AURORA, CO —
OSHA Inspection: TRIPLE FIVE VENTURES, LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of TRIPLE FIVE VENTURES, LLC in 10 SOUTH POTOMAC STREET, AURORA, CO 80012 (NAICS 812910). OSHA activity number 347264228.
Where did this inspection happen?
- Establishment
- TRIPLE FIVE VENTURES, LLC
- Site address
- 10 SOUTH POTOMAC STREET
- City
- AURORA
- State
- CO
- ZIP
- 80012
- Mailing
- 10 SOUTH POTOMAC STREET, AURORA, CO 80012
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 812910
- Employees
- 38
- Ownership type
- A
Citations
10 citations on file for this inspection.
1910.37 A03
- Issued
- Abate by
- Penalty
- Initial $4839.00 · Current $2640.00 Reduced
General-duty citation text
29 CFR 1910.37(a)(3):Exit route(s) were not kept free and unobstructed: (a) On or about February 7, 2024, and at times prior, the employer, exposed it employees to fire hazards by not ensuring that the exit routes throughout the facility were kept clear from obstructions such as extension cords, dog crates in the walkway, and fans in the walkways.
Recent events (2)
- — I (S) $2640
- — Z (S) $4839
1910.37 B05
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.37(b)(5):Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g. closet): (a) On or about February 7, 2024, and at times prior, the employer, exposed employees to fire hazards in that many blocked and locked doors located in the back of the boarding facility were marked as EXITS but no access could be gained from any doors to the backyard of the facility.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 B02
- Issued
- Abate by
- Penalty
- Initial $6453.00 · Current $3000.00 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: (a) On or about February 7, 2024, and at times prior, employees were exposed to electrical hazards in that extension cords were not used or installed in accordance listed and labeled instructions, extension cords were daisy chained.
Recent events (2)
- — I (S) $3000
- — Z (S) $6453
1910.305 G01 IV A
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: (a) On or about February 7, 2024, and at times prior, employees were exposed to electrical hazards in that extension cords, and grounding taps were used as permanent installations around the outside of the facility.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B02 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(b)(2)(i):Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: (a)On or about February 7, 2024, and at times prior, employees were exposed to electrical hazards in that multiple outlets throughout the facility were missing faceplates.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.334 A01
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.334(a)(1):Flexible electric cords were fastened with staples or otherwise hung in such a fashion as could damage the outer jacket or insulation: (a) On or about february 7, 2024, and at times prior, the employer, Triple Five Ventures dba Boarding and Beyond, exposed its employees to electrical hazards in that extension cords were hung in doorways and jams, hung and tied to aluminum metal fencing in the yard, and laying on the ground outside while zip tied together in wet conditions.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.22 A01
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.22(a)(1): The employer did not ensure that all places of employment, passageways, storerooms, service rooms, and walking-working surfaces are kept in a clean, orderly, and sanitary condition. (a) On or about February 7, 2024, and at times prior, the employer, exposed its employees to slip ad trip hazards by not ensuring all places of employment such as the grooming room, hallways, and kitchen were kept clean and maintained in sanitary conditions. Such areas had clumps of dog hair on electrical outlets and cables, dog food on the floors, and water puddles throughout the grooming room and kitchen.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.22 A03
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.22(a)(3): The employer did not ensure that walking-working surfaces are maintained free of hazards such as sharp or protruding objects, loose boards, corrosion, leaks, spills, snow, and ice. (a) On or about February 7, 2024, and at times prior, the employer, exposed employees to slip, trip, and fall hazards in that loose and water damaged flooring located in the kitchen are sinking in making an uneven ground to work on.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.141 A05
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.141(a)(5):A continuing and effective extermination program was not instituted where rodents, insects or other vermin were detected: (a) On or about February 7, 2024, and at times prior, the employer, exposed its employees to various health hazards associated with fecal matter from rodents, by not ensuring an effective extermination program was implemented to reduce the amount of vermin entering into the facility.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.157 E03
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.157(e)(3):Portable fire extinguishers were not subjected to an annual maintenance check: (a) On or about February 7, 2024, and at times prior, the employer did not ensure that fire extinguishers were maintained in an annual basis.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 812910)
AMERICAN FORK, UT—2026-07-08
ROCKY MOUNTAIN K9
PORTLAND, OR—2026-06-24
317744569 - BSUE DOGS CORP
SAN JOSE, CA—2026-06-19
SAN JOSE ANIMAL CARE CENTER
SAN ANDREAS, CA—2026-06-10
CALAVERAS COUNTY
BROWNSVILLE, TN—2026-06-08
BROWNSVILLE - ANIMAL SHELTER
More inspections in CO
CASTLE ROCK, CO—2026-07-10
MASTER MAGNETICS, INC.
STRASBURG, CO—2026-07-08
JUNIOR ROOFING LLC
FORT COLLINS, CO—2026-07-08
EDWARDS SEMICONDUCTOR SOLUTIONS LLC
CENTENNIAL, CO—2026-07-08
JORDY CONSTRUCTION
HIGHLANDS RANCH, CO—2026-07-08
HOWELL CONSTRUCTION
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347264228.