ANDREWS, TX —
OSHA Inspection: YMH, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of YMH, INC. in SENDERO RIG #103 11 MILES NE DIRECTION FROM GARDENDALE TX, ANDREWS, TX 79714 (NAICS 213112). OSHA activity number 347374753.
Where did this inspection happen?
- Establishment
- YMH, INC.
- Site address
- SENDERO RIG #103 11 MILES NE DIRECTION FROM GARDENDALE TX
- City
- ANDREWS
- State
- TX
- ZIP
- 79714
- Mailing
- 4830 EAST SEMINOLE HIGHWAY, HOBBS, NM 88240
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 213112
- Employees
- 8
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.304 G05
- Issued
- Abate by
- Penalty
- Initial $4702.00 · Current $4702.00
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: a) On or about March 27, 2024, Trailer #2226; employee(s) were utilizing the trailer which was not effectively grounded. The trailer was used for sleeping quarters. b) On or about March 27, 2024, Mud Engineer's Trailer #6967; employee(s) were utilizing the trailer which was not effectively grounded. The trailer was used for sleeping quarters. c) On or about March 27, 2024, Directional Driller's Trailer #6971; employee(s) were utilizing the trailer which was not effectively grounded. The trailer was used for sleeping quarters. d) On or about March 27, 2024, Command CenterTrailer #9916; employee(s) utilized the trailer which was not effectively grounded. The trailer was used for daily meetings. e) On or about March 27, 2024, Dragon Water Tank; employee(s) were utilizing the water tank which was not effectively grounded. The water tank was used to supply water to the trailer sewage systems.
Recent events (1)
- — Z (S) $4702
1910.305 B01 II
- Issued
- Abate by
- Penalty
- Initial $440.00 · Current $440.00
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: On or about March 27, 2024, outside of the Night Company Man's Trailer #2226; employee(s) utilized the trailer's air conditioning (A/C) unit powered by an electrical circuit box with an unused opening underneath while the A/C unit was being used.
Recent events (1)
- — Z (O) $440
1910.305 B02 I
- Issued
- Abate by
- Penalty
- Initial $440.00 · Current $440.00
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: a) On or about March 27, 2024, on front side of Day Company Man's Trailer #3364, employee(s) utilized a 2-outlet outdoor receptacle that did not have a faceplate while using the receptacle to power equipment. b) On or about March 27, 2024, on the side of the Command Center Trailer #5651, employee(s) utilized a 2-outlet outdoor receptacle that did not have a faceplate while using the receptacle to power equipment. c) On or about March 27, 2024, on the front side of Mud Engineer'sTrailer #6967, employee(s) utilized a 2-outlet outdoor receptacle that did not have a faceplate while using the receptacle to power equipment. d) On or about March 27, 2024, on the side of the Directional Driller Trailer #6971, employee(s) utilized a 2-outlet outdoor receptacle that did not have a faceplate while using the receptacle to power equipment.
Recent events (1)
- — Z (O) $440
1910.305 G02 III
- Issued
- Abate by
- Penalty
- Initial $440.00 · Current $440.00
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: a) On or about March 27, 2024, outside of the Night Company Man's Trailer #2226; employee(s) were utilizing the trailer's air conditioning (A/C) unit with a power cable that had a broken strain relief going into the main electrical circuit box. b) On or about March 27, 2024, outside of Mud Engineer's Trailer #6967; employee(s) were utilizing the trailer's air conditioning (A/C) unit with a power cable that had a broken strain relief going into the main electrical circuit box. c) On or about March 27, 2024, outside of Directional Driller's Trailer #6971; employee(s) were utilizing the trailer's air conditioning (A/C) unit with a power cable that had a broken strain relief going into the main electrical circuit box.
Recent events (1)
- — Z (O) $440
More inspections in this industry (NAICS 213112)
COLLBRAN, CO—2026-07-14
LARAMIE ENERGY
SEILING, OK—2026-06-26
GORE ENERGY
SCIO, OH—2026-06-25
AMPRO WELL SERVICES, LLC
MIDLAND, TX—2026-06-23
JAT PARTNER LOGISTICS LLC
STUART, OK—2026-06-18
HEARTLAND ENERGY SOLUTIONS, LLC
More inspections in TX
WICHITA FALLS, TX—2026-07-16
UNITED RENTALS, INC.
SAN MARCOS, TX—2026-07-16
CASA MECHANICAL SERVICES, LTD.
CLARKSVILLE, TX—2026-07-15
SEQUOIAS TREE EXPERT LLC
EL PASO, TX—2026-07-15
SURE STEEL
CORPUS CHRISTI, TX—2026-07-15
NORTH STAR ENERGY SOLUTIONS LLC
Source