induction machine, employees were exposed to an electrocution hazard while working with steel tubing and not utilizing protective shields, protective barriers or insulating materials.
Recent events (1)
  • — Z (S) $10938

1910.137 C02 VIII

Other-than-serious 1 instance 12 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.137(c)(2)(viii):Electrical protective equipment was not subjected to periodic electrical tests.  On or about July 19, 2023, employees were provided with rubber insulating gloves that had not been tested.
Recent events (1)
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346849425.