Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: DEPARTMENT OF ENERGY, WESTERN AREA POWER ADMINISTRATION (WAPA), MAINTENANCE FACILITY

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of DEPARTMENT OF ENERGY, WESTERN AREA POWER ADMINISTRATION (WAPA), MAINTENANCE FACILITY in 7940 SORENTO RD, ELVERTA, CA 95626 (NAICS 221121). OSHA activity number 347273567.

Watch Department OF Energy, Western Area Power Administration (Wapa), Maintenance Facility — free Get an email when a new federal OSHA severe-injury report for Department OF Energy, Western Area Power Administration (Wapa), Maintenance Facility is published. One employer, no account, unsubscribe in one click.
Site address
7940 SORENTO RD
City
ELVERTA
State
CA
ZIP
95626
Mailing
7940 SORENTO RD, ELVERTA, CA 95626
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221121
Employees
18
Ownership type
D

4 citations on file for this inspection.

1910.253 B04 III

Serious Gravity 1 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour:  In the Linemen shop and the electricians work area several Oxygen cylinders and fuel gas cylinders (Acetylene) were in storage and were not separated as required by the regulation.
Recent events (1)
  • — Z (S) $0

1910.303 B02

Serious Gravity 1 2 instances 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listed or labeling.    In the breakroom: The Inland Surge Guard with 6 outlets and being used as an extension cord to energize a Panasonic microwave (Serial No. 6A9305 1038) was not listed, labeled or certified for this application.   Electricians work area: The 4-inch square metal electrical box with knockouts and with a duplex receptacle attached to the end of the black flexible cord was not securely affixed to any surface. The assembly was used  as an extension cord to energize portable power tools and was not listed, labeled or certified for this application.
Recent events (1)
  • — Z (S) $0

1910.215 B09

Other-than-serious 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.215(b)(9):29 CFR 1910.215(b)(9):  The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch.  Electrician work area: An 8 inch JET Equipment bench grinder (Serial No. 6046740) tongue guards was not adjusted to 1/4 of an inch. The tongue guards opening was about one inch. Employees were exposed to face injuries.
Recent events (1)
  • — Z (O) $0

1910.305 B02 I

Other-than-serious 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:  In the Electrician Foreman Office: An outlet was incomplete installation and energized did not have the faceplate installed to cover the energized electrical parts.
Recent events (1)
  • — Z (O) $0

PSE&G

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347273567.