Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: SOUTH GEORGIA MEDICAL CENTER, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of SOUTH GEORGIA MEDICAL CENTER, INC. in 2501 NORTH PATTERSON ST., VALDOSTA, GA 31602 (NAICS 622110). OSHA activity number 347115917.

Watch South Georgia Medical Center, INC. — free Get an email when a new federal OSHA severe-injury report for South Georgia Medical Center, INC. is published. One employer, no account, unsubscribe in one click.
Site address
2501 NORTH PATTERSON ST.
City
VALDOSTA
State
GA
ZIP
31602
Mailing
2501 NORTH PATTERSON ST., VALDOSTA, GA 31602
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
622110
Employees
600
Ownership type
A

6 citations on file for this inspection.

1910.22 A01

Serious Gravity 1 1 instance 14 exposed
Issued
Abate by
Penalty
Initial $6913.00 · Current $4148.00 Reduced
29 CFR  1910.22(a)(1): The employer did not ensure that all places of employment, passageways, storerooms, service rooms, and walking-working surfaces are kept in a clean, orderly, and sanitary condition:  a)  In the supply warehouse and on the loading dock, located at 2501 North Patterson St., Valdosta, GA, on or about November 20, 2023, the employer exposed employees to struck-by and trip hazards in that supplies and equipment overcrowded the warehouse and loading dock and stored in a manner preventing safe access to them.
Recent events (2)
  • — I (S) $4147.8
  • — Z (S) $6913

1910.176 B

Serious Gravity 1 1 instance 14 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.176(b):  Material stored in tiers was not stacked, blocked, interlocked or limited in height so that it was stable and secure against sliding and collapse:  a)  In the supply warehouse, located at 2501 North Patterson St., Valdosta, GA, on or about November 20, 2023, the employer exposed employees to struck-by hazards, in that materials and supplies were not securely stacked.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.36 D01

Serious Gravity 5 1 instance 14 exposed
Issued
Penalty
Initial $11524.00 · Current $6914.00 Reduced
29 CFR  1910.36(d)(1):  Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge:  a)  In the supply warehouse, located at 2501 North Patterson St., Valdosta, GA, on or about November 20, 2023, the employer exposed employees to fire hazards, in that two emergency exits were magnetically locked and required wall mounted electrically powered push buttons, that would become inoperable in the event of a power outage, to be activate in order to open the doors.
Recent events (2)
  • — I (S) $6914.4
  • — Z (S) $11524

1910.36 G02

Serious Gravity 5 1 instance 14 exposed
Issued
Abate by
Penalty
Initial $9218.00 · Current $5531.00 Reduced
29 CFR  1910.36(g)(2):  Exit access(es) were not at least 28 inches (71.1 cm) wide at all points:  a)  In the supply warehouse, located at 2501 North Patterson St., Valdosta, GA, on or about November 20, 2023, the employer exposed employees to fire hazards, in that exit accesses were partially blocked and did not allow employees to freely exit the building.
Recent events (2)
  • — I (S) $5530.8
  • — Z (S) $9218

1910.37 A03

Serious Gravity 5 1 instance 14 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.37(a)(3):  Exit route(s) were not kept free and unobstructed:  a)  In the supply warehouse, located at 2501 North Patterson St., Valdosta, GA, on or about November 20, 2023, the employer exposed employees to entrapment hazards, in that exit accesses were partially blocked and did not allow employees to freely exit the building.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.165 E

Other-than-serious 1 instance 14 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.165(e):  Manually operated actuation devices for use in conjunction with employee alarms were not unobstructed, conspicuous and readily accessible:  a)  In the supply warehouse, located at 2501 North Patterson St., Valdosta, GA, on or about November 20, 2023, the employer exposed employees to entrapment and health hazards, in that manually operated fire alarms were partially blocked to prevent employee use in the event of an emergency.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

CFSE