HULBERT, OK —
OSHA Inspection: OG GREENHOUSE, LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of OG GREENHOUSE, LLC in 4025 W 730 RD, HULBERT, OK 74441 (NAICS 111998). OSHA activity number 347076531.
Where did this inspection happen?
- Establishment
- OG GREENHOUSE, LLC
- Site address
- 4025 W 730 RD
- City
- HULBERT
- State
- OK
- ZIP
- 74441
- Mailing
- 4025 W 730 RD, HULBERT, OK 74441
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 111998
- Employees
- 4
- Ownership type
- A
Citations
12 citations on file for this inspection.
1910.37 B02
- Issued
- Abate by
- Penalty
- Initial $2074.00 · Current $1244.00 Reduced
General-duty citation text
29 CFR 1910.37(b)(2): Each exit was not clearly visible or marked by a sign reading, "EXIT". On or about November 23, 2023, at the facility, none of the doors used as an exit out of the facility were identified with a sign stating, Exit". This exposes employees to a caught-in fire hazard.
Recent events (2)
- — I (S) $1244.4
- — Z (S) $2074
1910.101 B
- Issued
- Abate by
- Penalty
- Initial $2765.00 · Current $1659.00 Reduced
General-duty citation text
29 CFR 1910.101(b): The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks were not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in 29CFR 1910.6. Compressed gas cylinders were not stored in accordance with Compressed Gas Association Pamphlet P-1-1965. a. On or about November 1, 2023, a compressed cylinder of Carbon Dioxide was observed unsecured at the facility, exposing employees to fire hazards. b. On or about November 1, 2023, a small cylinder of propane was observed laying on the floor at the facility, exposing employees to fire hazards.
Recent events (2)
- — I (S) $1659
- — Z (S) $2765
1910.151 C
- Issued
- Abate by
- Penalty
- Initial $4148.00 · Current $2489.00 Reduced
General-duty citation text
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use. On or about November 1, 2023, employees were working with corrosive chemicals and were not provided suitable facilities for quick drenching or flushing of the eyes and body. This exposes the employees to chemical hazards.
Recent events (2)
- — I (S) $2488.8
- — Z (S) $4148
1910.303 B02
- Issued
- Abate by
- Penalty
- Initial $2074.00 · Current $1244.00 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled equipment was not used or installed in accordance with any instructions included in the listing or labeling. On or about November 1, 2023, at the grow facility, a relocatable power strip was observed secured to other electrical cords, exposing employees to electrical hazards.
Recent events (2)
- — I (S) $1244.4
- — Z (S) $2074
1910.303 E01 II
- Issued
- Abate by
- Penalty
- Initial $2074.00 · Current $1244.00 Reduced
General-duty citation text
29 CFR 1910.303(e)(1)(ii): Markings giving voltage, current, wattage, or other ratings was not on electrical equipment. On or about February 6, 2023, at the facility, an electrical panel was not marked with its ratings. This exposes employees to electrical hazards.
Recent events (2)
- — I (S) $1244.4
- — Z (S) $2074
1910.305 A02 X
- Issued
- Abate by
- Penalty
- Initial $4148.00 · Current $2489.00 Reduced
General-duty citation text
29 CFR 1910.305(a)(2)(x): Flexible cords and cables were not protected from accidental damage, as might be caused, for example, by sharp corners, projections, and doorways or other pinch points. On or about November 23, 2023, at the top of a set of double doors between hallway#2 and the room#5 storage area, a flexible metal conduit with flexible electrical wiring was ran through top of the double doors, exposing employees to an electrical hazard.
Recent events (2)
- — I (S) $2488.8
- — Z (S) $4148
1910.305 B01 II
- Issued
- Abate by
- Penalty
- Initial $2765.00 · Current $1659.00 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Openings through which conductors entered cutout boxes, cabinets, or fittings were not effectively closed. a. On or about November 23, 2023, in small plant room#3, a pendant box located above a set of double doors was not effectively closed and was missing its knockouts. This exposes employees to an electrical hazard. b. On or about November 23, 2023, in hallway#2, a light switch/outlet combo pendant box was not effectively closed and was missing its knockouts. This exposes employees to an electrical hazard.
Recent events (2)
- — I (S) $1659
- — Z (S) $2765
1910.305 B02
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(b)(2): All junction boxes and each outlet box was not provided with an approved cover, faceplate, or fixture canopy. a. On or about November 23, 2023, in hallway#1, a light switch fixture did not have an approved cover, exposing employees to an electrical hazard. b. On or about November 23, 2023, in hallway#1, an outlet fixture did not have an approved cover, exposing employees to an electrical hazard. c. On or about November 23, 2023, in hallway#2, a light switch/outlet fixture did not have an approved cover, exposing employees to an electrical hazard. d. On or about November 23, 2023, in hallway#2, a light switch fixture did not have an approved cover, exposing employees to an electrical hazard.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Abate by
- Penalty
- Initial $2074.00 · Current $1244.00 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure. a. On or about November 23, 2023, in hallway#1, three green extension cords were substituted for fixed wiring, exposing employees to electrical hazards. b. On or about November 23, 2023, in hallway#2, an orange extension cord was substituted for fixed wiring, exposing employees to electrical hazards.
Recent events (2)
- — I (S) $1244.4
- — Z (S) $2074
1910.305 G01 IV B
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and/or cables were run through holes in walls, ceilings, or floors. a. On or about November 23, 2023, in hallway#1, where three green extension cords were plugged into a relocatable power tap and ran through holes in walls, exposing employees to electrical hazards. b. On or about November 23, 2023, in hallway#2, an orange extension cord was plugged into a outlet and ran through a hole in the wall, exposing employees to electrical hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G02 III
- Issued
- Abate by
- Penalty
- Initial $2009.00 · Current $1205.00 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws. a. On or about November 23, 2023, in hallway #2, a yellow electrical cord was in use and was not provided with strain relief, exposing employees to an electrical hazard. b. On or about November 23, 2023, between hallway #2 and the room #5 storage area, a flexible conduit was in use and was not provided with strain relief, exposing employees to an electrical hazard.
Recent events (2)
- — I (S) $1205.4
- — Z (S) $2009
1910.334 A03 I
- Issued
- Abate by
- Penalty
- Initial $2765.00 · Current $1659.00 Reduced
General-duty citation text
29 CFR 1910.334 (a)(3)(i): A flexible cord used with grounding type equipment did not contain an equipment grounding conductor. On or about November 23, 2023, in hallway #2, the metal casing on a floor fan was energized. The floor fan electrical wiring did not have a grounding prong, exposing employees to electrical hazards.
Recent events (2)
- — I (S) $1659
- — Z (S) $2765
More inspections in this industry (NAICS 111998)
HARRISON, OH—2026-07-10
WEBER FAMILY FARMS LLC
PASCO, WA—2026-07-07
WA317991991 - BACK FORTY ACRES L L C
MORGAN HILL, CA—2026-07-01
GEORGE CHIALA FARMS, INC.
BRAWLEY, CA—2026-06-26
NATURE FRESH FARMS, LLC
GRANDVIEW, WA—2026-06-25
WA317991848 - WYCKOFF FARMS INCORPORATED
More inspections in OK
MADILL, OK—2026-07-08
MID AMERICAN STEEL & WIRE CO., LLC
SEILING, OK—2026-06-26
GORE ENERGY
ADA, OK—2026-06-25
PAN AMERICA ELECTRIC , INC.
ADA, OK—2026-06-25
CITATION OIL & GAS CORPORATION
EDMOND, OK—2026-06-23
BRICK EXPERTS INC.
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347076531.