Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: BYERLY GROUP III INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of BYERLY GROUP III INC. in 1560 AUTO MALL LOOP, COLORADO SPRINGS, CO 80920 (NAICS 441110). OSHA activity number 347309528.

Watch Byerly Group III INC. — free Get an email when a new federal OSHA severe-injury report for Byerly Group III INC. is published. One employer, no account, unsubscribe in one click.
Site address
1560 AUTO MALL LOOP
City
COLORADO SPRINGS
State
CO
ZIP
80920
Mailing
1560 AUTO MALL LOOP, COLORADO SPRINGS, CO 80920
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
441110
Employees
40
Ownership type
A

2 citations on file for this inspection.

1910.215 B09

Serious Gravity 1 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $4113.00 · Current $2468.00 Reduced
29 CFR 1910.215(b)(9): The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch:  (a) On or before 2/28/2024, the employer did not ensure that the gap between the abrasive wheel and the tongue guard did not exceed one fourth of an inch. The tongue guard was all the way up. This condition exposed employees to flying chips and sparks.
Recent events (2)
  • — I (S) $2467.8
  • — Z (S) $4113

1910.303 G01

Other-than-serious 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:  (a) On or before 2/28/2024, the employer did not ensure that all electrical service panels had at least 30 inches of clearance for ready and safe access. This condition exposed employees to electric shock and fire hazards.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347309528.