Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: DUCCI ELECTRICAL CONTRACTORS, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of DUCCI ELECTRICAL CONTRACTORS, INC. in 355 HIGH STREET, WILLIMANTIC, CT 06226 (NAICS 238210). OSHA activity number 346867609.

Watch Ducci Electrical Contractors, INC. — free Get an email when a new federal OSHA severe-injury report for Ducci Electrical Contractors, INC. is published. One employer, no account, unsubscribe in one click.
Site address
355 HIGH STREET
City
WILLIMANTIC
State
CT
ZIP
06226
Mailing
74 SCOTT SWAMP ROAD, FARMINGTON, CT 06032
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
200
Ownership type
A

1 citation on file for this inspection.

1926.403 B02

Deleted Other-than-serious 1 instance 1 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR  1926.403(b)(2):Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:  A) 355 High Street, Willimantic, CT, Windham High School construction project: On or about April 5, 2023, employees were using a relocatable power tap to energized multiple pieces of cord and plug equipment. The relocatable power tap was connected to a temporary outlet that was not rated for use on temporary wiring. The relocatable power tap was UL listed for household use only.  B) 355 High Street, Willimantic, CT, Windham High School construction project: On or about April 5, 2023, temporary electrical wiring used in the gymnasium were fastened from one point to the next at approximate intervals of 40 feet. The NEC Article 334 requires that temporary wiring be secured at intervals not to exceed 4.5 feet.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View DUCCI ELECTRICAL CONTRACTORS, INC.'s full OSHA safety record →